Command Manual – PoE
H3C S7500E Series Ethernet Switches
Chapter 1 PoE Configuration Commands
1-16
Output AC Current A Alarm : Normal
Output AC Current B Alarm : Under Limit
Output AC Current C Alarm : Lack Phase
Module 1:
Volt Phase AB Alarm : Above Limit
Volt Phase BC Alarm : Fuse Broken
Volt Phase CA Alarm : Switch Off
Module 2:
Volt Phase AB Alarm : Above Limit
Volt Phase BC Alarm : Fuse Broken
Volt Phase CA Alarm : Switch Off
Table 1-8
Description on the fields of display poe-power ac-input state
Field
Description
Module Number
Number of modules that a power supply unit (PSU)
contains
Output AC Current
A/B/C Alarm
Output three-phase AC voltage state:
z
Normal: The voltage is normal.
z
Under Limit: The voltage is below the lower limit.
z
Above Limit: The voltage is above the upper limit.
z
Lack Phase: A phase is lost.
z
Fuse Broken: The fuse is broken.
z
Switch Off: The switch is turned off.
z
Other Error: Other faults
Volt Phase AB/BC/CA
Alarm
AC voltage input state: Same as those of the output
three-phase AC current
1.1.10 display poe-power alarm
Syntax
display poe-power alarm
View
Any view
Parameters
None
Description
Use the
display poe-power alarm
command to display the alarm information of the
PoE power.