MAN3186 - TITANUS MICRO
•
SENS®
144
Risk of injury due to flammable liquids and vapours
Formation of explosive/highly flammable vapour/air mixtures is possible.
Injuries to health due to direct or indirect contact.
► Prior to processing, observe the safety notes of the manufacturer.
WARNING
Air flow reducers must not be attached to the air sampling hose.
► Cut the aspiration hose to length with a metal saw / pipe shears or a
pipe cutter (38 mm).
► Deburr the cut edges.
► Remove any shavings from the cut edges.
► Remove dirt and grease from the bonding surfaces using Tangit cleaner.
► Glue the aspiration hose transitions so they are airtight with the
respective fittings using Tangit glue.
Type SCH-PG16
► Glue the aspiration hose into the hose screw
connection type SCH
‑
PG16
‑
VO using ABS glue.
► Twist the hose screw connection into the relevant pipe with inner thread
type ABSR
‑
2518
‑
PG16.
Type SCH-P-25
► Glue the aspiration hose with UPVC adhesive in fittings/sleeves of
a pipe system with a 25 mm outer diameter.
► After completing the pipe system, check for the following:
▪ Leaks (e.g. due to damage)
▪ Incorrect connections
▪ Correct aspiration aperture project planning