background image

Side view

US 16m

PIR ø8m

2.5m

PIR Small Motion
ø4 m = 12,5 m

2

PIR Body Motion
ø8 m = 50 m

2

Ultrasonic Small Motion
10 x 8 m  (Oval) = 66 m

2

Ultrasonic Body Motion
16 x 10 m (Oval) = 138 m

2

Top view

US 10m

US

 8m

360°

PIR
ø4m

PIR
ø8m

US

 10m

US 16m

Open office

14m

8m

Classroom

Conference room

12m

7.5m

10m

8m

Fig. 2:

14m

8m

20%
overlap

Fig. 3:

120

47

60

34

30

109

64

Fig. 4:

Jumper

L

N

D2

D1

R

M/S

41-800 Presence detector PLUS

L

N

Fig. 1:

> 2m

> 2m

>

 

2m

Air
duct

W

W

Summary of Contents for niko 41-80

Page 1: ... m Oval 66 m2 Ultrasonic Body Motion 16 x 10 m Oval 138 m2 Top view US 10m US 8m 360 PIR ø4m PIR ø8m US 10m US 16m Open office 14m 8m Classroom Conference room 12m 7 5m 10m 8m Fig 2 14m 8m 20 overlap Fig 3 120 47 60 34 30 109 64 Fig 4 Jumper L N D2 D1 R M S 41 800 Presence detector PLUS L N Fig 1 2m 2m 2m Air duct W W ...

Page 2: ...ust be carried out by qualified electricians Contact a qualified electrician in the event of fault or breakdown Reserving the right to make changes Achtung Einbau und Montage elektrischer Geräte dürfen nur durch Elektrofachkräfte erfolgen Wenden Sie sich bei Störungen bzw Ausfall an einen Elektrofachkraft Änderungen vorbehalten Avertissement L installation et le montage d appareils électriques doive...

Page 3: ...at the detector is mounted on the ceiling If the detector is mounted suspended from the ceiling the ultrasonic range is decreased Location The recommended installation height of this detector is 2 3m and 2 5m is the optimal mounting height The detection range of PIR sensor can reach up to ø8m and ultrasonic sensor is an oval shape of 8m x 10m with small movement i e hand wave and an oval shape of ...

Page 4: ...f Learn actual lux is out of the range of 10 1000 lux the LED s in the presence detector will after 10sec Àash quickly for 5sec to indicate that Learn actual lux was unsuccessfully In that case the following values will be used Lux level is above 1000 lux the presence detector will use 1000 lux as lux setting Lux level is below 10 lux the presence detector will use 10 lux as lux setting Memo The M...

Page 5: ... false triggering and remove them from the detectors range 3 Refer to wiring diagrams See Fig 4 Fig 6 Problem Red LED does not turn on Possible cause 1 PIR is not chose as the triggering method 2 The movement is out of the PIR detection range 3 The lens mask is used an it coveres the movement Proposed solution 1 Choose PIR sensor as the triggering method 2 The movement should be in the valid detec...

Page 6: ... supply 230 V 10 50 Hz Power consumption 2 W Output Relay contact NO 230 V ȝ 10 A potential free Load Incandescent lamps 2300 W Fluorescent tubes not Compensated 1200 VA Halogen incandescent lamps 2300 W Energy saving bulbs 58 x 18 W Max compensation capacity 140 ȝF Max inrush current 165 A 20 m sec Performance Lux range 10 1000 lux Time delay 1 30 min Detection range 360 Ultrasonic 10 x 16 meter ...