V-GREAT VG-6633 Installation And Operation Manual Download Page 2

 

 

 

 

VSL3.780.047

       

                                                                                       

                         

  Issue 1.01                                                                                                                             

       

                                                                                       

                       

 

V-GREAT GLOBAL CORPORATION 

Installation and Operation Manual V1.01 

VG-6633 Conventional Heat Detector 

 

When  multiple  detectors  are  connected  with  a 

remote indicator, a diode 1N5819 should be connected 
to  Terminal  4  of  VG-6611  orientation  base  in  series 
before  going  to  the  positive  of  the  remote  indicator. 
System composition is shown in Fig. 5. 

Fig. 5

 

O

-

O

+

Conventional Detector

Remote
Indicator

Diode

Conventional Detector

Diode

 

Output loop of VC-6831 conventional control panel can 
be  connected  with  up  to

  30

  non-addressable  field 

devices. The control panel features loop checking.   

When the loop is broken, the panel will send fault signal 
for warning.   

 

Reed Switch Testing:   

Put  commission  tool  neat  the  LED  on  the  detector  for   
3 to 5 seconds. 

 

Reed Switch Testing

Commission
Tool

LED

 

 

Maintenance 

1. The detector should be installed just before commission and kept well before installation, taken corresponding 
measures for dust-proof, damp-proof and corrosion-proof. 
2. Protect the metal component on the PCB against damp and improper distortion. 
3. Fire simulation test should be made to the detector at least once half a year 
 

Specification 

Operating 
Voltage 

9VDC

28VDC 

Static Current 

≤60μA 

Alarm Current 

10mA≤I≤50mA   

Fire LED 

Red. Flashes once every 2s~4s 
in normal state; Illuminates in 
alarm.   

Remote 
Indicator 

Directly connects with remote 
indicator (internal 10

kΩ resistor 

in series output power supply 
voltage) Quiet in normal state, 
flashes in alarm.   

Max. ripple 
voltage 

2V(peak to peak value) 

Alarm reset 

Instant power down (2s Min, 
1.0VDC Max 

Power-up Time 

≤10s 

Wiring   

Polarized two wire 

Class 

A2R 

Ingress 
Protection 
Rating 

IP32 

Ambient 
Temperature 

-10

℃~

+55

 

Relative 
Humidity 

≤95%, non condensing 

Material of 
Enclosure 

ABS 

Dimensions   

Diameter: 100mm   
Height: 43mm

without base

 

Mounting Hole 
Spacing 

65mm 

Weight 

About 120g 

 

 

Accessories & Tools 

 

 

Limited Warranty 

We will repair or replace any properly used product that fails to operate due to material or craftsman defects within the warranty period. 

Any failure caused by intentional damage, improper use or tamper falls outside of this warranty and we are not responsible for any such 

consequence.  Anybody,  including  agents,  distributors  and  employees,  is  not  authorized  to  alter  the  contents  of  this  warranty.  Please 

contact your local distributor for products that are not within the scope of this warranty.

 

 

 

Company name

V-GREAT GLOBAL CORPORATION 

Add:Second Floor, Capital City, Independence Avenue, P.O. Box 1008, Victoria, Mahe, Seychelles 

Model 

Name 

Remarks 

VG-6611 

Base   

Order separately 

Reviews: