MAN3186 - TITANUS MICRO
•
SENS®
178
No standard conformity in case of improper project planning
For project planning that complies with AS ISO 7240-20, the delay time must
be set to ≤ 300 seconds.
NOTE
7.2.4 Setting the fault delay
In monitoring areas with temporary fault variables (e.g. air pressure
fluctuations), other delay times should be set according to the duration of the
fault variables.
Detection unit
Fault warning delay
Default setting
[s]
Setting levels
[s]
DM
‑
TMx
‑
xx
‑
10
‑
x
30 s - 60 min
100
1
DM
‑
TMx
‑
xx
‑
50
‑
x
30 s - 60 min
100
1
Table 54:
Fault warning delay
7.2.5 Setting the pre-alarm threshold (optional)
Changing the pre-alarm threshold for the option "Main alarm after ROOM
IDENT" is possible as a percentage of the main alarm sensitivity.
Detection unit
Pre-alarm threshold
[%]
Default setting
[%]
Setting levels
[%]
DM
‑
TMx
‑
xx
‑
10
‑
x
10 - 80
60
1
DM
‑
TMx
‑
xx
‑
50
‑
x
10 - 80
60
1
Table 55:
Pre-alarm threshold
7.2.6 Activating or deactivating the memory fault display
The display for collective faults (air flow and detection unit fault) can
optionally be set to "saving" or "non-saving".
Detection unit
Saving fault activated
Default setting
DM
‑
TMx
‑
xx
‑
10
‑
x
off - on
off
DM
‑
TMx
‑
xx
‑
50
‑
x
off - on
off
Table 56:
Saving fault display