TITANUS MICRO·SENS®
5.3.2.2 M-pipe system
Image 52:
M-pipe system, e.g. for equipment monitoring
Limit values
Min. distance between device and T-piece
2 m
Max. distance between device and T-piece
20 m
Max. branch lengths
16.5 m
Max. overall pipe length of pipe Ø 25 mm
50 m
Max. overall pipe length with fan voltage 9.0 V; pipe
∅
25 mm
40 m
Min. distance between two aspiration apertures (d)
0.1 m
Max. distance between two aspiration apertures (d)
4 m
Max. number of aspiration apertures (n) per pipe system
6 units
Table 36:
Limit values of M-pipe system for simplified pipe project planning
Number of aspiration
apertures
3
6
Ø aspiration aperture
[mm]
1)
5.0
3.6
Table 37:
Diameter of the aspiration apertures for the M-pipe system with simplified
project planning
1)
Punching diameter of the aspiration
‑
reducing film sheet