MAN3186 - TITANUS MICRO
•
SENS®
196
Example
For devices with a serial number greater than 187000, the air purge time
must be calculated according to the following formula:
Variable/
constant
Unit
Description
s
Required purge time
s
Maximum determined aspiration time
The calculated purge time is to be rounded up to whole seconds and the
value thus obtained is to be entered under "Blow out time".
For all devices where the serial number is less than 187000, select the
purge time according to the following table (intermediate values = next
higher value). Add 1 s to the respective purge time for each pipe bend or
elbow.
Pipe length [m]
Purge time [s]
10
80
15
97
20
113
25
130
30
147
35
163
40
180
Table 62:
Purge time
► Enter the voltage of the purge fan.
"Purge fan" web help
In order to achieve the shortest possible and thus optimum purge time, it is
recommended to leave the voltage of the purge fan at 13.5 V (default).
However, in systems where the capacity of the available power supply has
already reached its limits and/or where there is increased voltage loss on the
device supply cable due to long cable lengths, it may make sense to reduce
the voltage of the purge fan.