MAN3186 - TITANUS MICRO
•
SENS®
170
1 a
2
3
b
7.1.1 Plug
‑
and
‑
play commissioning
In the case of plug-and-play commissioning, the default settings are not
changed.
Image 118:
Inserting the detection unit in the device base
1
Housing cover with detection unit
1a
Interior view
1b
Front view
2
X4 (pin 1
… 3) on circuit board
3
Device base
► Reconnect jumper X4 (pin 1,2 or 2,3).
► Check the type of calibration against the test record.
► Insert the detection unit into the device base. Pay attention to the
mechanical coding, which prevents the TITANUS MICRO·SENS® from
being twisted.
➜
Air flow calibration is carried out automatically, independent of the air
pressure. An air pressure-dependent calibration can only be carried
out using diagnostic software. Make sure that the air flow is not
affected during the initialisation phase.
► Make sure that the operating LED on the unit is flashing.
► Make sure that the operating LED is permanently illuminated after the
initialisation phase.