Risk of injury due to flammable liquids and vapours
Formation of explosive/highly flammable vapour/air mixtures is possible.
Injuries to health due to direct or indirect contact.
► Prior to processing, observe the safety notes of the manufacturer.
WARNING
6.24 Installation of the condensate separator
The condensate separators are used to collect and drain precipitated water
vapour and condensate from the pipe system.
6.24.1 Condensate separator type KA-1
Image 114:
Condensate separator type KA-1
Install the condensate separator at the lowest point of the pipe system and
upstream of the air filter (optional) and the TITANUS MICRO·SENS®.
► Place the condensate separator in the intended position and fasten it
using two 40 mm pipe clips.