VSL3.780.047

       

                                                                                       

                         

  Issue 1.01

 

V-GREAT GLOBAL CORPORATION 

Installation and Operation Manual V1.01 

VG-6633 Conventional Heat Detector 

  Features 

 

Built-in MCU, data sampling and processing in real time. 

 

Fixed temperature and rate of rise alarming modes. 

 

Fire LED allows 360°viewing. 

 

Remote indicator output available. 

 

Reed switch testing. 

 

Comply with EN54-5 standard.   

 

Description 

VG-6633  Conventional  Heat  Detector  (the  detector)is  non-addressable,  developed  by  our  company.  With  built-in 
microprocessor, it works stably by being fixed with highly reliable fire judging program. 

 

When the detector checks fire signal, it can change its own current to transmit fire signal to control panel or interface 
module. The detector keeps illuminating fire LED to indicate fire status until resetting.   
NTC thermistor is adopted as sensing element for the detector.   

 

Installation 

The orientation base VG-6611 is shown in Fig. 3. 

65

A

C

B

Fi

g. 1 Bottom                          Fig. 2 Base 

  There are four terminals with numbers on the base. 

1: Detection zone positive IN 
2: Detection zone positive OUT 
3: Detection zone negative IN and OUT 
2: Positive terminal of remote indicator 

4: Negative terminal of remote indicator 

 

 

 

 

 

Recommended Wiring: 

1.0mm

or above fire cable for all terminals, laid through 

metal  conduit  or  flame-proof  conduit,  subject  to  local 
codes.   

Note:  It

’s  recommended  to  use  cables  of  different 

colors to avoid incorrect wiring.

 

First  fix  the  orientation  base  with  two  tapping  screws. 
Then align A (Fig. 1) on the bottom of the detector to B 
(Fig. 2) of the base, and rotate the detector clockwise to 
mark C.

 

Mounting of the detector is shown in Fig. 3.

 

Detector

Base

Conduit

Back Box

55

 

                                      Fig. 3

 

Application 

Warning: The alarm current depends on the current limit of the FACP. 24VDC power cannot be applied to 
the detector directly. Otherwise the detector may be damaged for lack of current- limit resistor.

 

The  detector  is  applicable  for  many  places  such  as 
hotels,  restaurants,  office  buildings,  teaching  buildings, 
banks,  warehouses,  libraries,  computer  rooms  and 
switching rooms and so on. 

 

 

When  the  detector  is  connected  with  VC-6831 

conventional  fire  alarm  control  panel  or  the 
addressable  zone  monitor  unit

,  if  a  4.7KΩ  terminal 

resistor  is  connected  to  the  end  of  output  loop,  then 
VG-6611  base  is  used.  The  system  composition  is 
shown in Fig. 4.

 

O

-

O

+

Conventional Detector

Remote

Indicator

4.7k

Ω

 E

n

d o
f

Line

 R

esistor

Conventional Detector

Remote

Indicator

Fig. 4 

 