Features 

—

 Intelligent signal-processing and communication 

with integrated microprocessor. 

—

  Intelligent algorithm ensures quick response with 

reduced false alarm. 

—

  Three sensitivity levels. 

—

  High sensitivity, reliable performance.   

—

  Dust-proof, damp-proof and corrosion-proof. 

Description 

DC-9104Exd is a light-sensitive detector that detects 

fire by picking up the ultraviolet light from flaming 

material. It’s designed for areas where an open fire is 

liable to occur with large amount of radiation and no 

smoldering stage, or where quick response to a fire is 

required. This detector can be applicable to zone 1 

and 2 of explosive areas. 

The detector is able to work either in addressable 

mode connecting with GST intelligent fire alarm 

control panel to transmit signal through detection loop 

or in non-addressable mode connecting to 24VDC 

power supply to transmit signal by outputting different 

resistance values.   

Connection and Wiring 

Screened 2-core cable with cross section 1mm

2

 or 

above, and outer diameter

 φ

8 mm is required for field 

wiring. Please follow the steps below: 

(1) Rotate down the back cover and the cable 

fastening nut. 

(2) Thread a proper length of the cable through the 

fastening nut, metal washer and joint washer in 

sequence. 

(3) Peal away the outer layer of the cable with 5mm of 

metal core exposed, rotate in the cable together 

with the joint washer, metal washer and the 

fastening nut into the detector housing, and fasten 

the nut using a spanner. 

(4) Connect the cables to corresponding terminals of 

the detector, and the screen layer to the safety 

earth position inside the housing.   

(5) Fasten the back cover with tools, and make sure 

the detector is earthed through its safety earth 

position on the cover.   

Installation 

(1) Fig. 1 is the schematic diagram for installing the 

detector. 

(2) Please check the following after installation: 

z

  There shall not be any crack or air bubbles. 

The back cover and the detector shall be 

securely fastened. 

z

  There shall not be any scratch or crack on the 

detecting window. 

z

  There shall be joint washer in the wiring hole. 

z

 The joint washer matches with the cable 

diameter. 

z

  The cable fastening nut is locked. 

z

  There is earth cable at the “earth” mark. 

z

  The detection window shall face the protected 

area.  

Note: The detector shall be installed in compliance 
with relative installation codes.  Make sure the 
housing is in good condition.

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1 

Application 

Schematic of system connection is shown in Fig. 2 

(addressable mode) and Fig .3 (non-addressable 

mode).  

 

 

 

 

 

Fig. 2 

 
 
 
 
 
 
 

Fig. 3 

Operation  

In addressable mode, Terminal Z1 and Z2 are to be 

connected with the loop of FACP polarity-insensitively. 

The FACP polls the detector status through the loop, 

and displays its fault and fire alarm messages.   

In non-addressable mode, 24VDC power supply can 

be directly applied to Terminal Z1 and Z2.    K1 and K2 

output different resistance in different conditions. If the 

resistance is 4.7k

, the detector is in normal standby 

state; if the terminals are shorted, the detector is in fire 

condition; if the terminals are open, the detector is in 

fault condition. 

The detector has three sensitivity levels. The factory 

default is Level 1.    The address and sensitivity can be 

read and changed using P-9910B Programmer. 

Please refer to 

P-9910B Hand Held Programmer 

Operation Manual

 for details.   

The Intelligent Solution

DC-9104Exd Digital Flame Proof 

UV Flame Detector 

M6

×

60

M3

×

16

FAC

P

Z1

Z2

Z

1

Z

2

K

1

K

2

DC-9104Exd Detector

Hazardous Area

Safety Area

In

p

u

t Eq
u

ip

m

en
t

Z

1

Z

2

K

1

K

2

DC-9104Exd Detector

24VDC

Signal 
Input

Hazardous Area

Safety Area

Z1and Z2 connects with the loop 
of FACP, polarity-insensitive.     

Z1, Z2: Power input, 
polarity-insensitive.   
K1, K2: Signal output. 

—

 

Resistance between the 
terminals is 4.7k

 normally. 

—

 

Shorted in fire alarm 
condition.  

—

 

Open in fault condition. 