8 Maintenance
You will find information about maintenance in this section.
The test record must be completed during the maintenance (see chapter
"Appendix"). The test record is required for the subsequent evaluation of the
data (e.g. air flow value, air pressure and temperature during maintenance).
8.1 Maintenance intervals
Maintenance includes regular inspections. The TITANUS MICRO·SENS® is
initially inspected during commissioning and then annually.
The following checks must be performed during each maintenance:
Type of test
Further information see chapter
…
Visual inspection
“Visual inspection”
Checking the detection unit and alarm
transmission
“Checking the detection unit and alarm signal
transmission”
Checking the pipe system
“Pipe system check”
Checking the air flow calibration
“Checking the air flow sensor calibration”
Testing ROOM IDENT and response indicator
“Checking ROOM·IDENT and response
indicators”
Checking the air flow monitoring and fault
signal transmission
“Checking the air flow monitoring and fault
signal transmission”
Table 65:
Maintenance intervals
In addition to annual maintenance, the national provisions or standards
regarding the purpose of use as well as any requirements specific to the
application must be considered.
8.2 Visual inspection
Check whether...
▪ the pipe system is firmly in place and undamaged if it is easy to access.
▪ the aspiration apertures of the pipe system are clear.
▪ the aspiration pipe and connecting cables are securely connected.
▪ the TITANUS MICRO·SENS® is undamaged.
Summary of Contents for Ampac TITANUS MICRO-SENS