![Grundfos Fire NKF Installation And Operating Instructions Manual Download Page 28](http://html1.mh-extra.com/html/grundfos/fire-nkf/fire-nkf_installation-and-operating-instructions-manual_2271423028.webp)
English (GB)
28
16.2 Pump set with diesel engine
Warning
Before starting service work, make sure that the
pump set cannot accidentally start.
Fault
Cause
Remedy
1. Pump delivers no or
too little water.
a) Air in suction pipe.
Fill priming tank with water and vent pump. Make sure the
suction pipe has been installed according to section
b) Pump draws in air due to defective seals.
Check pipe and pump housing gaskets, and replace if
necessary.
c) Counter-pressure is too high.
Check the sprinkler system for impurities and blockages.
d) Inlet pressure is too low.
Make sure that the storage tank is filled with water and
that the conditions in section
are complied with.
e) Suction pipe or impeller is blocked.
Clean the suction pipe and pump.
2. Pump makes too
much noise.
Pump runs unevenly
and vibrates.
a) Inlet pressure is too low (cavitation).
Make sure that the storage tank is filled with water and
that the conditions in section
are complied with.
b) Air in suction pipe.
Fill priming tank with water. Vent pump.
Make sure the suction pipe has been installed according
to section
.
c) Impeller out of balance.
Clean the impeller and remove foreign particles.
d) Inner parts worn.
Replace defective parts. See service instructions for the
pump.
e) Pump stressed by the pipework.
Mount the pump so that it is not stressed.
Support the pipes. See section
f)
Defective bearings.
Replace bearings.
g) Defective coupling.
Replace the coupling.
h) Foreign bodies in the pump.
Clean the pump and remove foreign bodies.
3. Leaking pump
housing.
a) Pump stressed by the pipework.
Mount the pump so that it is not stressed.
Support the pipes. See section
b) Pump housing gaskets or flange gaskets
defective.
Replace defective gaskets.
4. Leaking shaft seal.
a) Shaft seal dirty or seized up.
Check and clean the shaft seal.
b) Shaft seal defective.
Replace the shaft seal. See service instructions for the
pump.
c) Shaft surface or shaft sleeve defective.
Replace the shaft or the shaft sleeve. See service
instructions for the pump.
5. Too high pump
temperature.
a) Air in pump.
Fill the priming tank with water and vent the pump.
b) Inlet pressure too low.
Make sure that the storage tank is filled with enough
water and that the conditions in section
are complied with.
c) Bearings lubricated with too little, too much or
unsuitable lubricant.
Replenish, reduce or replace the lubricant.
d) Pump bearing seat stressed by pipework.
Mount the pump so that it is not stressed. Support the
pipes. Check the alignment of the pump, and correct, if
necessary. See section
and
.
e) Axial pressure too high.
Check the relief holes of the impeller and the lock rings
on the suction side.
Summary of Contents for Fire NKF
Page 1: ...GRUNDFOS INSTRUCTIONS Fire NKF Installation and operating instructions...
Page 31: ...English GB 31...
Page 267: ...BG 41 9 7 9 8 120 C 9 9 9 10 10 10 1 10 2 1 5 10 100 mm 10 Fire NKF TM05 2546 0212...
Page 274: ...BG 48 10 11 26 26 27 SUPPLY RETURN 27 10 12 Flex 11 TM04 9851 0211 TM04 5069 2609 A...
Page 276: ...BG 50 1 2 3 4 5 28 25 Nm 1 2 30 Nm 3 8 6 7 8 12 3 12 4 16...
Page 277: ...BG 51 13 16 6 14 1 2 3 29 25 Nm 1 2 30 Nm 3 8 29 5 1 2 1 2 12 TM03 3935 1206...
Page 278: ...BG 52 15 15 1 x x x x x x x x x x x x x V x V x x x x x x x x x x...
Page 280: ...BG 54 16 16 1 1 a b c d e 9 2 10 6 f g 2 a b c d 3 a 9 2 10 6 b c d e f g h i j 4 a b c d e...
Page 386: ...Appendix 385 Appendix 1 Exploded view of fire pump TM03 1508 2305...