background image

GE Multilin

C60 Breaker Protection System

2-17

2 PRODUCT DESCRIPTION

2.3 SIGNAL PROCESSING

2

2.3SIGNAL PROCESSING

2.3.1 UR SIGNAL PROCESSING

The UR series relays are microprocessor-based protective relays that are designed to measure power system conditions
directly via CT and PT inputs and via other sources of information, such as analog inputs, communications inputs and con-
tact inputs. The following figure shows the overall signal processing in URs.

An analog low pass anti-aliasing filter with a 3 dB corner frequency is set at 2.4 kHz and is used for current and voltage
analog filtering as well as signal conditioning. The same filtering is applied for phase, ground currents, phase-to-phase
(when applicable), and auxiliary voltages. The 2.4 kHz cut-off frequency applies to both 50 Hz and 60 Hz applications and
fixed in the hardware, and thus is not dependent on the system nominal frequency setting.

Figure 2–3: UR SIGNAL PROCESSING

The UR samples its AC signals at 64 samples per cycle, that is, at 3840 Hz in 60 Hz systems, and 3200 Hz in 50 Hz sys-
tems. The sampling rate is dynamically adjusted to the actual system frequency by an accurate and fast frequency tracking
system.

The A/D converter has the following ranges of AC signals:

Voltages:

(EQ 2.1)

Currents:

From 

CT/VT

U

I

Analog Inputs 

Analog low-

pass filter

Analog-to-

Digital 

Converter

A

Digital band-

pass filter

DSP module

Phasor 

estimation

½ cycle 

Fourier

1 cycle 

Fourier

RMS 

values

Fundamen

tal freq. 

Phasors, 

Seq. com-

ponents

D

Sampling 

frequency 

CPU module

I>

Z<

U<

Protection  

algorithms

IRIG-B
IEEE 

1588
SNTP

Tracking 

frequency 

selection, 

estimation 

Accurate 

Real-Time 

clock

Synchrophasors  

calculations

Serial 
ports

Ethernet 
ports

Communi-

cation 

protocols

Control 

elements, 

monitoring 

elements,  
FlexLogic, 

Aggregation, 
post-filtering

Contact Inputs 

module

HMI

Ddebounce 

filtering 

Optoisolated

Analog Inputs 

module

DCmA, RTD 

A

D

Inter-relay 

comms 

module

Channel 

monitoring 

CRC check

G.703, RS-422, 

C37.94, direct fiber 

Contact Outputs 

module

Et

h

e

rn

e

t

S

eria

l

PMU (IEEE C37.118,

IEC 61850-90-5)

IEC 61850 (GOOSE, 

MMS Server)

DNP, Modbus, 

IEC60870

Comtrade, data 

logger

Events

Inter-relay

comms 
module

Frequency

T

Analog Outputs 

module

Time stamping

Synchro-

phasors 

filtering 

859740A1.vsd

2

±

260

V

( )

Summary of Contents for C60

Page 1: ...A5 GEK 119554D GE Grid Solutions 650 Markland Street Markham Ontario Canada L6C 0M1 Tel 1 905 927 7070 Fax 1 905 927 5098 Internet http www GEGridSolutions com GE Multilin s Quality Management System is registered to ISO 9001 2008 QMI 005094 UL A3775 1601 0100 AA5 GE Grid Solutions LISTED 52TL IND CONT EQ E83849 ...

Page 2: ...dFiber Multilin and GE Multilin are trademarks or registered trademarks of GE Multilin Inc The contents of this manual are the property of GE Multilin Inc This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin The content of this manual is for informational use only and is subject to change without notice Part number 1601 0100...

Page 3: ...7 1 5 3 MENU HIERARCHY 1 17 1 5 4 RELAY ACTIVATION 1 18 1 5 5 RELAY PASSWORDS 1 18 1 5 6 FLEXLOGIC CUSTOMIZATION 1 18 1 5 7 COMMISSIONING 1 19 2 PRODUCT DESCRIPTION 2 1 INTRODUCTION 2 1 1 OVERVIEW 2 1 2 1 2 SECURITY 2 2 2 1 3 IEC 870 5 103 PROTOCOL 2 7 2 2 ORDER CODES 2 2 1 OVERVIEW 2 9 2 2 2 ORDER CODES WITH ENHANCED CT VT MODULES 2 9 2 2 3 ORDER CODES WITH PROCESS BUS MODULES 2 12 2 2 4 REPLACEM...

Page 4: ...LIST 4 1 4 1 3 ENERVISTA UR SETUP OVERVIEW 4 1 4 1 4 ENERVISTA UR SETUP MAIN WINDOW 4 3 4 2 EXTENDED ENERVISTA UR SETUP FEATURES 4 2 1 SETTINGS TEMPLATES 4 4 4 2 2 SECURING AND LOCKING FLEXLOGIC EQUATIONS 4 8 4 2 3 SETTINGS FILE TRACEABILITY 4 10 4 3 FACEPLATE INTERFACE 4 3 1 FACEPLATE 4 13 4 3 2 LED INDICATORS 4 14 4 3 3 CUSTOM LABELING OF LEDS 4 17 4 3 4 DISPLAY 4 22 4 3 5 KEYPAD 4 22 4 3 6 BREA...

Page 5: ...HASE CURRENT 5 169 5 6 4 NEUTRAL CURRENT 5 178 5 6 5 GROUND CURRENT 5 181 5 6 6 BREAKER FAILURE ANSI 50BF 5 184 5 6 7 VOLTAGE ELEMENTS 5 193 5 6 8 SUPERVISING ELEMENTS 5 200 5 6 9 SENSITIVE DIRECTIONAL POWER ANSI 32 5 202 5 7 CONTROL ELEMENTS 5 7 1 OVERVIEW 5 205 5 7 2 TRIP BUS 5 205 5 7 3 SETTING GROUPS 5 207 5 7 4 SELECTOR SWITCH 5 209 5 7 5 SYNCHROCHECK 5 215 5 7 6 AUTORECLOSE ANSI 79 5 220 5 7...

Page 6: ... 6 2 18 EGD PROTOCOL STATUS 6 10 6 2 19 TELEPROTECTION CHANNEL TESTS 6 11 6 2 20 REMAINING CONNECTION STATUS 6 11 6 2 21 PARALLEL REDUNDANCY PROTOCOL PRP 6 12 6 3 METERING 6 3 1 METERING CONVENTIONS 6 13 6 3 2 SOURCES 6 16 6 3 3 SYNCHROCHECK 6 21 6 3 4 TRACKING FREQUENCY 6 21 6 3 5 FLEXELEMENTS 6 21 6 3 6 IEC 61580 GOOSE ANALOG VALUES 6 22 6 3 7 SENSITIVE DIRECTIONAL POWER 6 22 6 3 8 PHASOR MEASUR...

Page 7: ... ITEMS A 1 A 1 2 FLEXINTEGER ITEMS A 13 B MODBUS COMMUNICATIONS B 1 MODBUS RTU PROTOCOL B 1 1 INTRODUCTION B 1 B 1 2 PHYSICAL LAYER B 1 B 1 3 DATA LINK LAYER B 1 B 1 4 MODBUS RTU CRC 16 ALGORITHM B 2 B 2 MODBUS FUNCTION CODES B 2 1 SUPPORTED FUNCTION CODES B 4 B 2 2 READ ACTUAL VALUES OR SETTINGS FUNCTION CODE 03 04H B 4 B 2 3 EXECUTE OPERATION FUNCTION CODE 05H B 5 B 2 4 STORE SINGLE SETTING FUNC...

Page 8: ...E GOOSE C 11 C 4 6 GSSE ID AND GOOSE ID SETTINGS C 11 C 5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP C 5 1 OVERVIEW C 12 C 5 2 CONFIGURING IEC 61850 SETTINGS C 13 C 5 3 ABOUT ICD FILES C 14 C 5 4 CREATING AN ICD FILE WITH ENERVISTA UR SETUP C 18 C 5 5 ABOUT SCD FILES C 18 C 5 6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP C 21 C 6 ACSI CONFORMANCE C 6 1 ACSI BASIC CONFORMANCE STATEMENT C 23 ...

Page 9: ...SERVER G 1 RADIUS SERVER CONFIGURATION G 1 1 RADIUS SERVER CONFIGURATION G 1 H MISCELLANEOUS H 1 CHANGE NOTES H 1 1 REVISION HISTORY H 1 H 1 2 CHANGES TO THE C60 MANUAL H 2 H 2 ABBREVIATIONS H 2 1 STANDARD ABBREVIATIONS H 6 H 3 WARRANTY H 3 1 GE MULTILIN WARRANTY H 9 INDEX ...

Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...

Page 11: ...be thoroughly familiar with all safety cau tions and warnings in this manual and with applicable country regional utility and plant safety regulations Hazardous voltages can exist in the power supply and at the device connection to current transformers voltage transformers control and test circuit terminals Make sure all sources of such voltages are isolated prior to attempting work on the device ...

Page 12: ...are missing contact GE Grid Solutions as fol lows GE GRID SOLUTIONS CONTACT INFORMATION AND CALL CENTER FOR PRODUCT SUPPORT GE Grid Solutions 650 Markland Street Markham Ontario Canada L6C 0M1 TELEPHONE Worldwide 1 905 927 7070 Europe Middle East Africa 34 94 485 88 54 North America toll free 1 800 547 8629 FAX 1 905 927 5098 E MAIL Worldwide multilin tech ge com Europe multilin tech euro ge com H...

Page 13: ...ES The contact inputs and outputs are digital signals associated with connections to hard wired contacts Both wet and dry contacts are supported The virtual inputs and outputs are digital signals associated with UR series internal logic signals Virtual inputs include signals generated by the local user interface The virtual outputs are outputs of FlexLogic equations used to customize the device Vi...

Page 14: ...e use of objects and classes An object is defined as a logical entity that contains both data and code that manipulates data A class is the generalized form of similar objects By using this approach one can create a protection class with the protection elements as objects of the class such as time overcurrent instantaneous overcurrent current differential undervoltage overvoltage underfrequency an...

Page 15: ...VD drive The following qualified modems have been tested to be compatible with the C60 and the EnerVista UR Setup software US Robotics external 56K FaxModem 5686 US Robotics external Sportster 56K X2 PCTEL 2304WT V 92 MDC internal modem 1 3 2 INSTALLATION After ensuring that the requirements for using EnerVista UR Setup software are met install the software from the GE EnerVista DVD Or download th...

Page 16: ...The UR device is added to the list of installed intelligent electronic devices IEDs in the EnerVista Launchpad window as shown Figure 1 5 UR DEVICE ADDED TO LAUNCHPAD WINDOW 1 3 3 CONFIGURING THE C60 FOR SOFTWARE ACCESS a OVERVIEW You connect remotely to the C60 through the rear RS485 or Ethernet port with a computer running the EnerVista UR Setup software The C60 can also be accessed locally with...

Page 17: ...hen select the new site to re open the Device Setup window 6 Click the Add Device button to define the new device 7 Enter a name in the Device Name field and a description optional of the site 8 Select Serial from the Interface drop down list This displays a number of interface parameters that must be entered for serial communications Figure 1 6 CONFIGURING SERIAL COMMUNICATIONS 9 Enter the COM po...

Page 18: ...tup window 16 Click the Add Device button to define the new device 17 Enter the desired name in the Device Name field and a description optional of the site 18 Select Ethernet from the Interface drop down list This displays a number of interface parameters that must be entered for proper Ethernet functionality Figure 1 7 CONFIGURING ETHERNET COMMUNICATIONS 19 Enter the relay IP address specified i...

Page 19: ...click the Quick Connect button to establish direct communi cations to the C60 device This ensures that configuration of the EnerVista UR Setup software matches the C60 model number b USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the C60 from a computer through Ethernet first assign an IP address to the relay from the front panel keyboard 1 Press the MEN...

Page 20: ...dows desktop right click the My Network Places icon and select Properties to open the network con nections window 2 Right click the Local Area Connection icon and select Properties 3 Select the Internet Protocol TCP IP item from the list and click the Properties button 4 Click the Use the following IP address box ...

Page 21: ...ime and TTL vary depending on local network configuration 5 If the following sequence of messages appears when entering the C WINNT ping 1 1 1 1 command Pinging 1 1 1 1 with 32 bytes of data Request timed out Request timed out Request timed out Request timed out Ping statistics for 1 1 1 1 Packets Sent 4 Received 0 Lost 4 100 loss Approximate round trip time in milliseconds Minimum 0ms Maximum 0ms...

Page 22: ...ection specific DNS suffix IP Address 0 0 0 0 Subnet Mask 0 0 0 0 Default Gateway Ethernet adapter Local Area Connection Connection specific DNS suffix IP Address 1 1 1 2 Subnet Mask 255 0 0 0 Default Gateway C WINNT Before using the Quick Connect feature through the Ethernet port disable any configured proxy settings in Internet Explorer 1 Start the Internet Explorer software 2 Select the Tools I...

Page 23: ...he Windows desktop right click the My Network Places icon and select Properties to open the network con nections window 2 Right click the Local Area Connection icon and select the Properties item 3 Select the Internet Protocol TCP IP item from the list provided and click the Properties button 4 Set the computer to Obtain a relay address automatically as shown If this computer is used to connect to...

Page 24: ... green status indicator 3 The Display Properties settings can now be edited printed or changed See chapter 4 in this manual or the EnerVista UR Setup Help File for information about the using the EnerVista UR Setup software interface QUICK ACTION HOT LINKS The EnerVista UR Setup software has several quick action buttons to provide instant access to several functions that are often performed when u...

Page 25: ...trator Supervisor Engineer Operator Observer or Administrator and Supervisor when device authentication is disabled When using a serial connection only device authentication is supported When server authentication is required characteristics for communication with a RADIUS server must be configured on the UR This is possible only through the EnerVista software The RADIUS server itself also must be...

Page 26: ...ial cable A shielded twisted pair 20 22 or 24 AWG connects the F485 converter to the C60 rear communications port The converter terminals GND are connected to the C60 communication module COM terminals See the CPU Communica tion Ports section in chapter 3 for details The line is terminated with an R C network that is 120 Ω 1 nF as described in the chapter 3 1 4 3 FACEPLATE DISPLAY All messages are...

Page 27: ...hen then 0 then then 0 then then 1 To save the address press the ENTER key 1 5 2 MENU NAVIGATION Press the MENU key to select a header display page top level menu The header title appears momentarily followed by a header display page menu item Each press of the MENU key advances through the following main heading pages Actual values Settings Commands Targets User displays when enabled 1 5 3 MENU H...

Page 28: ...ssigned to specific personnel There are two user security access levels COMMAND and SETTING 1 COMMAND The COMMAND access level restricts the user from making any settings changes but allows the user to perform the fol lowing operations Operate breakers via faceplate keypad Change state of virtual inputs Clear event records Clear oscillography records Operate user programmable pushbuttons 2 SETTING...

Page 29: ...nding system 2 Visual verification of active alarms relay display messages and LED indications 3 LED test 4 Visual inspection for any damage corrosion dust or loose wires 5 Event recorder file download with further events analysis Out of service maintenance 1 Check wiring connections for firmness 2 Analog values currents voltages RTDs analog inputs injection test and metering accuracy verification...

Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...

Page 31: ... serial ports use the Modbus RTU protocol The IEC 60870 5 103 protocol is supported on the RS485 interface IEC 60870 5 103 DNP and Modbus cannot be enabled simultaneously on this interface Also only one of the DNP IEC 60870 5 103 and IEC 60870 5 104 protocols can be enabled at any time on the relay When the IEC 60870 5 103 protocol is chosen the RS485 port has a fixed even parity and the baud rate...

Page 32: ...n over IRIG B or IEEE 1588 Breaker Restrike FlexElements 8 Time Synchronization over SNTP Contact Inputs up to 96 FlexLogic Equations Transducer Inputs Outputs Contact Outputs up to 64 IEC 60870 5 103 Communications optional User Definable Displays Control Pushbuttons IEC 61850 Communications optional User Programmable LEDs CyberSentry security Metering Current Voltage Power Energy Frequency User ...

Page 33: ...raphy records Clearing fault reports Changing the date and time Clearing the breaker arcing current Clearing energy records Clearing the data logger Clearing the user programmable pushbutton states The following operations are under setting password supervision Changing any setting Test mode operation The C60 supports password entry from a local or remote connection Local access is defined as any ...

Page 34: ... event reporting through the Syslog protocol for supporting Security Information Event Management SIEM systems for centralized cybersecurity monitoring Strong encryption of all access and configuration network messages between the EnerVista software and UR devices using the Secure Shell SSH protocol the Advanced Encryption Standard AES and 128 bit keys in Galois Counter Mode GCM as specified in th...

Page 35: ...d their corresponding capabilities Table 2 3 PERMISSIONS BY USER ROLE FOR CYBERSENTRY Roles Administrator Engineer Operator Supervisor Observer Complete access Complete access except for CyberSentry Security Command menu Authorizes writing Default role Device Definition R R R R R Settings Product Setup Security CyberSentry RW R R R R Supervisory see table notes R R see table notes R Display Proper...

Page 36: ...Resetting RW RW R R R Direct Inputs RW RW R R R Direct Outputs RW RW R R R Teleprotection RW RW R R R Direct Analogs RW RW R R R Direct Integers RW RW R R R IEC61850 GOOSE Analogs RW RW R R R IEC61850 GOOSE Integers RW RW R R R Transducer I O RW RW R R R Testing RW RW R R R Front Panel Labels Designer NA NA NA NA NA Protection Summary NA NA NA NA NA Commands RW RW RW R R Virtual Inputs RW RW RW R ...

Page 37: ...ain text by the EnerVista software or UR device nor are they ever transmitted without cryptographic protection CyberSentry Server Authentication The UR has been designed to automatically direct authentication requests based on user names In this respect local account names on the UR are considered as reserved and not used on a RADIUS server The UR automatically detects whether an authentication re...

Page 38: ...2 8 C60 Breaker Protection System GE Multilin 2 1 INTRODUCTION 2 PRODUCT DESCRIPTION 2 Commands Time synchronization The RS485 port supports IEC 60870 5 103 ...

Page 39: ...s BF IEEE 1588 IEC 61850 and two PMUs C0 Parallel Redundancy Protocol PRP C1 PRP and Ethernet Global Data C3 PRP and IEC 61850 C4 PRP Ethernet Global Data and IEC 61850 CE PRP and two PMUs CF PRP IEC 61850 and two PMUs D0 IEEE 1588 and CyberSentry Lvl 1 D1 IEEE 1588 CyberSentry Lvl 1 and Ethernet Global Data D3 IEEE 1588 CyberSentry Lvl 1 and IEC 61850 D4 IEEE 1588 CyberSentry Lvl 1 Ethernet Globa...

Page 40: ...al inputs 6R 6R 6R 6R 6R 2 Form A no monitoring and 2 Form C outputs 8 digital inputs 6S 6S 6S 6S 6S 2 Form A no monitoring and 4 Form C outputs 4 digital inputs 6T 6T 6T 6T 6T 4 Form A no monitoring outputs 8 digital inputs 6U 6U 6U 6U 6U 6 Form A no monitoring outputs 4 digital inputs 6V 6V 6V 6V 6V 2 Form A outputs 1 Form C output 2 Form A no monitoring latching outputs 8 digital inputs TRANSDU...

Page 41: ...monitoring MOSFET outputs 4B 4B 4B 4 Solid State voltage with optional current MOSFET outputs 4C 4C 4C 4 Solid State current with optional voltage MOSFET outputs 4D 4D 4D 16 digital inputs with Auto Burnishing maximum of three modules within a case 4L 4L 4L 14 Form A no monitoring Latching outputs 67 67 67 8 Form A no monitoring outputs 6A 6A 6A 2 Form A voltage with optional current and 2 Form C ...

Page 42: ...CyberSentry Lvl 1 Ethernet Global Data and IEC 61850 GE IEEE 1588 PRP CyberSentry Lvl 1 and two PMUs GF IEEE 1588 PRP CyberSentry Lvl 1 IEC 61850 and two PMUs J0 IEC 60870 5 103 J1 IEC 60870 5 103 and EGD J3 IEC 60870 5 103 and IEC 61850 J4 IEC 60870 5 103 EGD and IEC 61850 JE IEC 60870 5 103 and two PMUs JF IEC 60870 5 103 IEC 61850 and two PMUs K0 IEEE 1588 PRP and IEC 60870 5 103 K1 IEEE 1588 P...

Page 43: ...single mode ELED 2 Channels 7K 1300 nm single mode LASER 2 Channels 7L Channel 1 RS422 Channel 2 820 nm multimode LED 7M Channel 1 RS422 Channel 2 1300 nm multimode LED 7N Channel 1 RS422 Channel 2 1300 nm single mode ELED 7P Channel 1 RS422 Channel 2 1300 nm single mode LASER 7Q Channel 1 G 703 Channel 2 1300 nm single mode LASER 7R G 703 1 Channel 7S G 703 2 Channels 7T RS422 1 Channel 7W RS422 ...

Page 44: ... voltage with optional current and 4 Form C outputs 4 digital inputs 6C 8 Form C outputs 6D 16 digital inputs 6E 4 Form C outputs 8 digital inputs 6F 8 Fast Form C outputs 6G 4 Form A voltage with optional current outputs 8 digital inputs 6H 6 Form A voltage with optional current outputs 4 digital inputs 6K 4 Form C and 4 Fast Form C outputs 6L 2 Form A current with optional voltage and 2 Form C o...

Page 45: ... monitoring outputs 8 contact inputs 6U 6 Form A no monitoring outputs 4 contact inputs 6V 2 Form A outputs 1 Form C output 2 Form A no monitoring latching outputs 8 contact inputs CT VT MODULES NOT AVAILABLE FOR THE C30 8L Standard 4CT 4VT with enhanced diagnostics 8N Standard 8CT with enhanced diagnostics 8M Sensitive Ground 4CT 4VT with enhanced diagnostics 8R Sensitive Ground 8CT with enhanced...

Page 46: ...INTER RELAY COMMUNICATIONS 2A C37 94SM 1300 nm single mode ELED 1 channel single mode 2B C37 94SM 1300 nm single mode ELED 2 channel single mode 2E Bi phase single channel 2F Bi phase dual channel 2G IEEE C37 94 820 nm 128 kbps multimode LED 1 Channel 2H IEEE C37 94 820 nm 128 kbps multimode LED 2 Channels 2I Channel 1 IEEE C37 94 multimode 64 128 kbps Channel 2 1300 nm single mode Laser 2J Channe...

Page 47: ... Hz systems and 3200 Hz in 50 Hz sys tems The sampling rate is dynamically adjusted to the actual system frequency by an accurate and fast frequency tracking system The A D converter has the following ranges of AC signals Voltages EQ 2 1 Currents From CT VT U I Analog Inputs Analog low pass filter Analog to Digital Converter A Digital band pass filter DSP module Phasor estimation cycle Fourier 1 c...

Page 48: ...he same direction negative to positive Voltage or current samples are pre filtered using a Finite Impulse Response FIR digital filter to remove high frequency noise contained in the signal The period is used after several security conditions are met such as true RMS signal must be above 6 nominal for a certain time and others If these security conditions are not met the last valid measurement is u...

Page 49: ...0 pu in steps of 0 001 Dropout level 97 to 98 of pickup Level accuracy 0 1 to 2 0 CT rating 0 5 of reading or 0 4 of rated whichever is greater 2 0 CT rating 1 5 of reading Overreach 2 Pickup delay 0 00 to 600 00 s in steps of 0 01 Reset delay 0 00 to 600 00 s in steps of 0 01 Operate time 16 ms at 3 pickup at 60 Hz Phase Ground IOC 20 ms at 3 pickup at 60 Hz Neutral IOC Timer accuracy 3 of operat...

Page 50: ... FLASHOVER Operating quantity phase current voltage and voltage differ ence Pickup level voltage 0 to 1 500 pu in steps of 0 001 Dropout level voltage 97 to 98 of pickup Pickup level current 0 to 1 500 pu in steps of 0 001 Dropout level current 97 to 98 of pickup Level accuracy 0 5 or 0 1 of rated whichever is greater Pickup delay 0 to 65 535 s in steps of 0 001 Timer accuracy 3 of operate time or...

Page 51: ... Execution sequence as input prior to protection control and FlexLogic USER PROGRAMMABLE LEDs Number 48 plus trip and alarm Programmability from any logical variable contact or vir tual input Reset mode self reset or latched LED TEST Initiation from any contact input or user program mable condition Number of tests 3 interruptible at any time Duration of full test approximately 3 minutes Test seque...

Page 52: ... data ZLine error user data METHOD error see chapter 8 RELAY ACCURACY error 1 5 PHASOR MEASUREMENT UNIT Output format per IEEE C37 118 or IEC 61850 90 5 standard Number of channels 14 synchrophasors 8 analogs 16 digi tals TVE total vector error 1 Triggering frequency voltage current power rate of change of frequency user defined Reporting rate 1 2 5 10 12 15 20 25 30 50 or 60 times per second for ...

Page 53: ...ting 25 to 60 Hz Sampling frequency 64 samples per power cycle Tracking frequency range 20 to 70 Hz CONTACT INPUTS Dry contacts 1000 Ω maximum Wet contacts 300 V DC maximum Selectable thresholds 17 V 33 V 84 V 166 V Tolerance 10 Contacts per common return 4 Recognition time 1 ms Debounce time 0 0 to 16 0 ms in steps of 0 5 Continuous current draw 4 mA when energized CONTACT INPUTS WITH AUTO BURNIS...

Page 54: ...voltage 88 V Maximum DC voltage 300 V Nominal AC voltage 100 to 240 V at 50 60 Hz Minimum AC voltage 88 V at 25 to 100 Hz Maximum AC voltage 265 V at 25 to 100 Hz Voltage loss hold up 200 ms duration at maximum load ALL RANGES Volt withstand 2 Highest Nominal Voltage for 10 ms Power consumption typical 15 to 20 W VA maximum 45 W VA contact factory for exact order code con sumption INTERNAL FUSE RA...

Page 55: ...ts 32 DIRECT OUTPUTS Output points 32 DCMA OUTPUTS Range 1 to 1 mA 0 to 1 mA 4 to 20 mA Max load resistance 12 kΩ for 1 to 1 mA range 12 kΩ for 0 to 1 mA range 600 Ω for 4 to 20 mA range Accuracy 0 75 of full scale for 0 to 1 mA range 0 5 of full scale for 1 to 1 mA range 0 75 of full scale for 0 to 20 mA range 99 Settling time to a step change 100 ms Isolation 1 5 kV Driving signal any FlexAnalog...

Page 56: ...8TM2011 Slave only ordinary clock Peer delay measurement mechanism PARALLEL REDUNDANCY PROTOCOL PRP IEC 62439 3 CLAUSE 4 2012 Ethernet ports used 2 and 3 Networks supported 10 100 MB Ethernet OTHER TFTP HTTP IEC 60870 5 104 Ethernet Global Data EGD 2 4 9 INTER RELAY COMMUNICATIONS SHIELDED TWISTED PAIR INTERFACE OPTIONS RS422 distance is based on transmitter power and does not take into considerat...

Page 57: ... 125 μm 16 dBm 32 dBm 16 dBm 8 dBm 50 125 μm 20 dBm 12 dBm 1300 nm Multimode 62 5 125 μm 16 dBm 32 dBm 16 dBm 8 dBm 50 125 μm 20 dBm 12 dBm 1300 nm Single mode 9 125 μm 15 dBm 32 dBm 17 dBm 8 dBm 1300 nm Laser Single mode 9 125 μm 0 dBm 34 dBm 34 dBm 8 dBm 1550 nm Laser Single mode 9 125 μm 5 dBm 34 dBm 39 dBm 10 dBm EMITTER FIBER TYPE TRANSMIT POWER RECEIVED SENSITIVITY POWER BUDGET MAX OPTICAL I...

Page 58: ...ant 1 6 days OTHER Altitude 2000 m maximum Pollution degree II Overvoltage category II Ingress protection IP20 front IP10 back Noise 0 dB Typical distances listed are based on the follow ing assumptions for system loss As actual losses vary from one installation to another the distance covered by your system may vary CONNECTOR LOSSES TOTAL OF BOTH ENDS ST connector 0 7 dB each FIBER LOSSES 820 nm ...

Page 59: ...le DC IEC 60255 11 12 ripple 200 ms interrupts Radiated and conducted emissions CISPR11 CISPR22 IEC 60255 25 Class A Sinusoidal vibration IEC 60255 21 1 Class 1 Shock and bump IEC 60255 21 2 Class 1 Seismic IEC 60255 21 3 Class 1 Power magnetic immunity IEC 61000 4 8 Level 5 Pulse magnetic immunity IEC 61000 4 9 Level 4 Damped magnetic immunity IEC 61000 4 10 Level 4 Voltage dip and interruption I...

Page 60: ...ning is not required but for situations where dust has accumulated on the faceplate display a dry cloth can be used To avoid deterioration of electrolytic capacitors power up units that are stored in a de energized state once per year for one hour continuously COMPLIANCE APPLICABLE COUNCIL DIRECTIVE ACCORDING TO CE Low voltage directive EN 60255 5 EMC directive EN 60255 26 EN 50263 EN 61000 6 5 C ...

Page 61: ...e removable modules and is itself removable to allow mounting on doors with limited rear depth The case dimensions are shown below along with panel cutout details for panel mounting When planning the location of your panel cutout ensure that provision is made for the faceplate to swing open without interference to or from adjacent equipment The relay must be mounted such that the faceplate sits se...

Page 62: ... When planning the location of your panel cutout ensure that provision is made for the faceplate to swing open without interference to or from adjacent equipment The relay must be mounted such that the faceplate sits semi flush with the panel or switchgear door allowing the operator access to the keypad and the RS232 communications port The relay is secured to the panel with the use of four screws...

Page 63: ... 243 4 mm 7 00 177 7 mm 4 00 101 6 mm 7 10 180 2 mm 13 66 347 0 mm 14 03 356 2 mm 0 20 5 1 mm 1 55 39 3 mm 4 Places 0 213 5 41 mm Front of Panel Mounting Bracket Vertical Enhanced Front View Vertical Enhanced Top View Vertical Enhanced Mounting Panel CUTOUT Front of Panel Reference only Terminal Blocks Front Bezel Front of Panel Mounting Bracket Vertical Enhanced Side View 843809A2 cdr ...

Page 64: ...R Device Instruction Sheet GEK 113182 Connecting a Remote UR V Enhanced Front Panel to a Vertically Mounted Horizontal UR Device Instruction Sheet For side mounting C60 devices with the standard front panel use the following figures 13 72 348 5 mm 7 00 177 8 mm 13 50 342 9 mm Front of panel Front bezel Panel Mounting bracket 1 57 39 9 mm 4 00 101 6 7 13 181 1 mm 0 46 11 7 mm 13 65 346 7 mm 14 40 3...

Page 65: ...PANEL 10 32 NYLOCK NUT P N 1422 1032 4 PLACES 8 3 8 PAN PHILIPS HEAD BLACK OXIDE SCREW P N 1408 0306 8 PLACES TO MOUNT THE UNIT 8 LOCKWASHER EXTERNAL TOOTH P N 1435 0002 8 PLACES TO MOUNT STEP 4 ASSEMBLE UR V UNIT TO MOUNTING BRACKETS UR V UNIT STEP 1 CREATE THE HOLES AND CUT OUT INTO THE PANEL AS PER DRAWING 843753 PLUG THE DISPLAY CABLE INTO THE FRONT BEZEL BEFORE MOUNTING THE UNIT ON THE PANEL ...

Page 66: ... REAR DIMENSIONS STANDARD PANEL C U T O U T 1 33 33 9 2 83 71 9 6 66 169 2 12 20 309 9 0 159 DIA 6 PLACES 4 0 0 213 DIA 5 4 4 PLACES SEE HOLES MARKED X INCHES MILLIMETERS 5 33 135 4 PANEL SHOWN FOR REFERENCE ONLY VIEWED FROM FRONT X X X X 1 00 25 4 1 00 25 4 10 05 255 3 0 04 1 0 0 68 17 3 5 27 133 8 843753A3 cdr ...

Page 67: ...minal block See the following figure for an example of rear terminal assignments Figure 3 9 EXAMPLE OF MODULES IN F AND H SLOTS 834774A3 CDR X W V U T S P N M L K J H D G F B R 8 4 7 3 6 2 5 1 b 8 4 7 3 6 2 5 1 a a b c a b c a b c Optional direct input output module CPU module T module shown Optional contact input output module CT VT module Power supply module Tx1 Tx2 Rx1 Rx2 Tx1 Tx2 Optional cont...

Page 68: ... back of the relay chassis screws a b c shown is 9 inch pounds For the connections to the terminal blocks rows 1 to 8 use a minimum of 17 inch pounds During manufacturing the power supply and CPU modules are installed in slots B and D of the chassis with 13 inch pounds of torque on the screws at the top and bottom of the modules ...

Page 69: ...C60 Computer 1 TXD RXD RXD TXD SGND SGND 1 8 3 2 20 7 6 4 5 22 25 pin connector 9 pin connector 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 Computer Module arrangement J U X L W K V B H T D G S F M N P R Contact input H5a Contact input H5c Contact input H6a Contact input H6c Common H5b Contact input H7a Contact input H7c Contact input H8a Contact input H8c Common H7b Surge H6a H8a H5b H7b H8b H5a H7a H6c H8c ...

Page 70: ...nnections The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay see the Typical wiring diagram earlier The critical failure relay is a form C device that is energized once control power is applied and the relay has successfully booted up with no critical self test failures If on going self test diagnostic checks detect a critical failure see ...

Page 71: ...ound current input that is the same as the phase current input Each AC current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the module is withdrawn from the chassis There are no internal ground connections on the current inputs Current transformers with 1 to 50000 A primaries and 1 A or 5 A secondaries can be used CT VT modules with a sensitive ...

Page 72: ...und connection to neutral must be on the source side UNSHIELDED CABLE LOAD A B C N G Ground outside CT Source LOAD SHIELDED CABLE 996630A6 CDR A B C Source To ground must be on load side Stress cone shields NOTE 1a 1b 1c 2a 2b 2c 3a 4a 5a 6a 7a 8a 3b 4b 5c 6c 7c 8c 3c 4c Current inputs 8F 8G 8L and 8M modules 4 CTs and 4 VTs Voltage inputs VA VB VC VX VA VB VC VX IA IC IB IG IA5 IC5 IB5 IG5 IA1 IC...

Page 73: ... and two inputs per common return When a contact input output module is ordered four inputs per com mon is used If the inputs must be isolated per row then two inputs per common return should be selected 4D module The tables and diagrams on the following pages illustrate the module types 6A etc and contact arrangements that can be ordered for the relay Since an entire row is used for a single cont...

Page 74: ...on tinue to read the form A contact as being closed after it has closed and subsequently opened when measured as an impedance The solution is to use the voltage measuring trigger input of the relay test set and connect the form A contact through a voltage dropping resistor to a DC voltage source If the 48 V DC output of the power supply is used as a source a 500 Ω 10 W resistor is appropriate In t...

Page 75: ...6a 6c 2 Inputs 6 Fast Form C 6a 6c 2 Inputs 6 Form A 7a 7c 2 Inputs 7 Fast Form C 7a 7c 2 Inputs 7a 7c 2 Inputs 8a 8c 2 Inputs 8 Fast Form C 8a 8c 2 Inputs 8a 8c 2 Inputs 6K MODULE 6L MODULE 6M MODULE 6N MODULE TERMINAL ASSIGNMENT OUTPUT TERMINAL ASSIGNMENT OUTPUT OR INPUT TERMINAL ASSIGNMENT OUTPUT OR INPUT TERMINAL ASSIGNMENT OUTPUT OR INPUT 1 Form C 1 Form A 1 Form A 1 Form A 2 Form C 2 Form A ...

Page 76: ... Solid State 7a 7c 2 Inputs 7a 7c 2 Inputs 7 Form A 7 Not Used 8a 8c 2 Inputs 8a 8c 2 Inputs 8 Form A 8 Solid State 4B MODULE 4C MODULE 4D MODULE 4L MODULE TERMINAL ASSIGNMENT OUTPUT TERMINAL ASSIGNMENT OUTPUT TERMINAL ASSIGNMENT OUTPUT TERMINAL ASSIGNMENT OUTPUT 1 Not Used 1 Not Used 1a 1c 2 Inputs 1 2 Outputs 2 Solid State 2 Solid State 2a 2c 2 Inputs 2 2 Outputs 3 Not Used 3 Not Used 3a 3c 2 In...

Page 77: ...GE Multilin C60 Breaker Protection System 3 17 3 HARDWARE 3 2 WIRING 3 Figure 3 15 CONTACT INPUT AND OUTPUT MODULE WIRING 1 of 2 842762A3 CDR ...

Page 78: ... 8c COMMON 7b SURGE 8c 7c 8b I V I V I V I V DIGITAL I O 6N 1b 2b 3b 4b 6c 1a 2a 3a 4a 5a 6a 1c 2c 3c 4c 5c 5b 1 2 3 4 8a 7b 7a CONTACT IN 7a CONTACT IN 5a CONTACT IN 7c CONTACT IN 5c CONTACT IN 8a CONTACT IN 6a CONTACT IN 8c CONTACT IN 6c COMMON 7b COMMON 5b SURGE 8c 7c 8b DIGITAL I O 6T 1b 2b 3b 4b 6c 1a 2a 3a 4a 5a 6a 1c 2c 3c 4c 5c 5b 1 2 3 4 8a 7b 7a CONTACT IN 7a CONTACT IN 5a CONTACT IN 7c ...

Page 79: ...t a DC ground fault on 48 V DC control power external output We recommend using an external DC supply GENERAL APPLICATION CONSIDERATIONS Contacts outputs of protective relays auxiliary contacts from breakers disconnectors and other devices are generally con nected to contacts inputs of protective relays In some situations the contact outputs of some protective relays can have high impedance connec...

Page 80: ... and the input impedance of the contact input If the duration is greater than the debounce time setting then the contact input operates The application example that follows describes how to mitigate this problem by connecting a resistor across the contact input as shown in the next figure or by adjusting the debounce time setting to a value greater than the discharge time to prevent spurious opera...

Page 81: ...lue of this resistor R is calculated as follows 1 Determine the minimum voltage V threshold required to turn on the input This is determined by direct measurement or referenced in the input specifications 2 Calculate the resistance necessary to limit the voltage to 1 3 V threshold when the contact is OFF the non activated state as follows R Vthreshold 3 2 mA EQ 3 2 The 2 mA current is used in case...

Page 82: ...3 2 WIRING 3 HARDWARE 3 Vresistor 2 mA 14 Kohm 28 V Vresistor contact input threshold 84 V EQ 3 5 In conclusion in this example the contact input does NOT operate falsely with the Burden Resistor across its input AND when a battery ground is present ...

Page 83: ...o burnishing allow currents up to 50 to 70 mA at the first instance when the change of state was sensed Then within 25 to 50 ms this current is slowly reduced to 3 mA as indicated above The 50 to 70 mA peak current burns any film on the con tacts allowing for proper sensing of state changes If the external device contact is bouncing the auto burnishing starts when external device contact bouncing ...

Page 84: ...dition During Low impedance state contact input impedance is maintained at 10 K Ohms impedance to allow fast discharge of the stray capacitance of the long cables When the contact input voltage exceeds the set threshold active impedance maintains 10 K Ohms impedance value If voltage starts rapidly decreasing this indicates that stray capacitance is being discharged through the contact input If how...

Page 85: ...GE Multilin C60 Breaker Protection System 3 25 3 HARDWARE 3 2 WIRING 3 Figure 3 22 ACTIVE IMPEDANCE CONTACT INPUT V I CHARACTERISTIC ...

Page 86: ...ranged as three ter minals per row with a total of eight rows A given row can be used for either inputs or outputs with terminals in column a having positive polarity and terminals in column c having negative polarity Since an entire row is used for a single input output channel the name of the channel is assigned using the module slot position and row number Each module also requires that a conne...

Page 87: ...tup software provided with the relay Cabling for the RS232 port is shown in the following figure for both 9 pin and 25 pin connectors The baud rate for this port is fixed at 19200 bps Figure 3 25 RS232 FACEPLATE PORT CONNECTION Three wire shielded cable RTD terminals Maximum total lead resistance 25 ohms for Platinum RTDs Route cable in separate conduit from current carrying conductors RTD 859736A...

Page 88: ...together Though data is transmitted over a two wire twisted pair all RS485 devices require a shared reference or common voltage This common voltage is implied to be a power supply common Some systems allow the shield drain wire to be used as common wire and to connect directly to the C60 COM terminal 3 others function cor rectly only if the common wire is connected to the C60 COM terminal but insu...

Page 89: ...communication ports An iso lated power supply with an optocoupled data interface also acts to reduce noise coupling To ensure maximum reliability all equipment should have similar transient protection devices installed Terminate both ends of the RS485 circuit with an impedance as shown below Figure 3 27 RS485 SERIAL CONNECTION c 100BASE FX FIBER OPTIC PORTS Ensure that the dust covers are installe...

Page 90: ...ons can be synchronized Figure 3 28 OPTIONS FOR THE IRIG B CONNECTION Using an amplitude modulated receiver causes errors up to 1 ms in event time stamping The C60 is intended for use with external clocks that set the IRIG B control bits according to IEEE Std C37 118 1 2011 When used with a source that sets the IRIG B control bits according to IEEE Std 1344 1995 the source must have the sign of it...

Page 91: ...NEL CONNECTION IRC modules with protocol C37 94 and G 703 are designed for back to back communication connections so the ring con figuration shown in the previous figure does not apply To establish inter relay communication in more than two URs you need to have two channel IRC module and enable DIRECT I O CHANNEL CROSSOVER function in all relays as shown in the next figure This configuration can b...

Page 92: ...ommunication modules UR2 has a dual channel module The two communication chan nels can be of different types depending on the Type 7 modules used To allow the direct input and output data to cross over from channel 1 to channel 2 on UR2 the DIRECT I O CHANNEL CROSSOVER setting should be Enabled on UR2 This forces UR2 to forward messages received on Rx1 out Tx2 and messages received on Rx2 out Tx1 ...

Page 93: ... 7J fiber only modules Figure 3 33 LED AND ELED FIBER MODULES 3 3 3 FIBER LASER TRANSMITTERS The following figure shows the configuration for the 72 73 7D and 7K fiber laser modules Figure 3 34 7X LASER FIBER MODULES 7A 7B and 7C modules 7H 7I and 7J modules 1 channel 2 channels Rx1 Rx1 Rx2 Tx1 Tx1 Tx2 831719A3 CDR 1 channel 2 channels Rx1 Rx1 Rx2 Tx1 Tx1 Tx2 831720A5 CDR 72 and 7D modules 73 and ...

Page 94: ... the 2I and 2J fiber laser module Figure 3 35 2I AND 2J LASER FIBER MODULE Observing any fiber transmitter output can injure the eye When using a laser Interface attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver 2 channels Tx1 Tx2 Rx1 Rx2 831827A1 CDR 2I and 2J modules CAUTION NOTICE ...

Page 95: ... BETWEEN TWO G 703 INTERFACES Pin nomenclature can differ from one manufacturer to another Therefore it is not uncommon to see pinouts num bered TxA TxB RxA and RxB In such cases it can be assumed that A is equivalent to and B is equivalent to b G 703 SELECTION SWITCH PROCEDURES 1 With the power to the relay off remove the G 703 module 7R or 7S as follows Record the original location of the module...

Page 96: ...disabled OFF d G 703 TIMING MODES There are two timing modes for the G 703 module internal timing mode and loop timing mode default Internal Timing Mode The system clock is generated internally Therefore the G 703 timing selection should be in the internal timing mode for back to back UR to UR connections For back to back connections set for octet timing S1 OFF and timing mode to internal timing S...

Page 97: ...e Figure 3 39 G 703 MINIMUM REMOTE LOOPBACK MODE In dual loopback mode the multiplexers are active and the functions of the circuit are divided into two with each receiver transmitter pair linked together to deconstruct and then reconstruct their respective signals Differential Manchester data enters the Differential Manchester receiver module and then is returned to the differential Manchester tr...

Page 98: ...lock input for the two RS422 channels The system functions correctly when the following connections are observed and your data module has a terminal timing feature Terminal timing is a common fea ture to most synchronous data units that allows the module to accept timing from an external source Using the terminal timing feature two channel applications can be achieved if these connections are foll...

Page 99: ... proper system operation For example the following figure shows the positive edge of the Tx clock in the center of the Tx data bit Figure 3 44 CLOCK AND DATA TRANSITIONS Data module 1 Data module 2 Signal name Signal name SD A Send data TT A Terminal timing TT B Terminal timing SD B Send data RD A Received data RD A Received data SD A Send data SD B Send data RD B Received data RD B Received data ...

Page 100: ...hen using a LASER Interface attenuators can be necessary to ensure that you do not exceed maximum optical input power to the receiver Figure 3 45 RS422 AND FIBER INTERFACE CONNECTION Connections shown above are for multiplexers configured as DCE data communications equipment units 3 3 7 G 703 AND FIBER INTERFACE The figure below shows the combined G 703 plus fiberoptic interface configuration at 6...

Page 101: ...er optic connector type ST Wavelength 820 40 nm Connection as per all fiber optic connections a Tx to Rx connection is required The UR series C37 94 communication module can be connected directly to any compliant digital multiplexer that supports the IEEE C37 94 standard shown as follows The UR series C37 94 communication module can be connected to the electrical interface G 703 RS422 or X 21 of a...

Page 102: ...ord the original location of the module to help ensure that the same or replacement module is inserted into the correct slot 2 Simultaneously pull the ejector inserter clips located at the top and at the bottom of each module in order to release the module for removal 3 Remove the module cover screw 4 Remove the top cover by sliding it towards the rear and then lift it upwards 5 Set the timing sel...

Page 103: ...s follows Flashing green loop timing mode while receiving a valid data packet Cover screw Top cover Bottom cover Ejector inserter clip Ejector inserter clip Timing selection switches Channel 1 Channel 2 FRONT REAR 831774A3 CDR Tx1 Tx2 Rx1 Rx2 Tx1 Tx2 CH1 Link Activity LED CH2 Link Activity LED COMMS 2B C37 94SM 1300nm single mode ELED 2 channel Technical support Tel 905 294 6222 Fax 905 201 2098 N...

Page 104: ... data packet Solid red switch to internal timing mode while not receiving a valid data packet The link activity LED status is as follows Flashing green FPGA is receiving a valid data packet Solid yellow FPGA is receiving a yellow bit and remains yellow for each yellow bit Solid red FPGA is not receiving a valid packet or the packet received is invalid ...

Page 105: ...atible with HP HFBR 1315T transmitter and HP HFBR 2316T receiver Fiber optic cable length up to 11 4 km Fiber optic connector type ST Wavelength 1300 40 nm Connection as per all fiber optic connections a Tx to Rx connection is required The UR series C37 94SM communication module can be connected directly to any compliant digital multiplexer that sup ports C37 94SM as shown below It can also can be...

Page 106: ... original location of the module to help ensure that the same or replacement module is inserted into the correct slot 2 Simultaneously pull the ejector inserter clips located at the top and at the bottom of each module in order to release the module for removal 3 Remove the module cover screw 4 Remove the top cover by sliding it towards the rear and then lift it upwards 5 Set the timing selection ...

Page 107: ... follows Flashing green loop timing mode while receiving a valid data packet Cover screw Top cover Bottom cover Ejector inserter clip Ejector inserter clip Timing selection switches Channel 1 Channel 2 FRONT REAR 831774A3 CDR Tx1 Tx2 Rx1 Rx2 Tx1 Tx2 CH1 Link Activity LED CH2 Link Activity LED COMMS 2B C37 94SM 1300nm single mode ELED 2 channel Technical support Tel 905 294 6222 Fax 905 201 2098 NO...

Page 108: ... data packet Solid red switch to internal timing mode while not receiving a valid data packet The link activity LED status is as follows Flashing green FPGA is receiving a valid data packet Solid yellow FPGA is receiving a yellow bit and remains yellow for each yellow bit Solid red FPGA is not receiving a valid packet or the packet received is invalid ...

Page 109: ... required See the EnerVista UR Setup Help File or refer to the EnerVista UR Setup Software section in Chapter 1 for details 4 1 3 ENERVISTA UR SETUP OVERVIEW a ENGAGING A DEVICE The EnerVista UR Setup software can be used in online mode relay connected to directly communicate with the C60 relay Communicating relays are organized and grouped by communication interfaces and into sites Sites can cont...

Page 110: ...n that had been removed from the Settings List tree menu it is added back to the Settings List tree menu Drag and Drop The Site List and Settings List control bar windows are each mutually a drag source and a drop target for device order code compatible files or individual menu items Also the Settings List control bar window and any Windows Explorer directory folder are each mutually a file drag s...

Page 111: ...tended to inform users that the Modbus addresses have changed with the upgraded firmware This message does not signal any problems when appearing after firmware upgrades 4 1 4 ENERVISTA UR SETUP MAIN WINDOW The EnerVista UR Setup software main window supports the following primary display components 1 Title bar that shows the pathname of the active data view 2 Main window menu bar 3 Main window to...

Page 112: ...rocedure describes how to enable the settings tem plate for UR series settings files 1 Select a settings file from the offline window of the EnerVista UR Setup main screen 2 Right click the selected device or settings file and select the Template Mode Create Template option The settings file template is now enabled and the file tree displayed in light blue The settings file is now in template edit...

Page 113: ...below Figure 4 3 SETTINGS TEMPLATE VIEW TWO SETTINGS SPECIFIED AS EDITABLE 5 Click on Save to save changes to the settings template 6 Proceed through the settings tree to specify all viewable settings The next time that the device settings are accessed only those specified as viewable editable display in the menu hierarchy c ADDING PASSWORD PROTECTION TO A TEMPLATE GE recommends that templates be ...

Page 114: ...gs with settings not available for editing greyed out Use the following procedure to only display settings available for editing 3 Right click the device in the Online or Offline Window area and apply the template by selecting the Template Mode View In Template Mode option 4 Enter the template password then click OK to apply the template Once the template has been applied users are limited to view...

Page 115: ...ted to edit the settings specified by the template but all settings are shown The effect of applying the template to the phase time overcurrent settings is shown below Figure 4 6 APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND e REMOVING THE SETTINGS TEMPLATE Once a settings template is removed it cannot be reapplied and a new settings template needs to be defined before use 3 Right click the...

Page 116: ...ries of a FlexLogic equation 1 Right click the settings file or online device and select the Template Mode Create Template item to enable the set tings template feature 2 If prompted enter the template password 3 Select the FlexLogic FlexLogic Equation Editor settings menu item By default all FlexLogic entries are specified as viewable and displayed against a yellow background The icon on the uppe...

Page 117: ... as shown below and on the front panel display Figure 4 9 SECURED FLEXLOGIC IN GRAPHICAL VIEW b LOCKING FLEXLOGIC EQUATIONS TO A SERIAL NUMBER A settings file and associated FlexLogic equations also can be locked to a UR serial number Once FlexLogic entries in a settings file have been secured use the following procedure to lock the settings file to a serial number A serial number is viewable unde...

Page 118: ...ate time and serial number of the C60 are sent back to EnerVista UR Setup and added to the settings file on the local PC This infor mation can be compared with the C60 actual values at any later date to determine if security has been compromised The traceability information is only included in the settings file if a complete settings file is either transferred to the C60 device or obtained from th...

Page 119: ...any changes have been made to the relay configuration since the settings file was saved a SETTINGS FILE TRACEABILITY INFORMATION The serial number and file transfer date are saved in the settings files when they are sent to a C60 device The C60 serial number and file transfer date are included in the settings file device definition within the EnerVista UR Setup offline window as shown in the examp...

Page 120: ... INFORMATION SERIAL NUMBER ACTUAL VALUES PRODUCT INFO MODEL INFORMATION LAST SETTING CHANGE c ADDITIONAL TRACEABILITY RULES The following additional rules apply for the traceability feature If the user changes any settings within the settings file in the offline window then the traceability information is removed from the settings file If the user creates a new settings file then no traceability i...

Page 121: ...etup software The front panel interface consists of LED panels an RS232 port keypad LCD display control pushbuttons and optional user programmable pushbuttons The faceplate is hinged to allow easy access to the removable modules There is also a removable dust cover that fits over the faceplate that must be removed in order to access the keypad panel The following figure shows the horizontal arrang...

Page 122: ...SETTINGS INPUT OUTPUTS RESETTING menu The RS232 port is intended for connection to a portable PC The USER keys are used by the breaker control feature Figure 4 18 TYPICAL LED INDICATOR PANEL FOR ENHANCED FACEPLATE The status indicators in the first column are described below IN SERVICE This LED indicates that control power is applied all monitored inputs outputs and internal systems are OK and tha...

Page 123: ...udes phase instantaneous overcurrent phase undervoltage etc This means that the phase A B and C operate oper ands for individual protection elements are ORed to turn on or off the phase A B or C LEDs VOLTAGE This LED indicates voltage was involved CURRENT This LED indicates current was involved FREQUENCY This LED indicates frequency was involved OTHER This LED indicates a composite function was in...

Page 124: ... when the operate operand associated with the element is asserted and remain on until the RESET button on the front panel is pressed after the operand is reset All elements that are able to discriminate faulted phases can independently turn off or on the phase A B or C LEDs This includes phase instantaneous overcurrent phase undervoltage etc This means that the phase A B and C operate oper ands fo...

Page 125: ...ight user setting groups revisions 3 0x and higher support six setting groups For convenience of users using earlier firmware revisions the relay panel shows eight setting groups Please note that the LEDs despite their default labels are fully user programmable The relay is shipped with the default label for the LED panel 2 The LEDs however are not pre programmed To match the pre printed label the...

Page 126: ...r and press the Print button in the front panel report window 5 When printing is complete fold the sheet along the perforated lines and punch out the labels 6 Remove the C60 label insert tool from the package and bend the tabs as described in the following procedures These tabs are used for removal of the default and custom LED labels It is important that the tool be used EXACTLY as shown below wi...

Page 127: ...pwards as shown below 2 Bend the tab at the center of the tool tail as shown below The following procedure describes how to remove the LED labels from the C60 enhanced front panel and insert the custom labels 1 Use the knife to lift the LED label and slide the label tool underneath Make sure the bent tabs are pointing away from the relay ...

Page 128: ...n below This attaches the label tool to the LED label 3 Remove the tool and attached LED label as shown below 4 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs as shown below The following procedure describes how to remove the user programmable pushbutton labels from the C60 enhanced front panel and insert the custom labels ...

Page 129: ...of the label tool underneath as shown below Make sure the bent tab is pointing away from the relay 2 Slide the label tool under the user programmable pushbutton label until the tabs snap out as shown below This attaches the label tool to the user programmable pushbutton label 3 Remove the tool and attached user programmable pushbutton label as shown below ...

Page 130: ...tively val ues can be entered with the numeric keypad The decimal key initiates and advances to the next character in text edit mode or enters a decimal point The HELP key can be pressed at any time for context sensitive help messages The ENTER key stores altered setting values When entering an IP address on the front panel key in the first sequence of the number then press the key for the deci ma...

Page 131: ...breakers 4 3 7 MENUS a NAVIGATION Press the MENU key to select a header display page top level menu The header title appears momentarily followed by a header display page menu item Each press of the MENU key advances through the following main heading pages Actual values Settings ENTER COMMAND PASSWORD This message appears when the USER 1 USER 2 or USER 3 key is pressed and a COMMAND PASSWORD is r...

Page 132: ...4 24 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 Commands Targets User displays when enabled ...

Page 133: ...ears This page contains system and relay status information Repeatedly press the MESSAGE keys to display the other actual value headers SETTINGS PRODUCT SETUP Press the MENU key until the header for the first page of Settings appears This page contains settings to configure the relay SETTINGS SYSTEM SETUP Press the MESSAGE DOWN key to move to the next Settings page This page con tains settings for...

Page 134: ...the VALUE DOWN key displays the previous selection c ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length but user defined in character They can be upper case letters lower case letters numerals and a selection of special characters FLASH MESSAGE TIME 1 0 s For example select the SETTINGS PRODUCT SETUP DISPLAY PROPERTIES FLASH MESSAGE TIME setting MINIMUM 0 5 MAXIMUM...

Page 135: ...ey until the SECURITY message appears on the display 3 Press the MESSAGE DOWN key until the INSTALLATION message appears on the display 4 Press the MESSAGE RIGHT key until the RELAY SETTINGS Not Programmed message is displayed 5 After the RELAY SETTINGS Not Programmed message appears on the display press the VALUE keys change the selection to Programmed 6 Press the ENTER key 7 When the NEW SETTING...

Page 136: ...pe in the same password and press ENTER 9 When the NEW PASSWORD HAS BEEN STORED message appears your new Setting or Command Password will be active f CHANGING EXISTING PASSWORD To change an existing password follow the instructions in the previous section with the following exception A message prompts you to type in the existing password for each security level before a new password can be entered...

Page 137: ...See page 5 65 FAULT REPORT See page 5 70 OSCILLOGRAPHY See page 5 72 DATA LOGGER See page 5 74 DEMAND See page 5 76 USER PROGRAMMABLE LEDS See page 5 77 USER PROGRAMMABLE SELF TESTS See page 5 80 CONTROL PUSHBUTTONS See page 5 82 USER PROGRAMMABLE PUSHBUTTONS See page 5 84 FLEX STATE PARAMETERS See page 5 88 USER DEFINABLE DISPLAYS See page 5 89 DIRECT I O See page 5 91 TELEPROTECTION See page 5 9...

Page 138: ...ee page 5 161 FLEXLOGIC TIMERS See page 5 161 FLEXELEMENTS See page 5 162 NON VOLATILE LATCHES See page 5 166 SETTINGS GROUPED ELEMENTS SETTING GROUP 1 See page 5 168 SETTING GROUP 2 SETTING GROUP 6 SETTINGS CONTROL ELEMENTS TRIP BUS See page 5 205 SETTING GROUPS See page 5 207 SELECTOR SWITCH See page 5 209 SYNCHROCHECK See page 5 215 AUTORECLOSE See page 5 220 DIGITAL ELEMENTS See page 5 233 DIG...

Page 139: ...OTE OUTPUTS DNA BIT PAIRS See page 5 263 REMOTE OUTPUTS UserSt BIT PAIRS See page 5 264 RESETTING See page 5 264 DIRECT INPUTS See page 5 265 DIRECT OUTPUTS See page 5 265 TELEPROT INPUTS See page 5 269 TELEPROT OUTPUTS See page 5 270 IEC 61850 GOOSE ANALOGS See page 5 271 IEC 61850 GOOSE UINTEGERS See page 5 272 SETTINGS TRANSDUCER I O DCMA INPUTS See page 5 273 RTD INPUTS See page 5 274 DCMA OUT...

Page 140: ...pecified in per unit pu calculated quantities pu quantity actual quantity base quantity Where the current source is from a single CT the base quantity is the nominal secondary or primary current of the CT Use the secondary current base to convert per unit current settings to from a secondary current value and use the primary cur rent base to convert to from a primary current value Where the curren...

Page 141: ...s received by the relay EVENTS setting This setting is used to control whether the pickup dropout or operate states are recorded by the event recorder When set to Disabled element pickup dropout or operate are not recorded as events When set to Enabled events are created for Element PKP pickup Element DPO dropout Element OP operate The DPO event is created when the measure and decide comparator ou...

Page 142: ...or example in the scheme shown in the above diagram the user configures one source to be the sum of CT1 and CT2 and can name this source as Wdg1 I Once the sources have been configured the user has them available as selections for the choice of input signal for the pro tection elements and as metered quantities b CT VT MODULE CONFIGURATION CT and VT input channels are contained in CT VT modules Th...

Page 143: ...ed by the user to know how to connect the relay to external circuits Bank identification consists of the letter designation of the slot in which the CT VT module is mounted as the first character followed by numbers indicating the channel either 1 or 5 See the HardFiber instruction manual for designations of HardFiber voltage and current banks For three phase channel sets the number of the lowest ...

Page 144: ...sing a recognizable corporate email account Customer service provides a code to reset the relay to the factory defaults 2 Enter the reset code on the front panel under COMMANDS RELAY MAINTENANCE SERVICE COMMAND 3 Change the default password of ChangeMe1 as outlined in the Setting Up CyberSentry and Changing Default Pass word section in the first chapter PASSWORD REQUIREMENTS A user account require...

Page 145: ...sta UR Setup software and are disabled either by the user or by timeout The state of the session local or remote setting or command determines the state of the following FlexLogic operands ACCESS LOC SETG OFF Asserted when local setting access is disabled ACCESS LOC SETG ON Asserted when local setting access is enabled ACCESS LOC CMND OFF Asserted when local command access is disabled ACCESS LOC C...

Page 146: ...N PATH SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION The following access supervision settings are available INVALID ATTEMPTS BEFORE LOCKOUT This setting specifies the number of times an incorrect password can be entered within a three minute time span before lockout occurs When lockout occurs the LOCAL ACCESS DENIED or REMOTE ACCESS DENIED FlexLogic operands are set to On These operands are ...

Page 147: ...as normal that is a local setting password is required If this setting is any contact input on FlexLogic operand then the operand must be asserted set as on prior to providing the local setting password to gain setting access If setting access is not authorized for local operation front panel or RS232 interface and the user attempts to obtain setting access then the UNAUTHORIZED ACCESS message is ...

Page 148: ...ess Authorized Timeout setting represents the timeout delay remote setting access This setting is applicable when the Remote Settings Authorized setting is programmed to any operand except On or Off The state of the Flex Logic operand is continuously monitored for an off to on transition When this occurs remote setting access is permitted and the timer programmed with the Access Authorized Timeout...

Page 149: ...ed to enter a username and password ADD A NEW USER The following pre requisites are required to add user accounts to the EnerVista security management system The user adding the account must have administrator rights The EnerVista security management system must be enabled previous section To add user accounts 1 Select the Security User Management menu item to open the user management window 2 Ent...

Page 150: ...al values Settings Allows the user to read setting values Commands Allows the user to execute commands Event Recorder Allows the user to use the digital fault recorder FlexLogic Allows the user to read FlexLogic values Update Info Allows the user to write to any function to which they have read privileges When any of the Settings Event Recorder and FlexLogic check boxes are enabled by themselves t...

Page 151: ...omer enabled features are open All the other ports are closed For example Modbus is on by default so its TCP port number 502 is open But if Modbus is disabled port 502 is closed This function has been tested and no unused ports have been found open When CyberSentry is enabled Modbus communications over Ethernet is encrypted which is not always tolerated by SCADA systems The UR has a bypass access ...

Page 152: ...authentication port 1 65535 1812 Administrator Primary Accounting Port RADIUS accounting port 1 65535 1813 Administrator Vendor ID An identifier that specifies RADIUS vendor specific attributes used with the protocol Value that represents General Electric Administrator RADIUS Authentication Shared Secret Shared secret used in authentication It displays as asterisks This setting must meet the Cyber...

Page 153: ...abled To re enable device authentication the Supervisor unlocks the device for setting changes and then the Administrator can re enable device authentication Disabled Enabled Enabled Administrator Firmware Locked Indicates if the device receives firmware upgrades If Yes and the firmware upgrade attempt is made the device denies the upgrade and displays an error message that the lock is set On each...

Page 154: ...Supervisor role authenticates to unlock the UR relay for setting changes and not approve changes after the fact Only Supervisor can set the Settings and Firmware Lock in the Security Settings This role also has the ability to forcefully logoff any other role and clear the security event log This role can also be disabled but only through a Supervisor authentication When this role is disabled its p...

Page 155: ...ervisor approval can change the role associated password In CyberSentry password encryption is not supported Session Settings PATH SETTINGS PRODUCT SETUP SECURITY SESSION SETTINGS The following session settings are available SESSION LOCKOUT This setting specifies the number of failed authentications the default is three and the maxi mum is 99 before the device blocks subsequent authentication atte...

Page 156: ...the Bypass Access feature for such situations which allows unencrypted Modbus over Ethernet Setting it to Remote ensures no authentication is required over Ethernet and Modbus communication is unen crypted Only a Supervisor or Administrator if Supervisor role is disabled can enable this feature Note that other protocols DNP 101 103 104 EGD are not encrypted and they are good communications options...

Page 157: ...th the Session Lockout threshold When the Session Lockout threshold is exceeded a minor alarm indication comes up Operand is AUTHENTICA TION FAIL FIRMWARE LOCK When Enabled any firmware upgrade attempt brings up a minor self test alarm Operand is UNAUTH FW ATTEMPT SETTINGS LOCK When Enabled an unauthorized write attempt to a setting for a given role activates a minor self test alarm Operand is UNA...

Page 158: ...s user names Administra tor Supervisor Engineer Operator Observer in the RADIUS server If you do the UR relay automatically provides the authentication from the device 4 In the EnerVista software choose server authentication and log in using the user name and password configured on the RADIUS server for server authentication login 5 After making any required changes log out When changing settings ...

Page 159: ...cation with origin information username and IP MAC address a time stamp in UTC time when it occurred AUTH_LOCKOUT ORIGIN TIMESTAMP Error 3 An authentication lockout has occurred because of too many failed authentication attempts FIRMWARE_UPGD ORIGIN TIMESTAMP Warning 4 Indicates that a change of firmware has occurred FIRMWARE_LOCK ORIGIN TIMESTAMP Critical 1 An attempt was made to change firmware ...

Page 160: ... susceptible to noise Some customers prefer very low currents to display as zero while others prefer the current be displayed even when the value reflects noise rather than the actual signal The C60 applies a cut off value to the magnitudes and angles of the measured currents If the magnitude is below the cut off level it is substi tuted with zero This applies to phase and ground current phasors a...

Page 161: ...A 13811 2 V 66 4 V 720 5 watts Any calculated power value below this cut off will not be displayed As well the three phase energy data will not accumu late if the total power from all three phases does not exceed the power cut off Lower the VOLTAGE CUT OFF LEVEL and CURRENT CUT OFF LEVEL with care as the relay accepts lower sig nals as valid measurements Unless dictated otherwise by a specific app...

Page 162: ...amma ble pushbuttons can provide extra security if required For example to assign user programmable pushbutton 1 to clear demand records the following settings should be applied 1 Assign the clear demand function to pushbutton 1 by making the following change in the SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS menu CLEAR DEMAND PUSHBUTTON 1 ON 2 Set the properties for user programmable pushbutton 1 ...

Page 163: ... firmware A maximum of 32 relays can be daisy chained and connected to a DCS PLC or computer using the RS485 ports If IEC 60870 103 is chosen as the protocol valid baud rates are 9600 and 19200 bit s and valid parity is Even COMMUNICATIONS SERIAL PORTS See page 5 27 MESSAGE NETWORK See page 5 30 MESSAGE ROUTING See page 5 32 MESSAGE MODBUS PROTOCOL See page 5 35 MESSAGE PROTOCOL DNP 3 0 Range DNP ...

Page 164: ...10 1 1 2 255 255 255 0 where LAN 1 is 10 1 1 x 255 255 255 0 IP2 Mask2 10 2 1 2 255 255 255 0 where LAN2 is 10 2 1 x 255 255 255 0 IP3 Mask3 10 3 1 2 255 255 255 0 where LAN3 is 10 3 1 x 255 255 255 0 Example 2 IP1 Mask1 10 1 1 2 255 0 0 0 where LAN1 is 10 x x x 255 0 0 0 IP2 Mask2 11 1 1 2 255 0 0 0 where LAN2 is 11 x x x 255 0 0 0 IP3 Mask3 12 1 1 2 255 0 0 0 where LAN3 is 12 x x x 255 0 0 0 Exa...

Page 165: ...uses the IP and MAC address of P2 Figure 5 5 MULTIPLE LANS WITH REDUNDANCY Multiple LANS No Redundancy The following topology provides local configuration monitoring through EnerVista software on LAN1 to which port 1 P1 is connected access to the public network on LAN2 to which port 2 P2 is connected and communications with SCADA on LAN3 to which port 3 P3 is connected There is no redundancy Figur...

Page 166: ...2 REDUNDANCY determines if ports 2 and 3 operate in redundant or independent mode If a license for PRP was pur chased the options are None Failover and PRP If a license for PRP was not purchased the available options are None and Failover In non redundant mode REDUNDANCY set to None ports 2 and 3 operate independently with their own MAC IP and mask addresses If REDUNDANCY is set to Failover the op...

Page 167: ...t does not conflict with another multicast protocol e FAR END FAULT INDICATION FEFI Since 100BASE FX does not support Auto Negotiation a Far End Fault Indication FEFI feature is included in UR 7 that allows for detection of link failures The purpose of the Far End Fault feature is to allow the stations on both ends of a pair of fibers to be informed when there is a problem with one of the fibers W...

Page 168: ... to align PRP with the High availability Seamless Redundancy HSR protocol To achieve this the original PRP was modified at the cost of losing compatibility with the PRP 2010 ver sion The revised standard IEC 62439 3 2012 is commonly referred to as PRP 1 while the original standard is PRP 0 The UR relays support only PRP 1 The relay implements PRP on two of its Ethernet ports specifically Port 2 an...

Page 169: ...y Static Routes To delete a route 1 Replace the route destination with the default loopback address 127 0 0 1 When deleting a route the mask and gateway must be also brought back to default values 2 Delete the default route by replacing the default gateway with the default value 127 0 0 1 GENERAL CONDITIONS TO BE SATISFIED BY STATIC ROUTES The following rules are validated internally The route mas...

Page 170: ...1 1 Port 2 IP address 10 1 2 2 connects the UR to LAN 10 1 2 0 24 and to the EnerVista software through Router 2 Router 2 has an interface on 10 1 2 0 24 and the IP address of this interface is 10 1 2 1 The configuration before release 7 10 was as follows PRT1 IP ADDRESS 10 1 1 2 PRT1 SUBNET IP MASK 255 255 255 0 PRT1 GWY IP ADDRESS 10 1 1 1 PRT2 IP ADDRESS 10 1 2 2 PRT2 SUBNET IP MASK 255 255 255...

Page 171: ...e with protocol specifications for broadcast messages never replies Addresses do not have to be sequential but no two devices can have the same address or conflicts resulting in errors occur Generally each device added to the link should use the next higher address starting at 1 When using Modbus TCP IP the client must use the programmed MODBUS SLAVE ADDRESS value in the Unit Identifier field See ...

Page 172: ...DNP CHANNEL 1 2 PORT SETTINGS RS232 RS485 ETHERNET DNP Channel 1 Eth TCP Channel 2 Eth TCP Modbus Modbus DNP Modbus IEC 61850 Channel 1 Eth TCP Channel 2 none Modbus Modbus DNP Modbus IEC 61850 Channel 1 none Channel 2 Eth TCP Modbus Modbus DNP Modbus IEC 61850 Channel 1 Eth UDP Channel 2 none Modbus Modbus DNP Modbus IEC 61850 Channel 1 Eth TCP Channel 2 RS485 Modbus DNP DNP Modbus IEC 61850 Chan...

Page 173: ...0000 MESSAGE DNP VOLTAGE SCALE FACTOR 1 Range 0 001 0 01 0 1 1 10 100 1000 10000 100000 MESSAGE DNP POWER SCALE FACTOR 1 Range 0 001 0 01 0 1 1 10 100 1000 10000 100000 MESSAGE DNP ENERGY SCALE FACTOR 1 Range 0 001 0 01 0 1 1 10 100 1000 10000 100000 MESSAGE DNP PF SCALE FACTOR 1 Range 0 001 0 01 0 1 1 10 100 1000 10000 100000 MESSAGE DNP OTHER SCALE FACTOR 1 Range 0 001 0 01 0 1 1 10 100 1000 100...

Page 174: ...g is set to Network UDP the channel 1 DNP protocol can be used over UDP IP on the Ethernet ports See the DNP appendix for information on the DNP protocol Changes to these settings take effect when power has been cycled to the relay Do not set more than one protocol to the same TCP UDP port number as this results in unreliable operation of those protocols The DNP ADDRESS setting is the DNP slave ad...

Page 175: ...ta These settings group the C60 analog input data into the following types current voltage power energy power factor and other Each setting represents the default deadband value for all analog input points of that type For example to trigger unsolic ited responses from the C60 when any current values change by 15 A the DNP CURRENT DEFAULT DEADBAND setting should be set to 15 Note that these settin...

Page 176: ...S Up to 256 binary and up to 256 analog input points for the DNP protocol or the MSP and MME points for IEC 60870 5 104 protocol can be configured The value for each point is user programmable and can be configured by assigning FlexLogic operands for binary inputs MSP points or FlexAnalog parameters for analog inputs MME points The menu for the binary input points DNP or MSP points IEC 60870 5 104...

Page 177: ...utilizing 61850 messaging it can be desirable to route 61850 traffic on a separate port from SCADA communications or to use redundant inde pendent ports and a high speed network recovery method such as PRP The C60 supports the Manufacturing Message Specification MMS protocol as specified by IEC 61850 MMS is supported over two protocol stacks TCP IP over Ethernet The C60 operates as an IEC 61850 se...

Page 178: ...time interval The DEFAULT GSSE GOOSE UPDATE TIME setting is applicable to GSSE fixed C60 GOOSE and configurable GOOSE The GSSE settings are shown below PATH SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE GOOSE CONFIGURATION TRANSMISSION GSEE These settings are applicable to GSSE only If the fixed GOOSE function is enabled GSSE messages are not transmitted The GSSE ID setting represe...

Page 179: ...vious to 5 0x the destination Ethernet MAC address was determined automatically by taking the sending MAC address that is the unique local MAC address of the C60 and setting the multicast bit The GOOSE VLAN PRIORITY setting indicates the Ethernet priority of GOOSE messages This allows GOOSE messages to have higher priority than other Ethernet data The GOOSE ETYPE APPID setting allows the selection...

Page 180: ...ts 1 through 8 the integrity GOOSE message will still continue to be sent at the pre configured rate even if no changes in the data items are detected The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes sages due to an oscillation being created that is triggering a message The C60 has the ability of detecting if a data item in one of the ...

Page 181: ...he configuration required to transfer IEC 61850 data items between two devices The general steps required for transmission configuration are 1 Configure the transmission dataset 2 Configure the GOOSE service settings 3 Configure the data The general steps required for reception configuration are 1 Configure the reception dataset 2 Configure the GOOSE service settings 3 Configure the data Table 5 7...

Page 182: ...must match the configuration on the receiver the default value is 0 Set the CONFIG GSE 1 CONFREV value This value changes automatically as described in IEC 61850 part 7 2 For this example it can be left at its default value 3 Configure the data by making the following changes in the PRODUCT SETUP COMMUNICATION IEC 61850 PROTO COL GGIO1 STATUS CONFIGURATION settings menu Set GGIO1 INDICATION 1 to a...

Page 183: ...d by the GGIO1 ST Ind1 stVal value in the sending device The above settings will be automatically populated by the EnerVista UR Setup software when a com plete SCD file is created by third party substation configurator software For intercommunication between C60 IEDs the fixed DNA UserSt dataset can be used The DNA UserSt dataset con tains the same DNA and UserSt bit pairs that are included in GSS...

Page 184: ... two data items The Boolean status values from these data items can be utilized as remote input FlexLogic operands First the REMOTE DEVICE 1 16 DATASET setting must be set to contain dataset GOOSEIn 1 that is the first configurable dataset Then REMOTE IN 1 16 ITEM settings must be set to Dataset Item 1 and Dataset Item 2 These remote input FlexLogic operands will then change state in accordance wi...

Page 185: ...the C60 is restarted Do not set more than one protocol to the same TCP UDP port number as this results in unreliable operation of those protocols The SERVER SCANNING feature should be set to Disabled when IEC 61850 client server functionality is not required IEC 61850 has two modes of functionality GOOSE GSSE inter device communication and client server communication If the GOOSE GSSE functionalit...

Page 186: ...d values used to determine when the update the MMXU mag and cVal values from the associated instmag and instcVal values The mag and cVal values are used for the IEC 61850 buffered and unbuffered reports These settings correspond to the associated db data items in the CF functional con straint of the MMXU logical node as per the IEC 61850 standard According to IEC 61850 7 3 the db value shall repre...

Page 187: ...o control the C60 virtual inputs The GGIO4 analog configuration points are shown below PATH SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO4 ANALOG CONFIGURATION The NUMBER OF ANALOG POINTS setting determines how many analog data points will exist in GGIO4 When this value is changed the C60 must be rebooted in order to allow the GGIO4 logical node to be re instantiated and contain th...

Page 188: ...t all values can be stored Some values may be rounded to the closest possible floating point number The GGIO5 integer configuration points are shown below PATH SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO5 ANALOG CONFIGURATION The GGIO5 logical node allows IEC 61850 client access to integer data values This allows access to as many as 16 unsigned integer value points associated ti...

Page 189: ...a value from the list of IEC 61850 data attributes supported by the C60 Changes to the dataset will only take effect when the C60 is restarted It is recommended to use reporting service from logical node LLN0 if a user needs some but not all data from already existing GGIO1 GGIO4 and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset REPORT 1 DATASET ITEM...

Page 190: ...an result in very large OpCnt values over time This setting allows the OpCnt to be reset to 0 for XCBR1 XCBR CONFIGURATION XCBR1 ST LOC OPERAND Off Range FlexLogic operand MESSAGE XCBR6 ST LOC OPERAND Off Range FlexLogic operand MESSAGE CLEAR XCBR1 OpCnt No Range No Yes MESSAGE CLEAR XCBR6 OpCnt No Range No Yes MESSAGE XCBR1 SYNCCHECK CLS Off Range FlexLogic operand MESSAGE XCBR6 SYNCCHECK CLS Off...

Page 191: ...te details on these control models The XCBR1 Pos sboTimeout setting is used to select SBO timeout value To be successful the IEC 61850 operate com mand must be executed after the select command within the XCBR1 Pos sboTimeout setting value The disconnect switch configuration settings are shown below Changes to these values will not take effect until the UR is restarted PATH SETTINGS PRODUCT SETUP ...

Page 192: ...P UDP port number as this results in unreliable operation of those protocols n TFTP PROTOCOL PATH SETTINGS PRODUCT SETUP COMMUNICATIONS TFTP PROTOCOL The Trivial File Transfer Protocol TFTP can be used to transfer files from the C60 over a network The C60 operates as a TFTP server TFTP client software is available from various sources including Microsoft Windows NT The dir txt file obtained from t...

Page 193: ...threshold values from the default for each individual M_ME_NC_1 analog point Whenever power is removed and re applied to the C60 the default thresholds are in effect The IEC REDUNDANCY setting decides whether multiple client connections are accepted or not If redundancy is set to Yes two simultaneous connections can be active at any given time IEC TCP PORT NUMBER When set to 0 the change takes eff...

Page 194: ...s used for the real time transfer of data for display and control purposes The relay can be configured to produce EGD data exchanges and other devices can be configured to consume EGD data exchanges The number of produced exchanges up to three the data items in each exchange up to 50 and the exchange production rate can be configured EGD cannot be used to transfer data between UR series relays The...

Page 195: ...D exchange 1 has a setting range of 50 to 1000 ms Exchanges 2 and 3 have a setting range of 500 to 1000 ms FAST PROD EXCH 1 CONFIGURATION EXCH 1 FUNCTION Disable Range Disable Enable MESSAGE EXCH 1 DESTINATION 0 0 0 0 Range standard IP address MESSAGE EXCH 1 DATA RATE 1000 ms Range 50 to 1000 ms in steps of 1 MESSAGE EXCH 1 DATA ITEM 1 0 Range 0 to 65535 in steps of 1 Modbus register address range...

Page 196: ...e IEC 60870 5 103 protocol is enabled when the SETTINGS PRODUCT SETUP COMMUNICATIONS PROTOCOL set ting is set to IEC 60870 5 103 IEC103 COMMON ADDRESS OF ASDU This setting uniquely defines this C60 on the serial line Select an ID between 0 and 254 This ID does not need to be in sequential order for all stations that communicate with a controller but it is recom mended Note that RS485 only allows a...

Page 197: ...e to a general interrogation received from the controller or reported spontaneously Spontaneous transmission occurs as a response to cyclic Class 2 requests If the C60 wants to transmit Class 1 data at that time it demands access for Class 1 data transmission ACD 1 in the con trol field of the response For any change to take effect restart the relay PATH SETTINGS PRODUCT SETUP COMMUNICATIONS IEC60...

Page 198: ...GE ASDU 1 ANALOG 9 FACTOR 1 000 Range 0 000 to 65 535 in steps of 0 001 MESSAGE ASDU 1 ANALOG 9 OFFSET 0 Range 32768 to 32767 in steps of 1 ASDU 4 ASDU 4 TYP 9 Range 3 or 9 MESSAGE ASDU 4 FUN 0 Range 0 to 255 in steps of 1 MESSAGE ASDU 4 INF 0 Range 0 to 255 in steps of 1 MESSAGE ASDU 4 SCAN TOUT 0 Range 0 to 1000 s in steps of 1 MESSAGE ASDU 4 ANALOG 1 Off Range FlexAnalog parameter MESSAGE ASDU ...

Page 199: ...an configure only one measurand for each ASDU but the user is not allowed to skip ASDU2 and configure measurands in ASDU3 For any change to take effect restart the relay ANALOG FACTOR AND OFFSET For each measurand included in the ASDU a factor and offset can also be configured The factor and offset allow for scaling to be performed on measurands The final measurement sent to the IEC60870 103 mas t...

Page 200: ...able The ON and OFF for the same ASDU command can be mapped to different virtual inputs Each command is identified by the unique combination made by the function type FUN and information number INF If the master sends an ASDU command that does not have the FUN and INF of any configured command the relay rejects it IEC103 COMMANDS COMMAND 0 Range see sub menu below MESSAGE COMMAND 1 Range see sub m...

Page 201: ...reate timestamps for communications protocols as well as for historical data such as event records and oscillography When the relay restarts the RTC initializes from an onboard battery backed clock which has the same accuracy as an electronic watch approximately 1 minute per month 23 ppm Once the RTC is synchronized with the Precision Time Protocol PTP IRIG B or SNTP its accuracy approaches that o...

Page 202: ...ations protocols Whenever a time synchronization message is received through any of the active protocols the UR clock updates However given that IEC 60870 5 103 IEC 60870 5 104 Modbus and DNP are low accuracy time synchronization methods avoid their use for synchronization when better accuracy time protocols such as IRIG B and PTP are active in the system See the COMMANDS SET DATE AND TIME menu se...

Page 203: ... grandmaster role Should a clock on starting up discover it is better that the present grandmaster it assumes the grandmaster role and the previous grandmaster reverts to slave The C60 qualification mechanism accepts a potential master clock as a new grandmaster when in a four second interval it has received three announce messages from it all better than the present grandmaster clock and better t...

Page 204: ...relay s real time clock This is to compensate to the extent practical for time delivery delays not compensated for in the network In a fully compliant PP network the peer delay and the processing delay mechanisms compensate for all the delays between the grandmaster and the relay In such networks this setting should be zero In networks containing one or more switches and or clocks that do not impl...

Page 205: ...ON to Enabled The C60 then listens to SNTP messages sent to the all ones broadcast address for the subnet The C60 waits up to 18 min utes 1024 seconds without receiving an SNTP broadcast message before signaling an SNTP self test error The SNTP UDP PORT NUMBER is 123 for normal SNTP operation If SNTP is not required close the port by setting it to 0 When the SNTP UDP PORT NUMBER is set to 0 the ch...

Page 206: ...culate local time The DAYLIGHT SAVINGS TIME DST settings can be used to allow the relay to follow the DST rules of the local time zone Note that when IRIG B time synchronization is active the local time in the IRIG B signal contains any daylight savings time offset and so the DST settings are ignored 5 2 7 FAULT REPORTS PATH SETTINGS PRODUCT SETUP FAULT REPORTS FAULT REPORT 1 The C60 relay support...

Page 207: ...not triggered again Considering the reset time of protection elements there is very little chance that fault report can be triggered twice in this manner As the fault report must capture a usable amount of pre and post fault data it can not be triggered faster than every 20 ms Each fault report is stored as a file the relay capacity is fifteen 15 files An sixteenth 16th trigger overwrites the olde...

Page 208: ... cycles captured per record See the ACTUAL VALUES RECORDS OSCILLOGRAPHY menu to view the number of cycles captured per record The following table provides sam ple configurations with corresponding cycles record The minimum number of oscillographic records is three A new record can automatically overwrite an older record when TRIGGER MODE is set to Automatic Overwrite Set the TRIGGER POSITION to a ...

Page 209: ...ndent on The type of relay The type and number of CT VT hardware modules installed and The type and number of analog input hardware modules installed Upon startup the relay will automatically prepare the parameter list A list of all possible analog metering actual value parameters is presented in Appendix A FlexAnalog parameters The parameter index number shown in any of the tables is used to expe...

Page 210: ...an be configured with a few channels over a long period or a larger number of channels for a shorter period The relay automatically partitions the available memory between the channels in use Exam ple storage capacities for a system frequency of 60 Hz are shown in the following table DATA LOGGER DATA LOGGER MODE Continuous Range Continuous Trigger MESSAGE DATA LOGGER TRIGGER Off Range FlexLogic op...

Page 211: ...s set to Trigger DATA LOGGER RATE This setting selects the time interval at which the actual value data will be recorded DATA LOGGER CHNL 1 16 This setting selects the metering actual value that is to be recorded in Channel 1 16 of the data log The parameters available in a given relay are dependent on the type of relay the type and number of CT VT hardware modules installed and the type and numbe...

Page 212: ...stic of 15 minutes is illustrated below A setpoint establishes the time to reach 90 of a steady state value just as the response time of an analog instrument A steady state value applied for twice the response time will indicate 99 of the value Figure 5 9 THERMAL DEMAND CHARACTERISTIC CALCULATION METHOD 2 BLOCK INTERVAL This method calculates a linear average of the quantity RMS current real power...

Page 213: ...abled the LED test can be initiated from any digital input or user programmable condition such as user program mable pushbutton The control operand is configured under the LED TEST CONTROL setting The test covers all LEDs including the LEDs of the optional user programmable pushbuttons The test consists of three stages 1 All 62 LEDs on the relay are illuminated This is a quick test to verify if an...

Page 214: ...rned through user programmable pushbutton 1 The following set tings should be applied Configure user programmable pushbutton 1 by making the following entries in the SETTINGS PRODUCT SETUP USER PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu PUSHBUTTON 1 FUNCTION Self reset PUSHBTN 1 DROP OUT TIME 0 10 s Configure the LED test to recognize user programmable pushbutton 1 by making the following ent...

Page 215: ... Each of these indicators can be programmed to illumi nate when the selected FlexLogic operand is in the logic 1 state For the standard faceplate the LEDs are located as follows LED Panel 2 user programmable LEDs 1 through 24 LED Panel 3 user programmable LEDs 25 through 48 For the enhanced faceplate the LEDs are located as follows LED column 2 user programmable LEDs 1 through 12 LED column 3 user...

Page 216: ...YNC 2 SYNC OP LED 7 operand Off LED 19 operand Off LED 8 operand Off LED 20 operand Off LED 9 operand BREAKER 1 OPEN LED 21 operand AR ENABLED LED 10 operand BREAKER 1 CLOSED LED 22 operand AR DISABLED LED 11 operand BREAKER 1 TROUBLE LED 23 operand AR RIP LED 12 operand Off LED 24 operand AR LO USER PROGRAMMABLE SELF TESTS DIRECT RING BREAK FUNCTION Enabled Range Disabled Enabled Valid for units ...

Page 217: ...xLogic operand write to the event recorder or display target messages Moreover they do not trigger the ANY MINOR ALARM or ANY SELF TEST messages When in Enabled mode minor alarms continue to function along with other major and minor alarms See the Relay Self tests section in chapter 7 for information on major and minor self test alarms ...

Page 218: ... and are not protected by the control password However by supervising their output operands the user can dynamically enable or disable control pushbuttons for security reasons Each control pushbutton asserts its own FlexLogic operand These operands should be configured appropriately to perform the desired function The operand remains asserted as long as the pushbutton is pressed and resets when th...

Page 219: ... breaker control typically uses the larger optional user programmable pushbuttons making the control pushbuttons available for other user applications Figure 5 13 CONTROL PUSHBUTTON LOGIC 842010A2 CDR CONTROL PUSHBUTTON 1 FUNCTION SYSTEM SETUP BREAKERS BREAKER 1 BREAKER 1 PUSHBUTTON CONTROL SYSTEM SETUP BREAKERS BREAKER 2 BREAKER 2 PUSHBUTTON CONTROL SETTING SETTINGS TIMER FLEXLOGIC OPERAND Enable...

Page 220: ...tely update the EnerVista software under Maintenance Enable Pushbutton USER PUSHBUTTON 1 PUSHBUTTON 1 FUNCTION Disabled Range Self Reset Latched Disabled MESSAGE PUSHBTN 1 ID TEXT USER PB 1 Range Up to 20 alphanumeric characters MESSAGE PUSHBTN 1 ON TEXT Range Up to 20 alphanumeric characters MESSAGE PUSHBTN 1 OFF TEXT Range Up to 20 alphanumeric characters MESSAGE PUSHBTN 1 HOLD 0 0 s Range 0 0 t...

Page 221: ... set activated by asserting the operand assigned to the PUSH BTN 1 SET setting or by directly pressing the associated front panel pushbutton The state of each pushbutton is stored in non volatile memory and maintained through a loss of control power The pushbutton is reset deactivated in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET set ting or by directly pressing the asso...

Page 222: ...he bottom 20 character line of the user programmable pushbutton message and displays when the pushbutton is deactivated and the PUSHBUTTON 1 FUNCTION is Latched A message does not display when the PUSHBUTTON 1 FUNCTION is Self reset as the pushbutton operand status is implied to be Off upon its release The length of the Off message is configured with the PRODUCT SETUP DISPLAY PROPERTIES FLASH MESS...

Page 223: ...tton is activated While activated target and other messages are suppressed To allow front panel keypad operation when a keypad button is pressed the message is supressed for 10 seconds PUSHBUTTON 1 EVENTS If this setting is enabled each user programmable pushbutton state change is logged as an event into the event recorder The figures show the user programmable pushbutton logic Figure 5 16 USER PR...

Page 224: ...any FlexLogic operand PUSHBTN 1 LED CTL AND SETTING FLASH MESSAGE TIME TRST 0 PUSHBUTTON ON LATCHED LATCHED SELF RESET AND From user programmable pushbuttons logic sheet 1 FLEXLOGIC OPERAND PUSHBUTTON 1 ON FLEXLOGIC OPERAND PUSHBUTTON 1 OFF SETTING TRST 0 Instantaneous reset OFF MESSAGE ENGAGE MESSAGE SETTINGS XXXXXXXXXX PUSHBTN ID TEXT XXXXXXXXXX PUSHBTN OFF TEXT The message is temporarily remove...

Page 225: ...splay note that only the programmed screens are displayed The screens can be scrolled using the UP and DOWN keys The display disappears after the default message time out period specified by the PRODUCT SETUP DISPLAY PROPER TIES DEFAULT MESSAGE TIMEOUT setting USER PROGRAMMABLE CONTROL INPUT The user definable displays also respond to the INVOKE AND SCROLL setting Any FlexLogic operand in particul...

Page 226: ...through the characters A space is selected like a character 4 Press the decimal key to advance the cursor to the next position 5 Repeat step 3 and continue entering characters until the desired text is displayed 6 The HELP key may be pressed at any time for context sensitive help information 7 Press the ENTER key to store the new settings To enter a numerical value for any of the five items the de...

Page 227: ...ws decimal form of user selected Modbus register address corresponding to second tilde marker MESSAGE DISP 1 ITEM 3 0 This item is not being used There is no corresponding tilde marker in top or bottom lines MESSAGE DISP 1 ITEM 4 0 This item is not being used There is no corresponding tilde marker in top or bottom lines MESSAGE DISP 1 ITEM 5 0 This item is not being used There is no corresponding ...

Page 228: ...FlexLogic operands 1 DIRECT RING BREAK direct input output ring break This FlexLogic operand indicates that direct output messages sent from a UR series relay are not being received back by the relay 2 DIRECT DEVICE 1 OFF to DIRECT DEVICE 16 OFF direct device offline These FlexLogic operands indicate that direct output messages from at least one direct device are not being received Direct input an...

Page 229: ...OUTPUT DATA RATES MODULE CHANNEL SUPPORTED DATA RATES 74 Channel 1 64 kbps Channel 2 64 kbps 7L Channel 1 64 kbps 128 kbps Channel 2 64 kbps 128 kbps 7M Channel 1 64 kbps 128 kbps Channel 2 64 kbps 128 kbps 7P Channel 1 64 kbps 128 kbps Channel 2 64 kbps 128 kbps 7T Channel 1 64 kbps 128 kbps 7W Channel 1 64 kbps 128 kbps Channel 2 64 kbps 128 kbps 7V Channel 1 64 kbps 128 kbps Channel 2 64 kbps 1...

Page 230: ...1 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O DATA RATE 128 kbps For UR series IED 2 DIRECT OUTPUT DEVICE ID 2 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O DATA RATE 128 kbps The message delivery time is about 0 2 of power cycle in both ways at 128 kbps that is from device 1 to device 2 and from device 2 to device 1 Different communications cards can be selected by the user for this back ...

Page 231: ...h rings are healthy IED 1 to IED 2 0 2 of power system cycle IED 1 to IED 3 0 4 of power system cycle IED 1 to IED 4 0 2 of power system cycle IED 2 to IED 3 0 2 of power system cycle IED 2 to IED 4 0 4 of power system cycle IED 3 to IED 4 0 2 of power system cycle If one ring is broken say TX2 RX2 the delivery times are as follows IED 1 to IED 2 0 2 of power system cycle IED 1 to IED 3 0 4 of pow...

Page 232: ... OUTPUT DEVICE ID 2 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O CH2 RING CONFIGURATION Yes For UR series IED 3 DIRECT OUTPUT DEVICE ID 3 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O CH2 RING CONFIGURATION Yes In this configuration the following delivery times are expected at 128 kbps IED 1 to IED 2 0 2 of power system cycle IED 1 to IED 3 0 5 of power system cycle IED 2 to IED 3 0 2 of po...

Page 233: ...CH1 2 PATH SETTINGS PRODUCT SETUP DIRECT I O CRC ALARM CH1 2 The C60 checks integrity of the incoming direct input and output messages using a 32 bit CRC The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check The monitoring function counts all incoming messages including messages that failed the CRC check A separate ...

Page 234: ...uming the best case of only 1 bit error in a failed packet having 1 failed packet for every 63 received is about equal to a BER of 10 4 c UNRETURNED MESSAGES ALARM CH1 2 PATH SETTINGS PRODUCT SETUP DIRECT I O UNRETURNED MESSAGES ALARM CH1 2 The C60 checks integrity of the direct input and output communication ring by counting unreturned messages In the ring configuration all messages originating a...

Page 235: ...F TERMINALS is 3 three terminal system set the NUMBER OF CHANNELS to 2 For a two terminal system the NUMBER OF CHANNELS can set to 1 or 2 redundant channels LOCAL RELAY ID NUMBER TERMINAL 1 RELAY ID NUMBER and TERMINAL 2 RELAY ID NUMBER In installa tions that use multiplexers or modems it is desirable to ensure that the data used by the relays protecting a given line is from the correct relays The...

Page 236: ...ay until RELAY SETTINGS is set to Programmed This setting is defaulted to Not Programmed when at the factory The UNIT NOT PROGRAMMED self test error message is displayed until the relay is put into the Programmed state The RELAY NAME setting allows the user to uniquely identify a relay This name will appear on generated reports INSTALLATION RELAY SETTINGS Not Programmed Range Not Programmed Progra...

Page 237: ... consists of the following steps Configure the field units This establishes the point to point connection between a specific port on the relay process bus module and a specific digital core on a specific Brick This is a necessary first step in configuring a process bus relay Configure the AC banks This sets the primary and secondary quantities and connections for currents and voltages AC bank conf...

Page 238: ...T primary rating must be entered To detect low level ground fault currents the sensitive ground input can be used In this case the sensitive ground CT primary rating must be entered Refer to chapter 3 for more details on CT connections Enter the rated CT primary current values For both 1000 5 and 1000 1 CTs the entry would be 1000 For correct opera tion the CT secondary rating must match the setti...

Page 239: ...DARY voltage setting is the voltage across the relay input terminals when nominal voltage is applied to the VT primary For example on a system with a 13 8 kV nominal primary voltage and with a 14400 120 volt VT in a delta connec tion the secondary voltage would be 115 that is 13800 14400 120 For a wye connection the voltage value entered must be the phase to neutral voltage which would be 115 66 4...

Page 240: ... current For three phase selection phase A is used for angle referencing while Clarke transformation of the phase signals is used for frequency metering and tracking for better performance dur ing fault open pole and VT and CT fail conditions The phase reference and frequency tracking AC signals are selected based upon the Source configuration regardless of whether or not a particular signal is ac...

Page 241: ... in the relevant settings menu The internal design of the ele ment specifies which type of parameter to use and provides a setting for source selection In elements where the parameter may be either fundamental or RMS magnitude such as phase time overcurrent two settings are provided One setting specifies the source the second setting selects between fundamental phasor and RMS AC input actual value...

Page 242: ...The following figure shows the arrangement of sources used to provide the functions required in this application and the CT VT inputs that are used to provide the data INCREASING SLOT POSITION LETTER CT VT MODULE 1 CT VT MODULE 2 CT VT MODULE 3 CTs VTs not applicable 827092A3 CDR SOURCE 1 CURRENT PHASOR PRODUCT SETUP DISPLAY PROPERTIES CURRENT CUT OFF LEVEL PRODUCT SETUP DISPLAY PROPERTIES CURRENT...

Page 243: ...USE OF SOURCES Y LV D HV AUX SRC 1 SRC 2 SRC 3 Phase CT M1 F1 F5 None Ground CT M1 None None Phase VT M5 None None Aux VT None None U1 827794A1 CDR F 5 F 1 DSP Bank U 1 M 1 M 1 M 5 51BF 1 51BF 2 Source 4 87T 51P UR Relay A V V A W W Var Var Amps Source 1 Source 3 Volts Amps Amps Volts Amps Source 2 ...

Page 244: ... Off Range FlexLogic operand MESSAGE BREAKER 1 ΦA 3P CLSD Off Range FlexLogic operand MESSAGE BREAKER 1 ΦA 3P OPND Off Range FlexLogic operand MESSAGE BREAKER 1 ΦB CLOSED Off Range FlexLogic operand MESSAGE BREAKER 1 ΦB OPENED Off Range FlexLogic operand MESSAGE BREAKER 1 ΦC CLOSED Off Range FlexLogic operand MESSAGE BREAKER 1 ΦC OPENED Off Range FlexLogic operand MESSAGE BREAKER 1 Toperate 0 070 ...

Page 245: ...d used to track the breaker open or closed position If the mode is selected as 1 Pole the input mentioned above is used to track phase A and the BREAKER 1 ΦB and BREAKER 1 ΦC settings select operands to track phases B and C respectively BREAKER 1 ΦA 3P OPND This setting selects an operand usually a contact input that should be a normally closed 52 b status input to create a logic 1 when the breake...

Page 246: ...TING Enabled BREAKER 1 PUSHBUTTON CONTROL USER 2 OFF ON To close BRK1 Name SETTING Off 0 BREAKER 1 CLOSE FLEXLOGIC OPERAND AR CLOSE BKR 1 SETTING Off 0 BREAKER 1 BLOCK CLOSE SETTING MANUAL CLOSE RECAL1 TIME 0 FLEXLOGIC OPERAND BREAKER 1 MNL CLS FLEXLOGIC OPERAND BREAKER 1 ON CMD FLEXLOGIC OPERANDS BREAKER 1 OFF CMD BREAKER 1 TRIP A BREAKER 1 TRIP B BREAKER 1 TRIP C To breaker control logic sheet 2...

Page 247: ...D BREAKER 1 OPEN BREAKER 1 DISCREP FLEXLOGIC OPERAND BREAKER 1 TROUBLE FLEXLOGIC OPERAND BREAKER 1 BAD STATUS FLEXLOGIC OPERANDS BREAKER 1 ΦA BAD ST BREAKER 1 ΦA CLSD BREAKER 1 ΦA OPEN BREAKER 1 INTERM ΦA FLEXLOGIC OPERANDS BREAKER 1 ANY P OPEN BREAKER 1 1P OPEN BREAKER 1 OOS SETTING 3 Pole 1 Pole BREAKER 1 MODE SETTING Off BREAKER 1 EXT ALARM SETTING Off BREAKER 1 OUT OF SV AND OR OR SETTING BREA...

Page 248: ...and disables the operation of the disconnect switch element SWITCH 1 NAME Assign a user defined name up to six characters to the disconnect switch This name will be used in flash messages related to disconnect switch 1 SWITCH 1 SWITCH 1 FUNCTION Disabled Range Disabled Enabled MESSAGE SWITCH 1 NAME SW 1 Range up to 6 alphanumeric characters MESSAGE SWITCH 1 MODE 3 Pole Range 3 Pole 1 Pole MESSAGE ...

Page 249: ...k phases B and C respectively SWTCH 1 ΦA 3P OPND This setting selects an operand usually a contact input that is for a normally closed 89 b status input that creates a logic 1 when the disconnect switch is open If a separate 89 b contact input is not available then an inverted 89 a status signal can be used SWITCH 1 ΦB CLOSED If the mode is selected as three pole this setting has no function If th...

Page 250: ...H 1 ΦB INTERM FLEXLOGIC OPERANDS SWITCH 1 Φ BAD ST C SWITCH 1 ΦC CLSD SWITCH 1 ΦC OPEN SWITCH 1 ΦC INTERM 859713A1 CDR SETTING SWITCH 1 ALARM DELAY 0 SETTING Off SWITCH 1 BLK CLOSE SETTING Off SWITCH 1 CLOSE SETTING Off SWITCH 1 BLK OPEN SETTING Off SWITCH 1 OPEN SETTING Disabled Enabled SWITCH 1 FUNCTION AND AND FLEXLOGIC OPERAND SWITCH 1 ON CMD FLEXLOGIC OPERAND SWITCH 1 OFF CMD OR OR AND AND SW...

Page 251: ...0 to 0 98 and 1 03 to 20 00 This data is converted into two continuous curves by linear interpolation between data points To enter a custom FlexCurve enter the reset and operate times using the VALUE keys for each selected pickup point using the MESSAGE UP DOWN keys for the desired protection curve A B C or D FLEXCURVE A FLEXCURVE A TIME AT 0 00 xPKP 0 ms Range 0 to 65535 ms in steps of 1 Table 5 ...

Page 252: ...h a minimum response time and a fixed time above a specified pickup multiples There are 41 recloser curve types supported These definite oper ating times are useful to coordinate operating times typically at higher currents and where upstream and downstream pro tective devices have different operating characteristics The recloser curve configuration window shown below appears when the Initialize F...

Page 253: ...ms see below Figure 5 31 COMPOSITE RECLOSER CURVE WITH HCT DISABLED With the HCT feature enabled the operating time reduces to 30 ms for pickup multiples exceeding 8 times pickup Figure 5 32 COMPOSITE RECLOSER CURVE WITH HCT ENABLED Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed If this is attempted the EnerVista UR Setup software gene...

Page 254: ...R CURVES GE113 GE120 GE138 AND GE142 GE104 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 CURRENT multiple of pickup TIME sec GE101 GE102 GE103 GE106 GE105 842723A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 05 0 1 0 2 0 5 1 2 5 10 20 50 CURRENT multiple of pickup TIME sec GE113 GE142 GE138 GE120 842725A1 CDR ...

Page 255: ...ND GE201 Figure 5 36 RECLOSER CURVES GE131 GE141 GE152 AND GE200 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 5 1 2 5 10 20 50 CURRENT multiple of pickup TIME sec GE134 GE151 GE140 GE137 GE201 842730A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 2 5 10 20 50 CURRENT multiple of pickup TIME sec GE131 GE200 GE152 GE141 842728A1 CDR ...

Page 256: ... GE116 GE117 GE118 GE132 GE136 AND GE139 842729A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 5 10 20 50 CURRENT multiple of pickup TIME sec GE133 GE163 GE162 GE161 GE165 GE164 842726A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 5 10 20 CURRENT multiple of pickup TIME sec GE116 GE132 GE118 GE117 GE139 GE136 ...

Page 257: ...Figure 5 40 RECLOSER CURVES GE119 GE135 AND GE202 842724A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 5 10 20 CURRENT multiple of pickup TIME sec GE121 GE114 GE112 GE122 GE107 GE115 GE111 842727A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 2 0 5 1 2 5 10 20 50 CURRENT multiple of pickup TIME sec GE119 GE202 GE135 ...

Page 258: ... a common time base they are referred to as a SYNCHROPHASOR A vastly improved method for tracking power system dynamic phenomena for improved power system monitoring protection operation and control can be realized if Synchrophasors from different locations within the power system are networked to a central location The C60 offers PMU features over two communication standards IEC 61850 9 5 and IEE...

Page 259: ...120 Hz for protection class synchrophasors The following two figures depict the general data flow for the generation of synchrophasor data for IEC 61850 90 5 In the first figure when IEC 61850 90 5 is selected all real and vir tual sources are available for the IEC 61850 90 5 PMUs The number of PMUs and aggregators vary by product as outlined in the table The figure shows an example of an N60 usin...

Page 260: ...regator inherits the Sample Rate SmpRate and IEEE C37 118 Class P or M of that PMU The value of the SmpRate DO in the Report Control Block is set based on the value of the Sample Rate in the PMU The Class of the Dataset are mapped into the MSVID of the Dataset see text below for the overall name of the MSVID If other PMUs are mapped into the same aggregator with different Sample Rates or from diff...

Page 261: ...of each PMU data set for version 7 2 and later using FCDA data non structured data EXAMPLE Protection Synchrophasors Data Set with Reporting Rate 60 Frames Second This example gives the protection synchrophasors data set with a reporting rate of 60 frames per second P60MMXU1 See the figure earlier Logical Nodes Supported in Each Logical Device This data or list of items as shown in the following f...

Page 262: ...IEC 61850 90 5 The C60 is expected to send the CFG 2 file IEEE C37 118 config file upon request from the upstream synchrophasor devices for example P30 without stopping R SV multicasting as shown in the figure below The primary domain control ler PDC does not need to use a stop start data stream command if the UR protocol is set to IEC 61850 90 5 prior to requesting the configuration via CFG 2 IEE...

Page 263: ...aggregator is set to 90 5 the version number of the CFG 2 file found in bits 0 3 of the frame SYNC word which should presently be set to 2 is set as follows The PMU settings are organized in logical groups as follows For correct PMU operation upgrade the firmware to the latest v7 2x release consult the v7 2x Release Notes for information ATH SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PHASOR MEA...

Page 264: ...1 STYLE Polar Range Polar Rectangular MESSAGE PMU 1 RATE 10 sec Range 1 sec 2 sec 4 sec 5 sec 10 sec 12 sec 15 sec 20 sec 25 sec 30 sec 50 sec 60 sec 100 sec 120 sec MESSAGE PMU 1 PHS 1 Off Range Available synchrophasor values MESSAGE PMU 1 PHS 14 Off Range Available synchrophasor values MESSAGE PMU 1 PHS 1 NAME GE UR PMU PHS 1 Range 16 character ASCII string MESSAGE PMU 1 PHS 14 NAME GE UR PMU PH...

Page 265: ...out or recorded When one source is selected by one PMU it cannot be selected by another PMU PMU 1 CLASS Range P M None This setting selects the synchrophasor class Note that a reporting rate of 100 or 120 can only be selected for class P synchrophasors and if the system frequency is 50 or 60 Hz respectively PMU 1 NETWORK REPORTING FORMAT This setting selects between reporting synchrophasors as 16 ...

Page 266: ...urrently with the synchrophasor instant These values are mapped into a two byte integer number with byte 1 LSB corresponding to the digital channel 1 and byte 2 MSB corresponding to digital channel 16 PMU1 D CH 1 NM to PMU1 D CH 16 NM These settings allow for custom naming of the digital channels Sixteen character ASCII strings are allowed as in the CHNAM field of the configuration frame PMU1 D CH...

Page 267: ...pectively as specified in the IEC 61850 standard IEC 61850 90 5 PMU 1 CONFIGURATION PATH SETTINGS SYSTEM SETUP PHASOR MEASUREMENT BASIC CONFIGURATION PMU1 PMU 1 BASIC CONFIGURA TION 90 5 PMU 1 CONFIGURATION PMU1 LDINST A user defined visible string maximum 64 char ASCII test to assign Logical Device LD Inst for a PMU LD As per IEC 61850 6 standard specification the PMU LD Name is the concatenated ...

Page 268: ...steps of 0 1 MESSAGE PMU 1 VB CALIBRATION ANGLE 0 00 Range 5 00 to 5 00 in steps of 0 05 MESSAGE PMU 1 VB CALIBRATION MAG 100 0 Range 95 0 to 105 0 in steps of 0 1 MESSAGE PMU 1 VC CALIBRATION ANGLE 0 00 Range 5 00 to 5 00 in steps of 0 05 MESSAGE PMU 1 VC CALIBRATION MAG 100 0 Range 95 0 to 105 0 in steps of 0 1 MESSAGE PMU 1 VX CALIBRATION ANGLE 0 00 Range 5 00 to 5 00 in steps of 0 05 MESSAGE P...

Page 269: ...ol purposes without applying this correction 4 When connected to line to line voltages the PMU calculates symmetrical voltages with the reference to the AG voltage and not to the physically connected AB voltage see the Metering Conventions section in Chapter 6 PMU 1 SEQ CURR SHIFT ANGLE This setting allows correcting positive and negative sequence currents for vector groups of power transformers l...

Page 270: ... be implemented using FlexLogic e USER TRIGGERING PATH SETTINGS SYSTEM SETUP PHASOR MEASUREMENT PMU 1 2 TRIGGERING PMU 1 2 USER TRIGGER The user trigger allows customized triggering logic to be constructed from FlexLogic The entire triggering logic is refreshed once every two power system cycles f FREQUENCY TRIGGERING PATH SETTINGS SYSTEM SETUP PHASOR MEASUREMENT PMU 1 2 TRIGGERING PMU 1 2 FREQUEN...

Page 271: ...long as the trig gering condition is asserted Figure 5 48 FREQUENCY TRIGGER SCHEME LOGIC g VOLTAGE TRIGGERING PATH SETTINGS SYSTEM SETUP PHASOR MEASUREMENT PMU 1 2 TRIGGERING PMU 1 2 VOLTAGE TRIGGER PMU 1 VOLTAGE TRIGGER PMU 1 VOLT TRIGGER FUNCTION Disabled Range Enabled Disabled MESSAGE PMU 1 VOLT TRIGGER LOW VOLT 0 800 pu Range 0 250 to 1 250 pu in steps of 0 001 MESSAGE PMU 1 VOLT TRIGGER HIGH ...

Page 272: ...ng the recorder in the forced mode recording as long as the trig gering condition is asserted Figure 5 49 VOLTAGE TRIGGER SCHEME LOGIC h CURRENT TRIGGERING PATH SETTINGS SYSTEM SETUP PHASOR MEASUREMENT PMU 1 2 TRIGGERING PMU 1 2 CURRENT TRIGGER This element responds to elevated current The trigger responds to the phase current signal of the phasor measurement unit PMU source All current channel A ...

Page 273: ...r 1 pu is a product of 1 pu voltage and 1 pu current or the product of nominal secondary voltage the VT ratio and the nominal primary current For the three phase power 1 pu is three times that for a single phase power The comparator applies a 3 hysteresis PMU 1 POWER TRIGGER PMU 1 POWER TRIGGER FUNCTION Disabled Range Enabled Disabled MESSAGE PMU 1 POWER TRIGGER ACTIVE 1 250 pu Range 0 250 to 3 00...

Page 274: ...GGER PMU 1 df dt TRIGGER FUNCTION Disabled Range Enabled Disabled MESSAGE PMU 1 df dt TRIGGER RAISE 0 25 Hz s Range 0 10 to 15 00 Hz s in steps of 0 01 MESSAGE PMU 1 df dt TRIGGER FALL 0 25 Hz s Range 0 10 to 15 00 Hz s in steps of 0 01 MESSAGE PMU 1 df dt TRIGGER PKP TIME 0 10 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PMU 1 df dt TRIGGER DPO TIME 1 00 s Range 0 00 to 600 00 s in steps of ...

Page 275: ...positive df dt The comparator applies a 4 hysteresis PMU 1 df dt TRIGGER FALL This setting specifies the pickup threshold for the rate of change of frequency in the fall ing direction negative df dt The comparator applies a 4 hysteresis PMU 1 df dt TRIGGER PKP TIME This setting can be used to filter out spurious conditions and avoid unnecessary triggering of the recorder PMU 1 df dt TRIGGER DPO TI...

Page 276: ...OCOF df dt SETTINGS PMU 1 df dt TRIGGER RAISE PMU 1 df dt TRIGGER FALL df dt RAISE OR df dt FALL RUN SETTINGS PMU 1 df dt TRIGGER DPO TIME 0 t DPO FLEXLOGIC OPERAND PMU 1 ROCOF TRIGGER FLEXLOGIC OPERANDS PMU 1 VOLT TRIGGER PMU 1 CURR TRIGGER PMU 1 POWER TRIGGER PMU 1 FREQ TRIGGER SETTING PMU 1 USER TRIGGER Off 0 FLEXLOGIC OPERAND PMU 1 TRIGGERED to STAT bits of the data frame 847012A1 CDR AND OR S...

Page 277: ...the amount of pre trigger data as a percent of the entire record This setting applies only to the timed mode of recording l AGGREGATOR PATH SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PMU AGGREGATOR 1 2 When the protocol selection is set via the software or keypad all aggregators whose protocol is not set to None are set to the last protocol saved that is IEEE C37 118 or IEC 61850 90 5 to any ag...

Page 278: ...tandard allows for user defined controls originating at the PDC to be executed on the PMU The control is accomplished via an extended command frame The relay decodes the first word of the extended field EXTFRAME to drive 16 dedicated FlexLogic operands Each aggregator supports 16 FlexLogic operands as shown in the table The operands are asserted for 5 seconds following reception of the command fra...

Page 279: ... data concentrator asserts control bit 1 as received via the network as above AGTR2 PDC CNTRL 2 Phasor data concentrator asserts control bit 2 as received via the network as above AGTR2 PDC CNTRL 3 Phasor data concentrator asserts control bit 3 as received via the network as above AGTR1 PDC CNTRL 16 Phasor data concentrator asserts control bit 16 as received via the network Table 5 16 NUMBER OF AS...

Page 280: ...ation revision every time the configuration is changed This setting allows the user to reset the configuration back to 1 or a value from 1 to 4294967295 MSVCB 1 PRIORITY A value from 0 through 7 The default value is 4 MSVCB 1 IP Class The value represents the IPv4 Differentiated Services formerly called TypeOfService value The default value is set for Expedited Forwarding 101110B 46 or 2EH This va...

Page 281: ...GE Multilin C60 Breaker Protection System 5 145 5 SETTINGS 5 4 SYSTEM SETUP 5 1 yes no 2 yes yes ENUMERATION AUTHENTICATION ENCRYPTION ...

Page 282: ...plies to the other features that set flags elements virtual inputs remote inputs schemes and human operators If more complex logic than presented above is required it is implemented via FlexLogic For example if it is desired to have the closed state of contact input H7a and the operated state of the phase undervoltage element block the operation of the phase time overcurrent element the two contro...

Page 283: ... Ip On Voltage is presently applied to the input external contact closed Off Cont Ip Off Voltage is presently not applied to the input external contact open Contact Output type Form A contact only Contact Closed Cont Op 1 Closed Contact output is closed Current On Cont Op 1 Ion Current is flowing through the contact Voltage On Cont Op 1 VOn Voltage exists across the contact Voltage Off Cont Op 1 V...

Page 284: ...ser specified level ring configurations only The rate of returned direct input output messages on channel 2 exceeded the user specified level ring configurations only ELEMENT Autoreclose 1P 3P AR ENABLED AR DISABLED AR RIP AR 1 P RIP AR 3 P 1 RIP AR 3 P 2 RIP AR 3 P 3 RIP AR 3 P 4 RIP AR LO AR BKR1 BLK AR BKR2 BLK AR CLOSE BKR1 AR CLOSE BKR2 AR FORCE 3 P TRIP AR SHOT CNT 0 AR SHOT CNT 1 AR SHOT CN...

Page 285: ...control 1 element Breaker restrike detected in phase B of the breaker control 1 element Breaker restrike detected in phase C of the breaker control 1 element BKR RESTRIKE 2 Same set of operands as shown for BKR RESTRIKE 1 ELEMENT Breaker control BREAKER 1 OFF CMD BREAKER 1 ON CMD BREAKER 1 ΦA BAD ST BREAKER 1 ΦA INTERM BREAKER 1 ΦA CLSD BREAKER 1 ΦA OPEN BREAKER 1 ΦB BAD ST BREAKER 1 ΦB INTERM BRE...

Page 286: ...eutral instantaneous overcurrent 1 has dropped out NEUTRAL IOC2 to 8 Same set of operands as shown for NEUTRAL IOC1 ELEMENT Neutral overvoltage NEUTRAL OV1 PKP NEUTRAL OV1 DPO NEUTRAL OV1 OP Neutral overvoltage element 1 has picked up Neutral overvoltage element 1 has dropped out Neutral overvoltage element 1 has operated NEUTRAL OV2 to 3 Same set of operands as shown for NEUTRAL OV1 ELEMENT Neutr...

Page 287: ...undervoltage 1 has picked up Phase A of phase undervoltage 1 has operated Phase B of phase undervoltage 1 has operated Phase C of phase undervoltage 1 has operated Phase A of phase undervoltage 1 has dropped out Phase B of phase undervoltage 1 has dropped out Phase C of phase undervoltage 1 has dropped out PHASE UV2 to 3 Same set of operands as shown for PHASE UV1 ELEMENT Synchrophasor phasor meas...

Page 288: ...one position to another Disconnect switch 1 phase B is closed Disconnect switch 1 phase B is open Disconnect switch 1 phase B bad status is detected discrepancy between the 89 a and 89 b contacts Disconnect switch 1 phase B intermediate status is detected transition from one position to another Disconnect switch 1 phase C is closed Disconnect switch 1 phase C is open Disconnect switch 1 phase C ba...

Page 289: ...serted while the remote double point status input is in the intermediate state Asserted while the remote double point status input is off Asserted while the remote double point status input is on REMDPS Ip 2 to 5 Same set of operands as per REMDPS 1 INPUTS OUTPUTS Remote inputs REMOTE INPUT 1 On REMOTE INPUT 2 On REMOTE INPUT 3 On REMOTE INPUT 32 On Flag is set logic 1 Flag is set logic 1 Flag is ...

Page 290: ...and SELF DIAGNOSTICS See Relay Self tests descriptions in Chapter 7 Commands and Targets ANY MAJOR ERROR ANY MINOR ERROR ANY SELF TESTS BATTERY FAIL CLOCK UNSYNCHRONIZED DIRECT DEVICE OFF DIRECT RING BREAK EQUIPMENT MISMATCH FLEXLOGIC ERR TOKEN IRIG B FAILURE LATCHING OUT ERROR MAINTENANCE ALERT FIRST ETHERNET FAIL PROCESS BUS FAILURE PTP FAILURE REMOTE DEVICE OFF RRTD COMM FAIL SECOND ETHERNET FA...

Page 291: ...t generates a pulse in response to an edge on the input The output from a one shot is True positive for only one pass through the FlexLogic equation There is a maximum of 64 one shots NEGATIVE ONE SHOT One shot that responds to a negative going edge DUAL ONE SHOT One shot that responds to both the positive and negative going edges Logic gate NOT Logical NOT Operates on the previous parameter OR 2 ...

Page 292: ... 96 can only be properly assigned once Figure 5 55 EXAMPLE LOGIC SCHEME 1 Inspect the example logic diagram to determine if the required logic can be implemented with the FlexLogic operators If this is not possible the logic must be altered until this condition is satisfied Once this is done count the inputs to each gate to verify that the number of inputs does not exceed the FlexLogic limits whic...

Page 293: ...er at a time until the required logic is complete It is generally easier to start at the out put end of the equation and work back towards the input as shown in the following steps It is also recommended to list operator inputs from bottom to top For demonstration the final output will be arbitrarily identified as parameter 99 and each preceding parameter decremented by one in turn Until accustome...

Page 294: ...me for this example the state is to be ON for a closed contact The operand is therefore Cont Ip H1c On 95 The last step in the procedure is to specify the upper input to the AND gate the operated state of digital element 2 This operand is DIG ELEM 2 OP Writing the parameters in numerical order can now form the equation for virtual output 3 95 DIG ELEM 2 OP 96 Cont Ip H1c On 97 NOT 98 AND 2 99 Virt...

Page 295: ... lower input to the XOR is operand DIG ELEM 1 PKP 88 The upper input to the XOR is operand Virt Ip 1 On 87 The input just below the upper input to OR 1 is operand Virt Op 2 On 86 The upper input to OR 1 is operand Virt Op 1 On 85 The last parameter is used to set the latch and is operand Virt Op 4 On The equation for virtual output 4 is 85 Virt Op 4 On 86 Virt Op 1 On 87 Virt Op 2 On 88 Virt Ip 1 ...

Page 296: ...r 1 as arranged in the order shown below DIG ELEM 2 OP Cont Ip H1c On NOT AND 2 Virt Op 3 Virt Op 4 On Virt Op 1 On Virt Op 2 On Virt Ip 1 On DIG ELEM 1 PKP XOR 2 Virt Op 3 On OR 4 LATCH S R Virt Op 3 On TIMER 1 Cont Ip H1c On OR 3 TIMER 2 Virt Op 4 END In the expression above the virtual output 4 input to the four input OR is listed before it is created This is typical of a form of feedback in th...

Page 297: ... never be set to 1 The key may be used when editing FlexLogic equations from the keypad to quickly scan through the major parameter types 5 5 6 FLEXLOGIC TIMERS PATH SETTINGS FLEXLOGIC FLEXLOGIC TIMERS FLEXLOGIC TIMER 1 32 There are 32 identical FlexLogic timers available These timers can be used as operators for FlexLogic equations TIMER 1 TYPE This setting is used to select the time measuring un...

Page 298: ...led Enabled MESSAGE FLEXELEMENT 1 NAME FxE1 Range up to 6 alphanumeric characters MESSAGE FLEXELEMENT 1 IN Off Range Off any analog actual value parameter MESSAGE FLEXELEMENT 1 IN Off Range Off any analog actual value parameter MESSAGE FLEXELEMENT 1 INPUT MODE Signed Range Signed Absolute MESSAGE FLEXELEMENT 1 COMP MODE Level Range Level Delta MESSAGE FLEXELEMENT 1 DIRECTION Over Range Over Under ...

Page 299: ...setting is set to Absolute Sample applications for the Absolute setting include monitoring the angular difference between two phasors with a symmetrical limit angle in both directions monitoring power regardless of its direction or monitoring a trend The element responds directly to its operating signal as defined by the FLEXELEMENT 1 IN FLEXELEMENT 1 IN and FLEX ELEMENT 1 INPUT MODE settings if t...

Page 300: ...ion with the FLEXELEMENT 1 INPUT MODE setting the element could be programmed to provide two extra charac teristics as shown in the figure below FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION Over PICKUP HYSTERESIS of PICKUP FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION Under PICKUP HYSTERESIS of PICKUP 842705A1 CDR ...

Page 301: ... FLEXELEMENT 1 PICKUP setting is entered in per unit values using the following definitions of the base units Table 5 21 FLEXELEMENT BASE UNITS BREAKER ACC ARCING AMPS Brk X Acc Arc Amp A B and C BASE 2000 kA2 cycle BREAKER ARCING AMPS Brk X Arc Amp A B and C BASE 1 kA2 cycle DCmA BASE maximum value of the DCMA INPUT MAX setting for the two transducers configured under the IN and IN inputs DELTA T...

Page 302: ...ining operator commands or permanently block relay functions such as Autorecloser until a deliberate interface action resets the latch The settings element operation is described below LATCH 1 TYPE This setting characterizes Latch 1 to be Set or Reset dominant LATCH 1 SET If asserted the specified FlexLogic operands sets Latch 1 LATCH 1 RESET If asserted the specified FlexLogic operand resets Latc...

Page 303: ...E LATCH 1 SET LATCH 1 RESET RUN SET RESET SETTING SETTING SETTING SETTING FLEXLOGIC OPERANDS Off 0 Off 0 Enabled 1 LATCH 1 ON LATCH 1 OFF LATCH N TYPE LATCH N SET LATCH N RESET LATCH N ON LATCH N OFF Reset Dominant ON OFF ON OFF OFF OFF Previous State Previous State ON ON OFF ON OFF ON OFF ON Set Dominant ON OFF ON OFF ON ON ON OFF OFF OFF Previous State Previous State OFF ON OFF ON ...

Page 304: ...trol Elements section later in this chapter See also the Introduction to Elements section at the beginning of this chap ter 5 6 2 SETTING GROUP PATH SETTINGS GROUPED ELEMENTS SETTING GROUP 1 6 Each of the six setting group menus is identical Setting group 1 the default active group automatically becomes active if no other group is active see the Control elements section for additional details If t...

Page 305: ...E PHASE TOC4 MESSAGE PHASE TOC5 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE PHASE TOC6 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE PHASE IOC1 See page 5 177 MESSAGE PHASE IOC2 MESSAGE PHASE IOC3 MESSAGE PHASE IOC4 MESSAGE PHASE IOC5 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE PHASE IOC6 Note Se...

Page 306: ...tatic relays which set the energy capacity directly to zero when the current falls below the reset threshold The Timed selection can be used where the relay must coordinate with electromechanical relays IEEE CURVES The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37 112 1996 curve classifications for extremely very and moderately inverse The IEEE curves are derive...

Page 307: ... 387 10 465 8 410 7 196 6 418 5 889 5 513 10 0 161 790 70 277 29 423 17 983 13 081 10 513 8 995 8 023 7 361 6 891 IEEE MODERATELY INVERSE 0 5 3 220 1 902 1 216 0 973 0 844 0 763 0 706 0 663 0 630 0 603 1 0 6 439 3 803 2 432 1 946 1 688 1 526 1 412 1 327 1 260 1 207 2 0 12 878 7 606 4 864 3 892 3 377 3 051 2 823 2 653 2 521 2 414 4 0 25 756 15 213 9 729 7 783 6 753 6 102 5 647 5 307 5 041 4 827 6 0...

Page 308: ... 280 3 837 3 528 3 297 3 116 2 971 IEC CURVE B 0 05 1 350 0 675 0 338 0 225 0 169 0 135 0 113 0 096 0 084 0 075 0 10 2 700 1 350 0 675 0 450 0 338 0 270 0 225 0 193 0 169 0 150 0 20 5 400 2 700 1 350 0 900 0 675 0 540 0 450 0 386 0 338 0 300 0 40 10 800 5 400 2 700 1 800 1 350 1 080 0 900 0 771 0 675 0 600 0 60 16 200 8 100 4 050 2 700 2 025 1 620 1 350 1 157 1 013 0 900 0 80 21 600 10 800 5 400 3...

Page 309: ...88 1 239 1 060 0 926 IAC VERY INVERSE 0 5 1 451 0 656 0 269 0 172 0 133 0 113 0 101 0 093 0 087 0 083 1 0 2 901 1 312 0 537 0 343 0 266 0 227 0 202 0 186 0 174 0 165 2 0 5 802 2 624 1 075 0 687 0 533 0 453 0 405 0 372 0 349 0 331 4 0 11 605 5 248 2 150 1 374 1 065 0 906 0 810 0 745 0 698 0 662 6 0 17 407 7 872 3 225 2 061 1 598 1 359 1 215 1 117 1 046 0 992 8 0 23 209 10 497 4 299 2 747 2 131 1 81...

Page 310: ...table from instanta neous to 600 00 seconds in steps of 10 ms EQ 5 14 EQ 5 15 where T Operate Time sec TDM Multiplier setting I Input Current Ipickup Pickup Current setting TRESET Reset Time in seconds assuming energy capacity is 100 and RESET Timed RECLOSER CURVES The C60 uses the FlexCurve feature to facilitate programming of 41 recloser curves See the FlexCurve section in this chapter for detai...

Page 311: ...y a voltage restraint feature when enabled This is accom plished via the multipliers Mvr corresponding to the phase phase voltages of the voltage restraint characteristic curve see the figure below the pickup level is calculated as Mvr times the PHASE TOC1 PICKUP setting If the voltage restraint feature is disabled the pickup level always remains at the setting value PHASE TOC1 PHASE TOC1 FUNCTION...

Page 312: ...LOCK C PHASE TOC1 BLOCK B PHASE TOC1 VOLT RESTRAINT PHASE TOC1 A PKP PHASE TOC1 A DPO PHASE TOC1 A OP PHASE TOC1 B PKP PHASE TOC1 B DPO PHASE TOC1 B OP PHASE TOC1 C PKP PHASE TOC1 C DPO PHASE TOC1 C OP PHASE TOC1 PKP PHASE TOC1 OP PHASE TOC1 SOURCE PHASE TOC1 RESET PHASE TOC1 CURVE PHASE TOC1 PICKUP PHASE TOC1 INPUT IA Seq ABC Seq ACB Set Multiplier Set Multiplier Set Multiplier Set Pickup Multipl...

Page 313: ...s of 0 001 MESSAGE PHASE IOC1 PICKUP DELAY 0 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PHASE IOC1 RESET DELAY 0 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PHASE IOC1 BLOCK A Off Range FlexLogic operand MESSAGE PHASE IOC1 BLOCK B Off Range FlexLogic operand MESSAGE PHASE IOC1 BLOCK C Off Range FlexLogic operand MESSAGE PHASE IOC1 TARGET Self reset Range Self reset Latched Disab...

Page 314: ...SAGE NEUTRAL TOC4 MESSAGE NEUTRAL TOC5 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE NEUTRAL TOC6 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE NEUTRAL IOC1 See page 5 180 MESSAGE NEUTRAL IOC2 MESSAGE NEUTRAL IOC3 MESSAGE NEUTRAL IOC4 MESSAGE NEUTRAL IOC5 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE...

Page 315: ...and the element is blocked the time accumulator will be cleared immediately Figure 5 69 NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC NEUTRAL TOC1 NEUTRAL TOC1 FUNCTION Disabled Range Disabled Enabled MESSAGE NEUTRAL TOC1 SIGNAL SOURCE SRC 1 Range SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE NEUTRAL TOC1 INPUT Phasor Range Phasor RMS MESSAGE NEUTRAL TOC1 PICKUP 1 000 pu Range 0 000 to 30 000 pu in steps of 0 001 MES...

Page 316: ...resulting from System unbalances under heavy load conditions Transformation errors of current transformers CTs during double line and three phase faults Switch off transients during double line and three phase faults The positive sequence restraint must be considered when testing for pickup accuracy and response time multiple of pickup The operating quantity depends on how test currents are inject...

Page 317: ...MESSAGE GROUND IOC2 MESSAGE GROUND IOC3 MESSAGE GROUND IOC4 MESSAGE GROUND IOC5 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE GROUND IOC6 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE GROUND IOC7 Note Seen only if slot F and slot M have an 8H or 8J CT module installed MESSAGE GROUND IOC8 Note Seen only if slot F and slot M have 8H o...

Page 318: ...eset characteristic is set to Instantaneous and the ele ment is blocked the time accumulator will be cleared immediately These elements measure the current that is connected to the ground channel of a CT VT module The conversion range of a standard channel is from 0 02 to 46 times the CT rating This channel may be also equipped with a sensitive input The conversion range of a sensitive channel is ...

Page 319: ...rsion range of a sensitive channel is from 0 002 to 4 6 times the CT rating GROUND IOC1 GROUND IOC1 FUNCTION Disabled Range Disabled Enabled MESSAGE GROUND IOC1 SIGNAL SOURCE SRC 1 Range SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE GROUND IOC1 PICKUP 1 000 pu Range 0 000 to 30 000 pu in steps of 0 001 MESSAGE GROUND IOC1 PICKUP DELAY 0 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE GROUND IOC1 RESET DELA...

Page 320: ... FlexLogic operand MESSAGE BF1 PH AMP SUPV PICKUP 1 050 pu Range 0 001 to 30 000 pu in steps of 0 001 MESSAGE BF1 N AMP SUPV PICKUP 1 050 pu Range 0 001 to 30 000 pu in steps of 0 001 MESSAGE BF1 USE TIMER 1 Yes Range Yes No MESSAGE BF1 TIMER 1 PICKUP DELAY 0 000 s Range 0 000 to 65 535 s in steps of 0 001 MESSAGE BF1 USE TIMER 2 Yes Range Yes No MESSAGE BF1 TIMER 2 PICKUP DELAY 0 000 s Range 0 00...

Page 321: ... Off Range FlexLogic operand MESSAGE BF1 BREAKER TEST ON Off Range FlexLogic operand MESSAGE BF1 PH AMP HISET PICKUP 1 050 pu Range 0 001 to 30 000 pu in steps of 0 001 MESSAGE BF1 N AMP HISET PICKUP 1 050 pu Range 0 001 to 30 000 pu in steps of 0 001 MESSAGE BF1 PH AMP LOSET PICKUP 1 050 pu Range 0 001 to 30 000 pu in steps of 0 001 MESSAGE BF1 N AMP LOSET PICKUP 1 050 pu Range 0 001 to 30 000 pu...

Page 322: ...quired to clear the zone The delayed paths are associated with breaker failure timers 1 2 and 3 which are intended to have delays increasing with increasing timer num bers These delayed paths are individually enabled to allow for maximum flexibility Timer 1 logic early path is supervised by a fast operating breaker auxiliary contact If the breaker is still closed as indi cated by the auxiliary con...

Page 323: ...set and low set current supervision will guarantee correct operation BF1 N AMP SUPV PICKUP This setting is used to set the neutral current initiate and seal in supervision level Gener ally this setting should detect the lowest expected fault current on the protected breaker Neutral current supervision is used only in the three phase scheme to provide increased sensitivity This setting is valid onl...

Page 324: ... BF1 N AMP HISET PICKUP This setting sets the neutral current output supervision level Generally this setting should detect the lowest expected fault current on the protected breaker before a breaker opening resistor is inserted Neutral current supervision is used only in the three pole scheme to provide increased sensitivity This setting is valid only for three pole breaker failure schemes BF1 PH...

Page 325: ...AILURE INITIATE AND OR OR OR AND OR OR OR OR OR OR AND AND AND AND AND AND Seal in path Seal in path Seal in path to breaker failure single pole logic sheet 3 Function SETTINGS Enabled 1 Block Off 0 Phase A Initiate SETTING Off 0 Phase B Initiate SETTING Off 0 Three Pole Initiate SETTING Off 0 Use Seal In SETTING Yes 1 Use Amp Supervision SETTING Yes 1 Phase C Initiate SETTING Off 0 SETTING RUN IC...

Page 326: ... failure logic sheet 1 0 Timer 2 Pickup Delay SETTING AND Use Timer 3 SETTINGS Yes 1 Breaker Pos 2 Phase A 3P Off 0 Breaker Pos 2 Phase B Off 0 Breaker Pos 2 Phase C Off 0 Breaker Test On Off 0 AND Initiated from single pole breaker failure logic sheet 1 0 Timer 3 Pickup Delay SETTING AND AND OR AND OR OR SETTING Phase Current HiSet Pickup RUN IA 0 LoSet Time Delay SETTING SETTING Phase Current Hi...

Page 327: ...SHEET 2 OF 2 Initiated TO SHEET 2 OF 2 827068 cdr BF1 FUNCTION Disable 0 Enable 1 SETTING BF1 BLOCK Off 0 SETTING BF1 INITIATE Off 0 SETTING BF1 USE SEAL IN YES 1 NO 0 SETTING BF1 USE AMP SUPV YES 1 NO 0 SETTING IA IB IN IC BF1 SOURCE SETTING IA PICKUP RUN BF1 PH AMP SUPV SETTINGS PICKUP BF1 N AMP SUPV PICKUP RUN RUN RUN IB PICKUP IC PICKUP IN PICKUP BKR FAIL 1 RETRIP FLEXLOGIC OPERAND ...

Page 328: ...KUP SETTING AND SETTING BF1 TIMER1 PICKUP DELAY 0 SETTING AND SETTING NO 0 YES 1 BF1 USE TIMER 1 SETTING BKR FAIL 1 T2 OP FLEXLOGIC OPERAND FLEXLOGIC OPERAND NO 0 YES 1 BF1 USE TIMER 3 SETTING BF1 BKR POS2 A 3P Φ Off 0 SETTING BF1 BREAKER TEST ON Off 0 SETTING BF1 TIMER3 PICKUP DELAY 0 SETTING SETTINGS IB PICKUP IC PICKUP IN PICKUP BF1 LOSET TIME DELAY 0 SETTING RUN RUN IA PICKUP RUN BF1 N AMP LOS...

Page 329: ...gh the block feature of those elements Source Transfer Schemes In the event of an undervoltage a transfer signal may be generated to transfer a load from its normal source to a standby or emergency power source The undervoltage elements can be programmed to have a definite time delay characteristic The definite time curve oper ates when the voltage drops below the pickup level for a specified peri...

Page 330: ...own below EQ 5 18 where T operating time D undervoltage delay setting D 0 00 operates instantaneously V secondary voltage applied to the relay Vpickup pickup level Figure 5 79 INVERSE TIME UNDERVOLTAGE CURVES At 0 of pickup the operating time equals the UNDERVOLTAGE DELAY setting T D 1 V Vpickup 842788A1 CDR of voltage pickup Time seconds NOTE ...

Page 331: ...nd Phase to Phase MESSAGE PHASE UV1 PICKUP 1 000 pu Range 0 000 to 3 000 pu in steps of 0 001 MESSAGE PHASE UV1 CURVE Definite Time Range Definite Time Inverse Time MESSAGE PHASE UV1 DELAY 1 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PHASE UV1 MINIMUM VOLTAGE 0 100 pu Range 0 000 to 3 000 pu in steps of 0 001 MESSAGE PHASE UV1 BLOCK Off Range FlexLogic operand MESSAGE PHASE UV1 TARGET Se...

Page 332: ...AL SOURCE SRC 1 Range SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE PHASE OV1 PICKUP 1 000 pu Range 0 000 to 3 000 pu in steps of 0 001 MESSAGE PHASE OV1 PICKUP DELAY 1 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PHASE OV1 RESET DELAY 1 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PHASE OV1 BLOCK Off Range FlexLogic Operand MESSAGE PHASE OV1 TARGET Self reset Range Self reset Latched Disabled M...

Page 333: ...his element must be configured for a phase VT VT errors and normal voltage unbalance must be considered when setting this element This function requires the VTs to be wye connected Figure 5 82 NEUTRAL OVERVOLTAGE1 SCHEME LOGIC NEUTRAL OV1 NEUTRAL OV1 FUNCTION Disabled Range Disabled Enabled MESSAGE NEUTRAL OV1 SIGNAL SOURCE SRC 1 Range SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE NEUTRAL OV1 PICKUP 0 300 pu Ra...

Page 334: ...ristics The operating characteristics and equations for both definite and inverse time delay are as for the phase undervoltage element The element resets instantaneously The minimum voltage setting selects the operating voltage below which the element is blocked Figure 5 83 AUXILIARY UNDERVOLTAGE SCHEME LOGIC AUXILIARY UV1 AUX UV1 FUNCTION Disabled Range Disabled Enabled MESSAGE AUX UV1 SIGNAL SOU...

Page 335: ...er delta VT connection Figure 5 84 AUXILIARY OVERVOLTAGE SCHEME LOGIC AUXILIARY OV1 AUX OV1 FUNCTION Disabled Range Disabled Enabled MESSAGE AUX OV1 SIGNAL SOURCE SRC 1 Range SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE AUX OV1 PICKUP 0 300 pu Range 0 000 to 3 000 pu in steps of 0 001 MESSAGE AUX OV1 PICKUP DELAY 1 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE AUX OV1 RESET DELAY 1 00 s Range 0 00 to 60...

Page 336: ...nable disable operation of the element OPEN POLE BLOCK This setting is used to select a FlexLogic operand that blocks operation of the element OPEN POLE CURRENT SOURCE This setting is used to select the source for the current for the element OPEN POLE CURRENT PICKUP This setting is used to select the pickup value of the phase current The pickup set ting is the minimum of the range and likely to be...

Page 337: ...elay of the element OPEN POLE RESET DELAY This setting is used to select the reset delay of the element The use of this setting depends on the particular application and whether single pole or three pole tripping is used It should comprise the reset time of the operating elements it used in conjunction with the breaker opening time and breaker auxiliary contacts discrepancy with the main contacts ...

Page 338: ...eactive powers as measured per the UR series metering convention θ is a sum of the element characteristic DIR POWER 1 RCA and calibration DIR POWER 1 CALIBRATION angles and SMIN is the minimum operating power The operating quantity is displayed in the ACTUAL VALUES METERING SENSITIVE DIRECTIONAL POWER 1 2 actual value The element has two independent as to the pickup and delay settings stages for a...

Page 339: ...ed in the figure below For example section a in the figure below shows settings for reverse power while section b shows settings for low forward power applications Figure 5 87 DIRECTIONAL POWER ELEMENT SAMPLE APPLICATIONS RESTRAIN SMIN RCA CALIBRATION OPERATE D i r e c t i o n Q P 842702A1 CDR P Q OPERATE RESTRAIN RCA 0o SMIN 0 d P Q OPERATE RESTRAIN RCA 180o SMIN 0 a P Q OPERATE RESTRAIN RCA 0o S...

Page 340: ...imply a shift towards the operate region along the RCA line the negative values imply a shift towards the restrain region along the RCA line Refer to the Directional power sample applications figure for details Together with the RCA this setting enables a wide range of operating characteristics This setting applies to three phase power and is entered in per unit pu values The base quantity is 3 x ...

Page 341: ...ecific protection or control protection element and checking the desired bus box Once the desired element is selected for a specific bus a list of element operate type operands are displayed and can be assigned to a trip bus If more than one operate type operand is required it may be assigned directly from the trip bus menu TRIP BUS 1 TRIP BUS 1 FUNCTION Disabled Range Enabled Disabled MESSAGE TRI...

Page 342: ...ay should be set long enough to allow the breaker or contactor to perform a required action TRIP BUS 1 INPUT 1 to TRIP BUS 1 INPUT 16 These settings select a FlexLogic operand to be assigned as an input to the trip bus TRIP BUS 1 LATCHING This setting enables or disables latching of the trip bus output This is typically used when lockout is required or user acknowledgement of the relay response is...

Page 343: ...operand MESSAGE GROUP 1 NAME Range up to 16 alphanumeric characters MESSAGE GROUP 2 NAME Range up to 16 alphanumeric characters MESSAGE GROUP 6 NAME Range up to 16 alphanumeric characters MESSAGE SETTING GROUP EVENTS Disabled Range Disabled Enabled SETTINGS Off TRIP BUS 1 INPUT 2 Off TRIP BUS 1 INPUT 1 Off TRIP BUS 1 INPUT 16 OR SETTINGS Enabled TRIP BUS 1 FUNCTION Off TRIP BUS 1 BLOCK AND AND Lat...

Page 344: ...g when the FlexLogic parameter is set to On This can be useful in applications where it is undesirable to change the settings under certain conditions such as the breaker being open The GROUP 2 ACTIVATE ON to GROUP 6 ACTIVATE ON settings select a FlexLogic operand which when set makes the partic ular setting group active for use by any grouped element A priority scheme ensures that only one group ...

Page 345: ...e Time out Acknowledge MESSAGE SELECTOR 1 ACK Off Range FlexLogic operand MESSAGE SELECTOR 1 3BIT A0 Off Range FlexLogic operand MESSAGE SELECTOR 1 3BIT A1 Off Range FlexLogic operand MESSAGE SELECTOR 1 3BIT A2 Off Range FlexLogic operand MESSAGE SELECTOR 1 3BIT MODE Time out Range Time out Acknowledge MESSAGE SELECTOR 1 3BIT ACK Off Range FlexLogic operand MESSAGE SELECTOR 1 POWER UP MODE Restore...

Page 346: ...rwise the change will not take place and an alarm will be set SELECTOR 1 STEP UP This setting specifies a control input for the selector switch The switch is shifted to a new position at each rising edge of this signal The position changes incrementally wrapping up from the last SELECTOR 1 FULL RANGE to the first position 1 Consecutive pulses of this control operand must not occur faster than ever...

Page 347: ... SELECTOR TIME OUT setting after the last activity of the three bit control inputs Note that the stepping up control input and three bit control input have independent acknowledging signals SELECTOR 1 ACK and SELECTOR 1 3BIT ACK accordingly SELECTOR 1 POWER UP MODE This setting specifies the element behavior on power up of the relay When set to Restore the last position of the selector stored in t...

Page 348: ...ese diagrams T represents a time out setting Figure 5 92 TIME OUT MODE 842737A1 CDR STEP UP 3BIT A0 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 pre existing position 2 changed to 4 with a pushbutton changed to 1 with a 3 bit input changed to 2 with a pushbutton T T T T changed to 7 with a 3 bit input STP ALARM BIT ALARM ALARM ...

Page 349: ...t should synchronize the setting group to the three bit control input Make the following changes to setting group control in the SETTINGS CONTROL ELEMENTS SETTING GROUPS menu SETTING GROUPS FUNCTION Enabled GROUP 4 ACTIVATE ON SELECTOR 1 POS 4 SETTING GROUPS BLK Off GROUP 5 ACTIVATE ON Off GROUP 2 ACTIVATE ON SELECTOR 1 POS 2 GROUP 6 ACTIVATE ON Off GROUP 3 ACTIVATE ON SELECTOR 1 POS 3 Make the fo...

Page 350: ...owing changes in the SETTINGS PRODUCT SETUP USER PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu PUSHBUTTON 1 FUNCTION Self reset PUSHBUTTON 1 DROP OUT TIME 0 10 s The logic for the selector switch is shown below Figure 5 94 SELECTOR SWITCH LOGIC 842012A2 CDR step up acknowledge 3 bit position out ON FLEXLOGIC OPERANDS SELECTOR 1 POS 1 SELECTOR 1 POS 2 SELECTOR 1 POS 3 SELECTOR 1 POS 4 SELECTOR 1 ...

Page 351: ...gle equal to 2 ΔΦ at a frequency equal to the frequency difference ΔF This time can be calculated by EQ 5 20 SYNCHROCHECK 1 SYNCHK1 FUNCTION Disabled Range Disabled Enabled MESSAGE SYNCHK1 BLOCK Off Range FlexLogic operand MESSAGE SYNCHK1 V1 SOURCE SRC 1 Range SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE SYNCHK1 V2 SOURCE SRC 2 Range SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE SYNCHK1 MAX VOLT DIFF 10000 V Range 0 to 4000...

Page 352: ...D SOURCE SELECT This setting selects the combination of dead and live sources that will by pass synchronism check function and permit the breaker to be closed when one or both of the two voltages V1 or and V2 are below the maximum voltage threshold A dead or live source is declared by monitoring the voltage level Six options are available None Dead Source function is disabled LV1 and DV2 Live V1 a...

Page 353: ...with both phase voltages and an auxiliary voltage ensure that only the auxiliary voltage is programmed in one of the sources to be used for synchrocheck Exception Synchronism cannot be checked between Delta connected phase VTs and a Wye connected auxil iary voltage 2 The relay measures frequency and Volts Hz from an input on a given source with priorities as established by the con figuration of in...

Page 354: ...SETTINGS ΔF Maximum Max Freq Diff Freq Hysteresis SETTING ΔΦ Maximum Max Angle Diff SETTING ΔV Maximum Max Volt Diff AND OR XOR AND AND AND AND AND 827076AD CDR ACTUAL VALUES Synchrocheck 1 ΔV Synchrocheck 1 ΔΦ Synchrocheck 1 ΔF AND SETTINGS Enabled 1 Function Off 0 Block AND AND AND AND FLEXLOGIC OPERAND SYNC1 V2 ABOVE MIN SYNC1 V1 ABOVE MIN SYNC1 V1 BELOW MAX SYNC1 V2 BELOW MAX FLEXLOGIC OPERAND...

Page 355: ...phase voltage VT input is programmed as Delta with a ratio of 14400 V 120 V 120 and with a sec ondary voltage setting of 13800 V 120 115 volts The auxiliary VT connection is selected to be VAB since this vector is in phase with VA on the transformer 13 8 kV side The auxiliary secondary voltage setting is 230000 V 3 2000 66 4 volts and the auxiliary VT ratio is calculated as 2000 3 13 8 kV 230 kV 2...

Page 356: ...B Range Protection AND CB Protection Only MESSAGE AR BLOCK BKR1 Off Range FlexLogic operand MESSAGE AR CLOSE TIME BKR 1 0 10 s Range 0 00 to 655 35 s in steps of 0 01 MESSAGE AR BKR MAN CLOSE Off Range FlexLogic operand MESSAGE AR BLK TIME UPON MAN CLS 10 00 s Range 0 00 to 655 35 s in steps of 0 01 MESSAGE AR 1P INIT Off Range FlexLogic operand MESSAGE AR 3P INIT Off Range FlexLogic operand MESSA...

Page 357: ... of 0 01 MESSAGE AR RESET Off Range FlexLogic operand MESSAGE AR RESET TIME 60 00 s Range 0 to 655 35 s in steps of 0 01 MESSAGE AR BKR CLOSED Off Range FlexLogic operand MESSAGE AR BLOCK Off Range FlexLogic operand MESSAGE AR PAUSE Off Range FlexLogic operand MESSAGE AR INCOMPLETE SEQ TIME 5 00 s Range 0 to 655 35 s in steps of 0 01 MESSAGE AR BLOCK BKR2 Off Range FlexLogic operand MESSAGE AR CLO...

Page 358: ...rd and fourth shots are always three pole and start the AR 3 P DEAD TIME 2 4 timers 2 1 Pole In this mode the autorecloser starts the AR 1 P DEAD TIME for the first shot if the fault is single phase If the fault is three phase or a three pole trip on the breaker occurred during the single pole initiation the scheme goes to lockout without reclosing If two or more shots are enabled the second third...

Page 359: ...nother phase during the single pole dead time of the auto recloser the scheme will force a 3 pole trip and reclose RECLOSING SCHEME OPERATION FOR ONE BREAKER Permanent Fault Consider Mode 1 which calls for 1 Pole or 3 Pole Time Delay 1 for the first reclosure and 3 Pole Time Delay 2 for the second reclosure and assume a permanent fault on the line Also assume the scheme is in the Reset state For t...

Page 360: ... initiate signal the scheme moves into the reclose in progress state and starts the incomplete sequence timer The setting of this timer determines the maximum time interval allowed for a single reclose shot If a close breaker 1 or 2 signal is not present before this time expires the scheme goes to Lockout There are four other conditions that can take the scheme to the Lockout state as shown below ...

Page 361: ...ows MODE 1 to MODE 4 ACTIVATION This setting selects an operand for activating the corresponding AR mode in run time Mode change via activation input takes place when only one of the four activation inputs is high and the AR RIP operand is low that is reclose is not in progress and also the mode to be activated is different from the existing mode otherwise the activation input is ignored and the e...

Page 362: ...and the autoreclose scheme can start timing the three pole dead time The scheme has a pre wired input that indicates breaker status AR 3 P DEAD TIME 1 This is the dead time following the first three pole trip This intentional delay can be used for a high speed three pole autoreclose However it should be set longer than the estimated de ionizing time following the three pole trip AR 3 P DEAD TIME 2...

Page 363: ...1 This setting establishes how the scheme performs when the breaker closing sequence is 2 1 and breaker 2 is blocked When set to Yes the closing command will be transferred direct to breaker 1 without waiting the transfer time When set to No the closing command will be blocked by the AR BKR2 BLK signal and the scheme will be sent to lockout by the incomplete sequence timer AR BKR1 FAIL OPTION This...

Page 364: ...c sheet 3 OR AND AND OR SETTING Off 0 Bkr 3 Pole Open OR BKR 3 POLE OPEN from autoreclose logic sheet 3 AND OR SETTING Protection and CB AR Initiate Mode AND AND RESET from autoreclose logic sheet 2 CLOSE BKR1 OR BKR2 OR OR FLEXLOGIC OPERAND AR SHOT COUNT 0 OR SETTING Off 0 Pause SHOT COUNT MAX from autoreclose logic sheet 2 SETTING Mode 2 1 Pole AR Mode Mode 3 3 Pole A Mode 4 3 Pole B OR FLEXLOGI...

Page 365: ...ause AR Mode equals to 1 2 3 and 4 respec tively so that it can be monitored and logged FLEXLOGIC OPERAND AR RIP AND Off 0 Mode 1 Off 0 Mode 2 Off 0 Mode 3 Off 0 Mode 4 Only 1 out of 4 is high AR Mode Activation SETTING SETTING AR M0DE Mode 1 1 3 Pole Mode 2 1 Pole Mode 3 3 Pole A Mode 4 3 Pole B Mode to be activated a 1 4 Current AR Mode b 1 4 Switch to new mode Note only one mode can be activate...

Page 366: ...EAKER 1 CLOSED SETTING Max Number of Shots 4 3 2 1 0 maximum Increment shout count Decrement shout count Reset count OR AND FLEXLOGIC OPERANDS AR SHOT CNT 4 AR SHOT CNT 3 AR SHOT CNT 2 AR SHOT CNT 1 OR FLEXLOGIC OPERAND AR SHOT CNT 0 SHOT COUNT MAX CLOSE BKR 1 OR 2 BKR FAIL TO RECLS to Lockout RESET to autoreclose logic sheet 1 ACTUAL VALUES AR SHOT COUNT 4 AR SHOT COUNT 3 AR SHOT COUNT 2 AR SHOT ...

Page 367: ...EAKER 2 ONE P OPEN BREAKER 2 CLOSED BREAKER 1 MNL CLS BREAKER 1 OOS BREAKER 2 OOS FLEXLOGIC OPERAND FLEXLOGIC OPERAND FLEXLOGIC OPERAND BREAKER 2 MNL CLS FLEXLOGIC OPERAND FLEXLOGIC OPERAND FLEXLOGIC OPERAND OR AND AND AND AND AND AND AND AND AND AND AND AND AND AND AND OR OR OR OR OR OR OR OR OR OR OR OR OR OR BKR MANUAL CLOSE To sheet 1 BKR CLOSED To sheet 1 and 2 BKR 3 POLE OPEN To sheet 1 BKR ...

Page 368: ...T PROT T TRIP BKR T PROT RESET T R I P AR RIP AR 1 P RIP AR FORCE 3P TRIP CLOSE AR CLOSE BKR1 T CLOSE BKR1 T TRIP BKR T PROT RESET 3 P 2 DEAD TIME TRANSFER TIME T CLOSE BKR2 842703A4 CDR T PROT T CLOSE BKR1 RESET TIME AR RESET TIME AR SHOT COUNT 0 BREAKER 1 CLOSED AR 3P INIT AR 3P 2 RIP BREAKER 2 CLOSED AR CLOSE BKR2 AR TRANSFER TIME AR INCOMPLETE SEQ TIME 1 P DEAD TIME 1 25 cycle ...

Page 369: ...or pickup and reset delays for the output operand DIGITAL ELEMENT 1 INPUT Selects a FlexLogic operand to be monitored by the digital element DIGITAL ELEMENT 1 PICKUP DELAY Sets the required time delay from element pickup to element operation If a pickup delay is not required set to 0 To avoid nuisance alarms set the delay greater than the operating time of the breaker DIGITAL ELEMENT 1 RESET DELAY...

Page 370: ...a low level of current well below the operating current of the breaker trip coil If the circuit presents a high resis tance the trickle current will fall below the monitor threshold and an alarm would be declared In most breaker control circuits the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open see diagram below To prevent unwanted alarms ...

Page 371: ... circuit In this case it is not required to supervise the monitoring circuit with the breaker position the BLOCK setting is selected to Off In this case the settings are as follows EnerVista UR Setup example shown Figure 5 104 TRIP CIRCUIT EXAMPLE 2 The wiring connection for two examples above is applicable to both form A contacts with voltage monitoring and solid state contact with voltage monito...

Page 372: ...o EQL or less than LO the set value COUNTER 1 UP Selects the FlexLogic operand for incrementing the counter If an enabled UP input is received when the accumulated value is at the limit of 2 147 483 647 counts the counter will rollover to 2 147 483 648 COUNTER 1 DOWN Selects the FlexLogic operand for decrementing the counter If an enabled DOWN input is received when the accumulated value is at the...

Page 373: ...erand for capturing freezing the accumulated count value into a separate register with the date and time of the operation and resetting the count to 0 COUNTER 1 FREEZE COUNT Selects the FlexLogic operand for capturing freezing the accumulated count value into a separate register with the date and time of the operation and continuing counting The present accumulated value and captured frozen value ...

Page 374: ...MESSAGE BREAKER 3 ARCING CURRENT See page 5 239 MESSAGE BREAKER 4 ARCING CURRENT See page 5 239 MESSAGE BREAKER FLASHOVER 1 See page 5 242 MESSAGE BREAKER FLASHOVER 2 See page 5 242 MESSAGE BREAKER RESTRIKE 1 See page 5 247 MESSAGE BREAKER RESTRIKE 2 See page 5 247 MESSAGE VT FUSE FAILURE 1 See page 5 249 MESSAGE VT FUSE FAILURE 2 See page 5 249 MESSAGE VT FUSE FAILURE 3 See page 5 249 MESSAGE VT ...

Page 375: ...ult duration is defined as a time between operation of the disturbance detector occurring before initiation of this feature and reset of an internal low set overcurrent function Cor rection is implemented to account for a non zero reset time of the overcurrent function Breaker arcing currents and fault duration values are available under the ACTUAL VALUES RECORDS MAINTENANCE BREAKER 1 4 menus BKR ...

Page 376: ...Multilin 5 7 CONTROL ELEMENTS 5 SETTINGS 5 Figure 5 106 ARCING CURRENT MEASUREMENT Initiate Breaker Contacts Part Arc Extinguished 100 ms Programmable Start Delay Start Integration Stop Integration Total Area Breaker Arcing Current kA cycle ...

Page 377: ...G AMPS BKR 1 ARCING AMP FA BKR 1 OPERATING TIME FA BKR 1 OPERATING TIME FB BKR 1 OPERATING TIME FC BKR 1 OPERATING TIME BKR 1 ARCING AMP FB BKR 1 ARCING AMP FC BKR1 ARC OP BKR1 ARC DPO BREAKER 1 ARCING AMP SOURCE IA IB IC Off 0 Off 0 Off 0 Off 0 NO 0 YES 1 Enabled 1 AND AND OR 859750A1 CDR KA Cycle Limit 2 SETTING BREAKER 1 ARCING AMP DELAY 100 ms 0 0 Set All To Zero Add to Accumulator Integrate I...

Page 378: ...ne SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE BKR 1 STATUS CLSD A Off Range FlexLogic operand MESSAGE BKR 1 STATUS CLSD B Off Range FlexLogic operand MESSAGE BKR 1 STATUS CLSD C Off Range FlexLogic operand MESSAGE BKR 1 FLSHOVR V PKP 0 850 pu Range 0 000 to 1 500 pu in steps of 0 001 MESSAGE BKR 1 FLSHOVR DIFF V PKP 1000 V Range 0 to 100000 V in steps of 1 MESSAGE BKR 1 FLSHOVR AMP PKP 0 600 pu Range 0 000 t...

Page 379: ... prior to flashover detection are 1 52a status 0 2 VAg VBg or VCg is greater than the pickup setting 3 IA IB IC 0 no current flows through the breaker 4 ΔVA is greater than pickup not applicable in this scheme The conditions at flashover detection are 1 52a status 0 2 IA IB or IC is greater than the pickup current flowing through the breaker 3 ΔVA is greater than pickup not applicable in this sche...

Page 380: ...RK 1 STATUS CLSD A to BRK 1 STATUS CLSD C These settings specify FlexLogic operands to indicate the open status of the breaker A separate FlexLogic operand can be selected to detect individual breaker pole status and pro vide flashover detection The recommended setting is 52a breaker contact or another operand defining the breaker poles open status BRK 1 FLSHOVR V PKP This setting specifies a pick...

Page 381: ... per breaker pole that supervise the operation of the element per phase Supervision can be provided by operation of other protection elements breaker failure and close and trip commands A six cycle time delay applies after the selected FlexLogic operand resets BRK FLSHOVR PKP DELAY This setting specifies the time delay to operate after a pickup condition is detected ...

Page 382: ...K 1 FLSHOVR SUPV B BRK 1 STATUS CLSD C BRK 1 FLSHOVR SUPV C BRK 1 FLSHOVR AMP PKP BRK 1 FLSHOVR DIFF V PKP BRK 1 FLSHOVR SIDE 1 SRC BRK 1 FLSHOVR SIDE 2 SRC Enable 1 RUN RUN RUN RUN RUN RUN SRC 1 SRC 2 SRC 6 SRC 1 SRC 2 SRC 6 none VB Vb IB Block OFF 0 VA PKP FlexLogic operand On 1 FlexLogic operand Off 0 FlexLogic operand On 1 FlexLogic operand Off 0 Phase B logic Phase B logic Phase B logic Phase...

Page 383: ...urrent with a magnitude greater than the threshold is resumed at least of a cycle later than the phase current interruption then a breaker restrike condi BREAKER RESTRIKE 1 BREAKER RESTRIKE 1 FUNCTION Disabled Range Disabled Enabled MESSAGE BKR RSTR 1 BLOCK Off Range FlexLogic operand MESSAGE BREAKER RESTRIKE 1 SOURCE SRC 1 Range SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE BREAKER RESTRIKE 1 PICKUP 0 500 pu R...

Page 384: ...the breaker failure function or a regular instantaneous overcurrent element Also a fast succession of restrikes will be picked up by breaker failure or instantaneous overcurrent protection The following settings are available for each element BREAKER RESTRIKE 1 FUNCTION This setting enable and disables operation of the breaker restrike detection ele ment BRK RSTR 1 BLOCK This setting is used to bl...

Page 385: ...f AC potential caused by one or more blown fuses Some elements that might be blocked via the BLOCK input are distance voltage restrained overcurrent and directional current There are two classes of fuse failure that occur Class A loss of one or two phases Class B loss of all three phases Different means of detection are required for each class An indication of class A failures is a significant lev...

Page 386: ...WIRE OPEN 1 3 HRAM PKP setting specifies the pickup level of 3rd harmonic of 3V0 signal for the VT NEU WIRE OPEN detection logic to pick up Figure 5 112 VT FUSE FAIL SCHEME LOGIC Base voltage for this element is PHASE VT SECONDARY setting in the case of WYE VTs and PHASE VT SECONDARY in case of DELTA VTs 827093AQ CDR FUSE FAIL FAULT AND AND AND SET RESET Reset dominant Latch AND AND AND AND OR OR ...

Page 387: ...ve is defined as follows EQ 5 22 In the above equations top time to operate τop thermal protection trip time constant I measured overload RMS current Ip measured load RMS current before overload occurs k IEC 255 8 k factor applied to IB defining maximum permissible current above nominal current THERMAL PROTECTION 1 THERMAL PROTECTION 1 FUNCTION Disabled Range Disabled Enabled MESSAGE THERMAL PROTE...

Page 388: ...e delayed using following formula EQ 5 23 In the above equation τrst thermal protection trip time constant Tmin is a minimum reset time setting Figure 5 113 IEC 255 8 SAMPLE OPERATE AND RESET CURVES The thermal overload protection element estimates accumulated thermal energy E using the following equations calculated each power cycle When current is greater than the pickup level In k IB element st...

Page 389: ...calculations are performed per phase If the accumulated energy reaches value 1 in any phase the thermal overload protection element operates and only resets when energy is less than 0 05 in all three phases The logic for the thermal overload protection element is shown below Figure 5 114 THERMAL OVERLOAD PROTECTION SCHEME LOGIC Table 5 32 TYPICAL TIME CONSTANTS PROTECTED EQUIPMENT TIME CONSTANT MI...

Page 390: ... user settable debounce time in order for the C60 to validate the new contact state In the figure below the debounce time is set at 2 5 ms thus the 6th sample in a row validates the change of state mark no 1 in the diagram Once validated de bounced the contact input asserts a corresponding FlexLogic operand and logs an event as per user setting A time stamp of the first sample in the sequence that...

Page 391: ... filter the LOW HIGH marks no 1 2 3 and 4 in the figure below and HIGH LOW marks no 5 6 7 and 8 below transitions Figure 5 115 INPUT CONTACT DEBOUNCING MECHANISM AND TIME STAMPING SAMPLE TIMING Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each group The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect ...

Page 392: ...put operand will be set to on for only one evaluation of the FlexLogic equations and then return to off If set to Latched the virtual input sets the state of the output operand to the same state as the most recent received input The self reset operating mode generates the output operand for a single evaluation of the FlexLogic equations If the operand is to be used anywhere other than internally i...

Page 393: ... prevent damage to the less robust initiating contact This can be done by monitoring an auxiliary contact on the breaker which opens when the breaker has tripped but this scheme is subject to incorrect oper ation caused by differences in timing between breaker auxiliary contact change of state and interruption of current in the trip circuit The most dependable protection of the initiating contact ...

Page 394: ...rip coil of the contact The relay will seal in this input to safely open the contact Once the contact is opened and the OPERATE input is logic 0 off any activity of the RESET input such as subsequent chattering will not have any effect With both the OPERATE and RESET inputs active logic 1 the response of the latching contact is specified by the OUTPUT H1A TYPE setting OUTPUT H1a TYPE This setting ...

Page 395: ...y specific sequence of operation such as make before break If required the sequence of operation must be programmed explicitly by delaying some of the con trol inputs as shown in the next application example Application Example 3 A make before break functionality must be added to the preceding example An overlap of 20 ms is required to implement this functionality as described below Write the foll...

Page 396: ...ity GOOSE messages have additional advantages over GSSE messages due to their support of VLAN virtual LAN and Ethernet priority tagging functionality The GSSE message structure contains space for 128 bit pairs representing digital point state information The IEC 61850 specification provides 32 DNA bit pairs that represent the state of two pre defined events and 30 user defined events All remaining...

Page 397: ...mmed in the SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE GOOSE CONFIGURATION TRANSMISSION FIXED GOOSE GOOSE ID setting Likewise the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes sage is programmed in the SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE GOOSE CONFIGURATION TRANSMISSION GSSE GSSE ID setting In C60 ...

Page 398: ... UserSt 32 and Dataset Item 1 through Dataset Item 32 The function of DNA inputs is defined in the IEC 61850 specification and is presented in the IEC 61850 DNA Assignments table in the Remote Outputs section The function of UserSt inputs is defined by the user selection of the FlexLogic operand whose state is represented in the GSSE GOOSE message A user must program a DNA point from the appropria...

Page 399: ...emote double point status input REM DPS IN 1 DEV This setting selects a remote device ID to indicate the origin of a GOOSE message The range is selected from the remote device IDs specified in the Remote Devices section REM DPS IN 1 ITEM This setting specifies the required bits of the GOOSE message The configurable GOOSE dataset items must be changed to accept a double point status item from a GOO...

Page 400: ...o latch the faceplate LED event indicators target message and or graphical panel annunciator windows Once set the latching mechanism holds all of the latched indicators or messages in the set state after the initiating condition has cleared until a RESET command is received to return these latches not including FlexLogic latches to the reset state where the initiating condition has cleared The RES...

Page 401: ...st communication exchange the input will default to Logic 1 When communication resumes the input becomes fully operational Setting DIRECT INPUT 1 DEFAULT STATE to Latest Off freezes the input in case of lost communications If the latest state is not known such as after relay power up but before the first communication exchange the input will default to Logic 0 When communication resumes the input ...

Page 402: ...ignal from downstream devices say 2 3 and 4 to the upstream device that monitors a single incomer of the busbar as shown in the figure below Figure 5 120 SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME Assume that Phase Instantaneous Overcurrent 1 is used by Devices 2 3 and 4 to block Device 1 If not blocked Device 1 would trip the bus upon detecting a fault and applying a short coordination time del...

Page 403: ...architecture shown below The scheme output operand HYB POTT TX1 is used to key the permission Figure 5 122 SINGLE CHANNEL OPEN LOOP CONFIGURATION In the above architecture Devices 1 and 3 do not communicate directly Therefore Device 2 must act as a bridge The fol lowing settings should be applied UR IED 1 DIRECT OUT 2 OPERAND HYB POTT TX1 DIRECT INPUT 5 DEVICE ID 2 DIRECT INPUT 5 BIT NUMBER 2 this...

Page 404: ...IRECT INPUT AND OUTPUT EXAMPLE 3 In three terminal applications both the remote terminals must grant permission to trip Therefore at each terminal direct inputs 5 and 6 should be ANDed in FlexLogic and the resulting operand configured as the permission to trip HYB POTT RX1 setting 842717A1 CDR UR IED 3 UR IED 2 UR IED 1 DIRECT OUT 2 HYB POTT TX1 DIRECT INPUT 5 DIRECT INPUT 6 DIRECT OUT 2 HYB POTT ...

Page 405: ...ionality The teleprotection function must be enabled to utilize the inputs b TELEPROTECTION INPUTS PATH SETTINGS INPUTS OUTPUTS TELEPROTECTION TELEPROT INPUTS Setting the TELEPROT INPUT DEFAULT setting to On defaults the input to logic 1 when the channel fails A value of Off defaults the input to logic 0 when the channel fails The Latest On and Latest Off values freeze the input in case of lost co...

Page 406: ...ROT OUTPUT 2 1 Off Range FlexLogic operand MESSAGE TELEPROT OUTPUT 2 2 Off Range FlexLogic operand MESSAGE TELEPROT OUTPUT 2 16 Off Range FlexLogic operand 842750A2 CDR TELEPROT OUTPUT 1 1 same for 1 2 1 16 TELEPROT INPUT 1 1 DEFAULT same for 1 2 1 16 Off Flexlogic Operand TELEPRO INPUT 1 1 On same for 1 2 1 16 UR 1 Teleprotection I O Enabled Communication channel 1 On Off ACTUAL VALUES CHANNEL 1 ...

Page 407: ...gles or power factor can be used in a FlexEle ment The following text must be used in the UNITS setting to represent these types of analogs A V W var VA Hz deg and no text blank setting for power factor GOOSE Analogs can be compared to other GOOSE Analogs with any character string or no string GOOSE ANALOG 1 PU This setting specifies the per unit base factor when using the GOOSE analog input FlexA...

Page 408: ...and this setting is Last Known the value of the GOOSE uinteger input remains at the last received value When the sending device is offline and this setting value is Default Value then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting The GOOSE integer input FlexInteger values are available for use in other C60 functions that use FlexInteger values SOURCE ENERGY Pos...

Page 409: ...e automatically generated for every channel available in the specific relay as shown above for the first channel of a type 5F transducer module installed in slot H The function of the channel may be either Enabled or Disabled If Disabled no actual values are created for the chan nel An alphanumeric ID is assigned to each channel this ID will be included in the channel actual value along with the p...

Page 410: ... automatically generated for every channel available in the specific relay as shown above for the first channel of a type 5C transducer module installed in the first available slot The function of the channel may be either Enabled or Disabled If Disabled there will not be an actual value created for the channel An alphanumeric ID is assigned to the channel this ID will be included in the channel a...

Page 411: ... 122 119 39 157 74 131 45 10 97 60 140 123 24 165 90 138 25 11 35 70 158 127 07 174 25 145 20 11 74 80 176 130 89 182 84 152 37 12 12 90 194 134 70 191 64 159 70 12 51 100 212 138 50 200 64 167 20 12 90 110 230 142 29 209 85 174 87 13 28 120 248 146 06 219 29 182 75 13 67 130 266 149 82 228 96 190 80 14 06 140 284 153 58 238 85 199 04 14 44 150 302 157 32 248 95 207 45 14 83 160 320 161 04 259 30 ...

Page 412: ...nu an exam ple for channel M5 is shown The relay checks the driving signal x in equations below for the minimum and maximum limits and subsequently re scales so the limits defined as MIN VAL and MAX VAL match the output range of the hardware defined as RANGE The follow ing equation is applied EQ 5 26 where x is a driving signal specified by the SOURCE setting Imin and Imax are defined by the RANGE...

Page 413: ...tem measured via UR series relay source 1 is to be monitored by the DCmA H1 output of the range of 1 to 1 mA The following settings are applied on the relay CT ratio 1200 5 VT secondary 115 VT connection is delta and VT ratio 120 The nominal current is 800 A primary and the nominal power factor is 0 90 The power is to be monitored in both importing and exporting directions and allow for 20 overloa...

Page 414: ...are EQ 5 35 The base unit for voltage refer to the FlexElements section in this chapter for additional details is EQ 5 36 The minimum and maximum voltage values to be monitored in pu are EQ 5 37 The following settings should be entered DCMA OUTPUT H3 SOURCE SRC 2 V_1 mag DCMA OUTPUT H3 RANGE 0 to 1 mA DCMA OUTPUT H3 MIN VAL 0 404 pu DCMA OUTPUT H3 MAX VAL 0 635 pu The limit settings differ from th...

Page 415: ...ns based inputs and outputs remain fully operational in test mode If a control action is programmed using direct inputs and outputs or remote inputs and outputs then the test procedure must take this into account When in Forcible mode the operand selected by the TEST MODE FORCING setting dictates further response of the C60 to testing conditions To force contact inputs and outputs through relay se...

Page 416: ...across the input terminals The force contact inputs feature provides a method of performing checks on the function of all contact inputs Once enabled the relay is placed into test mode allowing this feature to override the normal function of contact inputs The Test Mode LED will be on indicating that the relay is in test mode The state of each contact input may be programmed as Dis abled Open or C...

Page 417: ... 3 should open and contact input 4 should close Also contact output 1 should freeze contact output 2 should open contact output 3 should close and contact output 4 should remain fully opera tional The required settings are shown below To enable user programmable pushbutton 1 to initiate the test mode make the following changes in the SETTINGS TESTING TEST MODE menu TEST MODE FUNCTION Enabled and T...

Page 418: ... MESSAGE PMU 1 VC TEST ANGLE 120 00 Range 180 00 to 180 00 in steps of 0 05 MESSAGE PMU 1 VX TEST MAGNITUDE 500 00 kV Range 0 00 to 700 00 kV in steps of 0 01 MESSAGE PMU 1 VX TEST ANGLE 0 00 Range 180 00 to 180 00 in steps of 0 05 MESSAGE PMU 1 IA TEST MAGNITUDE 1 000 kA Range 0 000 to 9 999 kA in steps of 0 001 MESSAGE PMU 1 IA TEST ANGLE 10 00 Range 180 00 to 180 00 in steps of 0 05 MESSAGE PMU...

Page 419: ... the outgoing data frames When required it is recommended to use the user pro grammable digital channels to signal the IEEE C37 118 client that test values are being sent in place of the real measure ments The UR Synchrophasor Implementation defines a test mode which sends a pre defined set of Synchrophasors out over the communication channel when the test mode function setting is enabled In test ...

Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...

Page 421: ...UTPUTS See page 6 5 VIRTUAL OUTPUTS See page 6 6 AUTORECLOSE See page 6 6 REMOTE DEVICES STATUS See page 6 6 REMOTE DEVICES STATISTICS See page 6 7 DIGITAL COUNTERS See page 6 7 SELECTOR SWITCHES See page 6 7 FLEX STATES See page 6 8 ETHERNET See page 6 8 REAL TIME CLOCK SYNCHRONIZING See page 6 8 DIRECT INPUTS See page 6 9 DIRECT DEVICES STATUS See page 6 10 IEC 61850 GOOSE UINTEGERS See page 6 1...

Page 422: ... IEC 61850 GOOSE ANALOGS See page 6 22 SENSITIVE DIRECTIONAL POWER See page 6 22 PHASOR MEASUREMENT UNIT See page 6 23 PMU AGGREGATOR See page 6 23 TRANSDUCER I O DCMA INPUTS See page 6 24 TRANSDUCER I O RTD INPUTS See page 6 24 ACTUAL VALUES RECORDS FAULT REPORTS See page 6 25 EVENT RECORDS See page 6 25 OSCILLOGRAPHY See page 6 26 DATA LOGGER See page 6 26 PMU RECORDS See page 6 27 MAINTENANCE S...

Page 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...

Page 424: ...tes the ID of the virtual input For example Virt Ip 1 refers to the virtual input in terms of the default name The second line of the display indicates the logic state of the virtual input 6 2 3 REMOTE INPUTS PATH ACTUAL VALUES STATUS REMOTE INPUTS The present state of the 32 remote inputs is shown here The state displayed will be that of the remote point unless the remote device has been establis...

Page 425: ...e The first line of a message display indicates the ID of the contact output For example Cont Op 1 refers to the contact output in terms of the default name array index The second line of the display indicates the logic state of the contact output REMOTE DPS INPUTS REMOTE DPS INPUT 1 STATUS Bad Range On Off Intermediate Bad MESSAGE REMOTE DPS INPUT 2 STATUS Bad Range On Off Intermediate Bad MESSAG...

Page 426: ...r that output 6 2 8 AUTORECLOSE PATH ACTUAL VALUES STATUS AUTORECLOSE The automatic reclosure shot count is shown here 6 2 9 REMOTE DEVICES a STATUS PATH ACTUAL VALUES STATUS REMOTE DEVICES STATUS The present state of the programmed remote devices is shown here The ALL REMOTE DEVICES ONLINE message indicates whether or not all programmed remote devices are online If the corresponding state is No t...

Page 427: ...COUNTERS DIGITAL COUNTERS Counter 1 8 The present status of the eight digital counters is shown here The status of each counter with the user defined counter name includes the accumulated and frozen counts the count units label will also appear Also included is the date and time stamp for the frozen count The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp 6 2 11 SELECTO...

Page 428: ... PTP grandmaster this actual value is zero The grandmasterIdentity code is specified by PTP to be globally unique so one can always know which clock is grandmaster in a system with multiple grandmaster capable clocks FLEX STATES PARAM 1 Off Off Range Off On MESSAGE PARAM 2 Off Off Range Off On MESSAGE PARAM 256 Off Off Range Off On ETHERNET ETHERNET PRI LINK STATUS Fail Range Fail OK MESSAGE ETHER...

Page 429: ... ACTUAL VALUES STATUS DIRECT INPUTS The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input output ring configuration this value is not applicable for non ring configurations This is a rolling average calculated for the last ten messages There are two return times for dual channel communications modules The UNRETURNED MSG COUNT values one ...

Page 430: ...points are displayed in this menu The GGIO5 integer data values are received via IEC 61850 GOOSE messages sent from other devices 6 2 18 EGD PROTOCOL STATUS a FAST EXCHANGE PATH ACTUAL VALUES STATUS EGD PROTOCOL STATUS PRODUCER STATUS FAST EXCHANGE 1 These values provide information that may be useful for debugging an EGD network The EGD signature and packet size for the fast EGD exchange is displ...

Page 431: ...ion this count can be reset to 0 through the COMMANDS CLEAR RECORDS menu VALIDITY OF CHANNEL CONFIGURATION This value displays the current state of the communications channel identification check and hence validity If a remote relay ID does not match the programmed ID at the local relay the FAIL message will be displayed The N A value appears if the local relay ID is set to a default value of 0 th...

Page 432: ...plays here 6 2 21 PARALLEL REDUNDANCY PROTOCOL PRP The Parallel Redundancy Protocol PRP defines a redundancy protocol for high availability in substation automation net works PATH ACTUAL VALUES STATUS PRP The C60 Breaker Protection System is provided with optional PRP capability This feature is specified as a software option at the time of ordering See the Order Codes section in chapter 2 for deta...

Page 433: ...ve PF Lag Current Voltage WATTS Positive VARS Negative PF Lead Current Voltage WATTS Negative VARS Negative PF Lag Current Voltage WATTS Negative VARS Positive PF Lead Current Generator Generator Inductive Inductive Resistive Resistive Generator Generator UR RELAY UR RELAY UR RELAY UR RELAY G G M M G G VCG IC VAG IA VBG IB 1 VCG IC VAG IA VBG IB 2 VCG IC VAG IA VBG IB 3 VCG IC VAG IA VBG IB 4 Q Q ...

Page 434: ...t measurable the phase angles are not referenced The phase angles are assigned as positive in the leading direction and are presented as negative in the lagging direction to more closely align with power system metering conventions This is illustrated below Figure 6 2 UR PHASE ANGLE MEASUREMENT CONVENTION c UR CONVENTION FOR MEASURING SYMMETRICAL COMPONENTS The UR series of relays calculate voltag...

Page 435: ...rated in the following figure Figure 6 3 MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS ABC phase rotation ACB phase rotation Table 6 1 SYMMETRICAL COMPONENTS CALCULATION EXAMPLE SYSTEM VOLTAGES SEC V VT CONN RELAY INPUTS SEC V SYMM COMP SEC V VAG VBG VCG VAB VBC VCA F5AC F6AC F7AC V0 V1 V2 13 9 0 76 2 125 79 7 250 84 9 313 138 3 97 85 4 241 WYE 13 9 0 76 2 125 79 7 250 19 5 192 56 5 7 23 3 187...

Page 436: ... PATH ACTUAL VALUES METERING SOURCE SRC 1 PHASE CURRENT SOURCE SRC 1 PHASE CURRENT SRC 1 See page 6 16 MESSAGE GROUND CURRENT SRC 1 See page 6 17 MESSAGE PHASE VOLTAGE SRC 1 See page 6 17 MESSAGE AUXILIARY VOLTAGE SRC 1 See page 6 18 MESSAGE POWER SRC 1 See page 6 18 MESSAGE ENERGY SRC 1 See page 6 19 MESSAGE DEMAND SRC 1 See page 6 19 MESSAGE FREQUENCY SRC 1 See page 6 20 PHASE CURRENT SRC 1 SRC ...

Page 437: ...urce see SETTINGS SYSTEM SETUP SIGNAL SOURCES d PHASE VOLTAGE METERING PATH ACTUAL VALUES METERING SOURCE SRC 1 PHASE VOLTAGE MESSAGE SRC 1 ZERO SEQ I0 0 000 A 0 0 MESSAGE SRC 1 POS SEQ I1 0 000 A 0 0 MESSAGE SRC 1 NEG SEQ I2 0 000 A 0 0 GROUND CURRENT SRC 1 SRC 1 RMS Ig 0 000 A MESSAGE SRC 1 PHASOR Ig 0 000 A 0 0 MESSAGE SRC 1 PHASOR Igd 0 000 A 0 0 PHASE VOLTAGE SRC 1 SRC 1 RMS Vag 0 00 V MESSAG...

Page 438: ...S SYSTEM SETUP SIGNAL SOURCES f POWER METERING PATH ACTUAL VALUES METERING SOURCE SRC 1 POWER MESSAGE SRC 1 PHASOR Vca 0 000 V 0 0 MESSAGE SRC 1 ZERO SEQ V0 0 000 V 0 0 MESSAGE SRC 1 POS SEQ V1 0 000 V 0 0 MESSAGE SRC 1 NEG SEQ V2 0 000 V 0 0 AUXILIARY VOLTAGE SRC 1 SRC 1 RMS Vx 0 00 V MESSAGE SRC 1 PHASOR Vx 0 000 V 0 0 POWER SRC 1 SRC 1 REAL POWER 3φ 0 000 W MESSAGE SRC 1 REAL POWER φa 0 000 W M...

Page 439: ... voltage phasors Î is the conjugate of I g ENERGY METERING PATH ACTUAL VALUES METERING SOURCE SRC 1 ENERGY The metered values for real and reactive energy are displayed in this menu The SRC 1 text will be replaced by whatever name was programmed by the user for the associated source see SETTINGS SYSTEM SETUP SIGNAL SOURCES Because energy values are accumulated these values should be recorded and t...

Page 440: ...me interval the maxi mum demand since the last maximum demand reset and the time and date stamp of this maximum demand value Maxi mum demand quantities can be reset to zero with the CLEAR RECORDS CLEAR DEMAND RECORDS command i FREQUENCY METERING PATH ACTUAL VALUES METERING SOURCE SRC 1 FREQUENCY MESSAGE SRC 1 DMD IA DATE 2001 07 31 16 30 07 MESSAGE SRC 1 DMD IB 0 000 A MESSAGE SRC 1 DMD IB MAX 0 0...

Page 441: ...g frequency is displayed here The frequency is tracked based on the selection of the reference source with the FREQUENCY AND PHASE REFERENCE setting in the SETTINGS SYSTEM SETUP POWER SYSTEM menu See the Power System section of chapter 5 for details 6 3 5 FLEXELEMENTS PATH ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1 8 The operating signals for the FlexElements are displayed in pu values usin...

Page 442: ...ies of the sensitive directional power elements are displayed here The display may be useful to calibrate the feature by compensating the angular errors of the CTs and VTs with the use of the RCA and CALIBRATION settings SOURCE ENERGY Positive and Negative Watthours Positive and Negative Varhours EBASE 10000 MWh or MVAh respectively SOURCE POWER PBASE maximum value of VBASE IBASE for the IN and IN...

Page 443: ...onnection MESSAGE PMU 1 VB 0 0000 kV 0 00 Range Va or Vab per VT bank connection MESSAGE PMU 1 VC 0 0000 kV 0 00 Range Va or Vab per VT bank connection MESSAGE PMU 1 VX 0 0000 kV 0 00 MESSAGE PMU 1 V1 0 0000 kV 0 00 MESSAGE PMU 1 V2 0 0000 kV 0 00 MESSAGE PMU 1 V0 0 0000 kV 0 00 Range Substituted with zero if delta connected VTs MESSAGE PMU 1 IA 0 0000 kA 0 00 MESSAGE PMU 1 IB 0 0000 kA 0 00 MESSA...

Page 444: ...fragmented data frames causing increased network traffic 6 3 10 TRANSDUCER INPUTS OUTPUTS PATH ACTUAL VALUES METERING TRANSDUCER I O DCMA INPUTS DCMA INPUT xx Actual values for each dcmA input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value followed by the programmed units PATH ACTUAL VALUES METERING TRANSDUCER I O RTD INPUTS RT...

Page 445: ... have been filled the oldest record will be removed as a new record is added Each event record shows the event identifier sequence number cause and date time stamp associated with the event trigger See the COMMANDS CLEAR RECORDS menu for clearing event records Only major output operands generate events not every operand Elements that assert output per phase for example log operating phase output o...

Page 446: ...cords 6 4 4 DATA LOGGER PATH ACTUAL VALUES RECORDS DATA LOGGER The OLDEST SAMPLE TIME represents the time at which the oldest available samples were taken It will be static until the log gets full at which time it will start counting at the defined sampling rate The NEWEST SAMPLE TIME represents the time the most recent samples were taken It counts up at the defined sampling rate If the data logge...

Page 447: ...LEAR RECORDS menu for clearing breaker arcing current records The BREAKER OPERATING TIME is defined as the slowest operating time of breaker poles that were initiated to open PMU RECORDS NUMBER OF TRIGGERS 0 Range 0 to 65535 in steps of 1 MESSAGE PMU 1 RECORDING See below PMU 1 RECORDING PMU 1 FORCE TRIGGER Yes Range No Yes MESSAGE PUM 1 AVAILABLE RECORDS 0 Range 0 to 65535 in steps of 1 MESSAGE P...

Page 448: ...ample order code shown MESSAGE SERIAL NUMBER Range standard GE serial number format MESSAGE ETHERNET MAC ADDRESS 000000000000 Range standard Ethernet MAC address format MESSAGE MANUFACTURING DATE 0 Range YYYY MM DD HH MM SS MESSAGE PMU FEATURE ACTIVE No Range Yes No MESSAGE CT VT ADVANCED DIAG ACTIVE No Range Yes No MESSAGE OPERATING TIME 0 00 00 Range operating time in HH MM SS MESSAGE LAST SETTI...

Page 449: ...d entry 7 1 2 VIRTUAL INPUTS PATH COMMANDS VIRTUAL INPUTS The states of up to 64 virtual inputs are changed here The first line of the display indicates the ID of the virtual input The second line indicates the current or selected status of the virtual input This status will be a state off logic 0 or on logic 1 COMMANDS MESSAGE COMMANDS VIRTUAL INPUTS MESSAGE COMMANDS CLEAR RECORDS MESSAGE COMMAND...

Page 450: ... relay is synchronizing to an external time source such as PTP IRIG B or SNTP the manually entered time is over written COMMANDS CLEAR RECORDS CLEAR FAULT REPORTS No Range No Yes CLEAR OSCILLOGRAPHY No Range No Yes CLEAR DATA LOGGER No Range No Yes CLEAR BREAKER 1 ARCING AMPS No Range No Yes CLEAR BREAKER 2 ARCING AMPS No Range No Yes CLEAR DEMAND RECORDS No Range No Yes CLEAR ENERGY No Range No Y...

Page 451: ...GE Multilin C60 Breaker Protection System 7 3 7 COMMANDS AND TARGETS 7 1 COMMANDS 7 The timescale of the entered time is local time including daylight savings time where and when applicable ...

Page 452: ...e can initiate the Reboot Relay command The SERVICE COMMAND is used to perform specific C60 service actions Presently there is only one service action avail able Code 101 is used to clear factory diagnostic information stored in the non volatile memory If a code other than 101 is entered the command will be ignored and no actions will be taken Various self checking diagnostics are performed in the...

Page 453: ...t time The PMU ONE SHOT PENDING operand indicates that the one shot operation is pending that is the present time is before the scheduled one shot time The PMU ONE SHOT OP operand indicates the one shot operation and remains asserted for 30 seconds afterwards When the function is disabled all three operands are de asserted The one shot function applies to all logical PMUs of a given C60 relay Figu...

Page 454: ...referenced to different time scales Figure 7 2 USING THE PMU ONE SHOT FEATURE TO TEST SYNCHROPHASOR MEASUREMENT ACCURACY Collecting synchronized measurements ad hoc The one shot feature can be used for ad hoc collection of synchronized measurements in the network Two or more PMU can be pre scheduled to freeze their measurements at the same time When frozen the measurements could be collected using...

Page 455: ...ill be included if applicable If a tar get message status changes the status with the highest priority will be displayed If a self test error is detected a message appears indicating the cause of the error For example UNIT NOT PROGRAMMED indicates that the minimal relay settings have not been programmed 7 1 10 RELAY SELF TESTS a DESCRIPTION The relay performs a number of self test diagnostic check...

Page 456: ...ed target message No Description of problem A FlexLogic equation is incorrect How often the test is performed The test is event driven performed whenever FlexLogic equations are modified What to do Finish all equation editing and use self tests to debug any errors Latched target message No Description of problem The PRODUCT SETUP INSTALLATION RELAY SETTINGS setting indicates the C60 is not pro gra...

Page 457: ... as fast distance protection Synchrophasors Frequency and Rate of Change of Frequency calculations to conform to C37 118 2005 standard The new functionality leveraging the hardware is supported with firmware revision 7 25 and above When using an older revision of the process card with a new firmware revision 7 25 Module Failure 31 indicates the limited functionality If your application requires th...

Page 458: ...sical damage or perform a continuity test The IRIG B receiver is functioning Check the input signal level it may be less than specification If none of these apply then contact the factory Latched target message No Description of problem No PTP enabled port has good PTP signal input How often the test is performed Activated when no acceptable signal is being received What to do Ensure the following...

Page 459: ...t is performed Every second What to do Check direct input and output configuration and wiring Latched target message No Description of problem One or more GOOSE devices are not responding How often the test is performed Event driven The test is performed when a device programmed to receive GOOSE messages stops receiving This can be from 1 to 60 seconds depending on GOOSE packets What to do Check G...

Page 460: ...eing down How often the test is performed What to do Check the connection Latched target message No Description of problem The number of failures threshold was exceeded What to do Wait for the lockout interval and try to authenticate again Message Unauthorized firmware attempt Latched target message No Description of problem A firmware upgrade operation was attempted while the lock relay setting w...

Page 461: ...vated HardFiber Self Test Error Messages In addition to those provided by the standard UR series devices the UR devices implement HardFiber self tests These are listed below Any abnormal diagnostic condition indicated by the LEDs or the critical failure relay also results in a self test message so troubleshooting is described here For other relays such at the B95Plus see that product s instruction...

Page 462: ...ngle origin Process Bus Trouble Minor Self Test Description Communications problems with one or more Bricks The text of the message identifies the affected field units This self test is initiated by low received signal levels at either the Brick or Process Card end and by the sustained failure to receive poll responses from the proper Brick Severity This self test error does not directly inhibit p...

Page 463: ...to fault Z positive sequence impedance of the line The currents from the local and remote systems can be parted between their fault F and pre fault load pre components EQ 8 2 and neglecting shunt parameters of the line EQ 8 3 Inserting the IA and IB equations into the VA equation and solving for the fault resistance yields EQ 8 4 Assuming the fault components of the currents IAF and IBF are in pha...

Page 464: ...ON setting value is V0 and the VTs are connected in a wye configuration the fault location is performed based on the actual phase to ground voltages If the VTs are connected in a delta configuration fault location is performed based on the delta voltages and externally supplied neutral voltage EQ 8 13 If the FAULT REPORT 1 VT SUBSTITUTION setting value is I0 and the VTs are connected in a wye conf...

Page 465: ... 50DD OP X VA or VAB VC or VCA VB or VBC 827094A5 CDR Off 0 AND FAULT LOCATOR 1 RUN 0 3 SEC ACTUAL VALUES DATE TIME FAULT TYPE FAULT LOCATION FAULT RECLOSE SHOT FAULT REPORT Vn or V_0 FAULT REPORT 1 Z1 MAG FAULT REPORT 1 Z1 ANGLE FAULT REPORT 1 Z0 MAG FAULT REPORT 1 Z0 ANGLE FAULT REPORT 1 LENGTH UNITS FAULT REPORT 1 LENGTH FAULT REPORT 1 VT SUBSTITUTION FAULT REP 1 SYSTEM Z0 MAG FAULT REP 1 SYSTE...

Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...

Page 467: ...s for the withdrawal and insertion of modules Modules must only be replaced with like modules in their original factory configured slots The enhanced faceplate can be opened to the left once the thumb screw has been removed as shown below This allows for easy accessibility of the modules for withdrawal The new wide angle hinge assembly in the enhanced front panel opens completely and allows easy a...

Page 468: ...a module ensure that the correct module type is inserted into the correct slot position The ejector inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is smoothly inserted into the slot Once the clips have cleared the raised edge of the chassis engage the clips simultaneously When the clips have locked into position the module will b...

Page 469: ...nhanced front panel 4 For the standard front panel it needs to be removed in order to access the power supply module which is typically in the first slot on the left side and blocked by the hinge of the front panel To remove the front panel unscrew the bracket on the front left side of the unit 5 Simultaneously pull the ejector clips at the top and bottom of the power supply module and remove the ...

Page 470: ...nit 17 Remove the power supply module by simultaneously pulling the ejector clips at the top and bottom of the module and sliding it out 18 Unscrew all four screws not three that attach the metal cover to the module The fourth screw is at the back end of the module on the opposite side from the clips beside the white electronics part see figure 19 Slide the metal cover away from the clips about 0 ...

Page 471: ...αταρία που δεν πρέπει να απορρίπτεται σε δημόσια συστήματα απόρριψης στην Ευρωπαϊκή Κοινότητα είτε την τεκμηρίωση του προϊόντος για συγκεκριμένες πληροφορίες που αφορούν τη μπαταρία Η μπαταρία είναι φέρει σήμανση με αυτό το σύμβολο το οποίο μπορεί να περιλαμβάνει γράμματα για να δηλώσουν το κάδμιο Cd τον μόλυβδο Pb ή τον υδράργυρο Hg Για την κατάλληλη ανακύκλωση επιστρέψτε την μπαταρία στον προμηθ...

Page 472: ...ette produkt inneholder et batteri som ikke kan kastes med usortert kommunalt søppel i den Europeiske Unionen Se produktdokumentasjonen for spesifikk batteriinformasjon Batteriet er merket med dette symbolet som kan inkludere symboler for å indikere at kadmium Cd bly Pb eller kvikksølv Hg forekommer Returner batteriet til leverandøren din eller til et dedikert oppsamlingspunkt for korrekt gjenvinn...

Page 473: ...sedd deponering För mer information se www recyclethis info TR Pil Geri Dönüşümü Bu ürün Avrupa Birliği genel atık sistemlerine atılmaması gereken pil içermektedir Daha detaylı pil bilgisi için ürünün kataloğunu inceleyiniz Bu sembolle işaretlenmiş piller Kadmiyum Cd Kurşun Pb ya da Civa Hg içerebilir Doğru geri dönüşüm için ürünü yerel tedarikçinize geri veriniz ya da özel işaretlenmiş toplama no...

Page 474: ...for example to comply with data security regu lations On the computer settings files can identified by the urs extension To clear the current settings file create a default set tings file write it to the relay then delete all other urs files For the existing installation upgrading the firmware overwrites the flash memory Other files can be in standard formats such as COMTRADE or csv You cannot era...

Page 475: ...rect information Tightly pack the unit in a box with bubble wrap foam material or styrofoam inserts or packaging peanuts to cushion the item s You may also use double boxing whereby you place the box in a larger box that contains at least 5 cm of cushioning material Ship the unit by courier or freight forwarder along with the Commercial Invoice and RMA to the factory GE GRID SOLUTIONS 650 MARKLAND...

Page 476: ...ore the unit indoors in a cool dry place If possible store in the original packaging Follow the storage temperature range outlined in the Specifications To avoid deterioration of electrolytic capacitors power up units that are stored in a de energized state once per year for one hour continuously NOTICE ...

Page 477: ...e battery there are no special requirements for disposal of the unit at the end its service life For customers located in the European Union dispose of the battery as outlined earlier To prevent non intended use of the unit remove the modules as outlined earlier dismantle the unit and recycle the metal when possible ...

Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...

Page 479: ...alue Field TDR 7 value 5846 Field TDR 8 Value Field TDR 8 value 6144 SRC 1 Ia RMS Amps Source 1 phase A current RMS 6146 SRC 1 Ib RMS Amps Source 1 phase B current RMS 6148 SRC 1 Ic RMS Amps Source 1 phase C current RMS 6150 SRC 1 In RMS Amps Source 1 neutral current RMS 6152 SRC 1 Ia Mag Amps Source 1 phase A current magnitude 6154 SRC 1 Ia Angle Degrees Source 1 phase A current angle 6155 SRC 1 ...

Page 480: ...244 SRC 2 Igd Angle Degrees Source 2 differential ground current angle 6272 SRC 3 Ia RMS Amps Source 3 phase A current RMS 6274 SRC 3 Ib RMS Amps Source 3 phase B current RMS 6276 SRC 3 Ic RMS Amps Source 3 phase C current RMS 6278 SRC 3 In RMS Amps Source 3 neutral current RMS 6280 SRC 3 Ia Mag Amps Source 3 phase A current magnitude 6282 SRC 3 Ia Angle Degrees Source 3 phase A current angle 6283...

Page 481: ...rrent angle 6656 SRC 1 Vag RMS Volts Source 1 phase AG voltage RMS 6658 SRC 1 Vbg RMS Volts Source 1 phase BG voltage RMS 6660 SRC 1 Vcg RMS Volts Source 1 phase CG voltage RMS 6662 SRC 1 Vag Mag Volts Source 1 phase AG voltage magnitude 6664 SRC 1 Vag Angle Degrees Source 1 phase AG voltage angle 6665 SRC 1 Vbg Mag Volts Source 1 phase BG voltage magnitude 6667 SRC 1 Vbg Angle Degrees Source 1 ph...

Page 482: ...x Angle Degrees Source 2 auxiliary voltage angle 6755 SRC 2 V_0 Mag Volts Source 2 zero sequence voltage magnitude 6757 SRC 2 V_0 Angle Degrees Source 2 zero sequence voltage angle 6758 SRC 2 V_1 Mag Volts Source 2 positive sequence voltage magnitude 6760 SRC 2 V_1 Angle Degrees Source 2 positive sequence voltage angle 6761 SRC 2 V_2 Mag Volts Source 2 negative sequence voltage magnitude 6763 SRC ...

Page 483: ... Mag Volts Source 4 phase AB voltage magnitude 6871 SRC 4 Vab Angle Degrees Source 4 phase AB voltage angle 6872 SRC 4 Vbc Mag Volts Source 4 phase BC voltage magnitude 6874 SRC 4 Vbc Angle Degrees Source 4 phase BC voltage angle 6875 SRC 4 Vca Mag Volts Source 4 phase CA voltage magnitude 6877 SRC 4 Vca Angle Degrees Source 4 phase CA voltage angle 6878 SRC 4 Vx RMS Volts Source 4 auxiliary volta...

Page 484: ...three phase real power 7234 SRC 3 Pa Watts Source 3 phase A real power 7236 SRC 3 Pb Watts Source 3 phase B real power 7238 SRC 3 Pc Watts Source 3 phase C real power 7240 SRC 3 Q Vars Source 3 three phase reactive power 7242 SRC 3 Qa Vars Source 3 phase A reactive power 7244 SRC 3 Qb Vars Source 3 phase B reactive power 7246 SRC 3 Qc Vars Source 3 phase C reactive power 7248 SRC 3 S VA Source 3 t...

Page 485: ...cy Hz Source 1 frequency 7554 SRC 2 Frequency Hz Source 2 frequency 7556 SRC 3 Frequency Hz Source 3 frequency 7558 SRC 4 Frequency Hz Source 4 frequency 7680 SRC 1 Demand Ia Amps Source 1 phase A current demand 7682 SRC 1 Demand Ib Amps Source 1 phase B current demand 7684 SRC 1 Demand Ic Amps Source 1 phase C current demand 7686 SRC 1 Demand Watt Watts Source 1 real power demand 7688 SRC 1 Deman...

Page 486: ...ase C current magnitude 9032 Prefault Ic Ang 1 Degrees Fault 1 pre fault phase C current angle 9033 Prefault Va Mag 1 Volts Fault 1 pre fault phase A voltage magnitude 9035 Prefault Va Ang 1 Degrees Fault 1 pre fault phase A voltage angle 9036 Prefault Vb Mag 1 Volts Fault 1 pre fault phase B voltage magnitude 9038 Prefault Vb Ang 1 Degrees Fault 1 pre fault phase B voltage angle 9039 Prefault Vc ...

Page 487: ... 9602 PMU 1 Ia Mag Amps Phasor measurement unit 1 phase A current magnitude 9604 PMU 1 Ia Angle Degrees Phasor measurement unit 1 phase A current angle 9605 PMU 1 Ib Mag Amps Phasor measurement unit 1 phase B current magnitude 9607 PMU 1 Ib Angle Degrees Phasor measurement unit 1 phase B current angle 9608 PMU 1 Ic Mag Amps Phasor measurement unit 1 phase C current magnitude 9610 PMU 1 Ic Angle De...

Page 488: ...easurement unit 2 negative sequence current magnitude 9669 PMU 2 I2 Angle Degrees Phasor measurement unit 2 negative sequence current angle 9670 PMU 2 I0 Mag Amps Phasor measurement unit 2 zero sequence current magnitude 9672 PMU 2 I0 Angle Degrees Phasor measurement unit 2 zero sequence current angle 9673 PMU 2 Freq Hz Phasor measurement unit 2 frequency 9675 PMU 2 df dt Hz s Phasor measurement u...

Page 489: ... 20 RTD input 20 actual value 13572 RTD Ip 21 RTD input 21 actual value 13573 RTD Ip 22 RTD input 22 actual value 13574 RTD Ip 23 RTD input 23 actual value 13575 RTD Ip 24 RTD input 24 actual value 13576 RTD Ip 25 RTD input 25 actual value 13577 RTD Ip 26 RTD input 26 actual value 13578 RTD Ip 27 RTD input 27 actual value 13579 RTD Ip 28 RTD input 28 actual value 13580 RTD Ip 29 RTD input 29 actua...

Page 490: ...rmonic 45584 GOOSE Analog In 1 IEC 61850 GOOSE analog input 1 45586 GOOSE Analog In 2 IEC 61850 GOOSE analog input 2 45588 GOOSE Analog In 3 IEC 61850 GOOSE analog input 3 45590 GOOSE Analog In 4 IEC 61850 GOOSE analog input 4 45592 GOOSE Analog In 5 IEC 61850 GOOSE analog input 5 45594 GOOSE Analog In 6 IEC 61850 GOOSE analog input 6 45596 GOOSE Analog In 7 IEC 61850 GOOSE analog input 7 45598 GO...

Page 491: ...RACSEC timestamps 9885 PMU 1 STAT PMU 1 STAT flags 9887 PMU 2 SOC seconds PMU 2 SOC timestamps 9889 PMU 2 FRACSEC seconds PMU 2 FRACSEC timestamps 9891 PMU 2 STAT PMU 2 STAT flags 9968 GOOSE UInt Input 1 IEC61850 GOOSE UInteger input 1 9970 GOOSE UInt Input 2 IEC61850 GOOSE UInteger input 2 9972 GOOSE UInt Input 3 IEC61850 GOOSE UInteger input 3 9974 GOOSE UInt Input 4 IEC61850 GOOSE UInteger inpu...

Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...

Page 493: ...e in packets that are groups of asynchronously framed byte data The master transmits a packet to the slave and the slave responds with a packet The following information describes the general for mat for both transmit and receive packets For details on packet formatting see subsequent sections describing each func tion code SLAVE ADDRESS This is the address of the slave device that is intended to ...

Page 494: ...ocol Identifier Used for intra system multiplexing The Modbus protocol is identified by the value 0 Length The length field is a byte count of the following fields including the Unit Identifier and data fields Unit Identifier For the purposes of the UR this field is equivalent to the Modbus RTU SLAVE ADDRESS field The client must use the same value here as programmed in the UR setting MODBUS SLAVE...

Page 495: ...number of data bytes Di i th data byte i 0 to N 1 G 16 bit characteristic polynomial 1010000000000001 binary with MSbit dropped and bit order reversed shr x right shift operator th LSbit of x is shifted into a carry flag a 0 is shifted into the MSbit of x all other bits are shifted right one location ALGORITHM 1 FFFF hex A 2 0 i 3 0 j 4 Di Alow Alow 5 j 1 j 6 shr A 7 Is there a carry No go to 8 Ye...

Page 496: ...e identical The following table shows the format of the master and slave packetsin Modbus RTU Modbus TCP IP ADUs have a MBAP instead of slave address and CRC is in another stack layer The example shows a master device requesting three register values starting at address 4050h from slave device 11h 17 decimal the slave device responds with the values 40 300 and 0 from registers 4050h 4051h and 4052...

Page 497: ...at memory map address 4051h to slave device 11h 17 dec Table B 5 MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE MASTER TRANSMISSION SLAVE RESPONSE PACKET FORMAT EXAMPLE HEX PACKET FORMAT EXAMPLE HEX SLAVE ADDRESS 11 SLAVE ADDRESS 11 FUNCTION CODE 05 FUNCTION CODE 05 OPERATION CODE high 00 OPERATION CODE high 00 OPERATION CODE low 01 OPERATION CODE low 01 CODE VALUE high FF CODE VALUE high FF ...

Page 498: ...e function code set to 1 The following table shows the format of the master and slave packets in Modbus RTU Modbus TCP IP ADUs have a MBAP instead of slave address and CRC is in another stack layer The example shows a master device sending the unsupported function code 39h to slave device 11h Table B 8 MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE MASTER TRANSMISSION SLAVE RESPONSE PACKET FO...

Page 499: ...cific file transfer information so files may be read simultaneously on multiple Modbus connections b OTHER PROTOCOLS All the files available via Modbus may also be retrieved using the standard file transfer mechanisms in other protocols for example TFTP or MMS c COMTRADE OSCILLOGRAPHY AND DATA LOGGER FILES Oscillography and data logger files are formatted using the COMTRADE file format per IEEE C3...

Page 500: ...ollowing to the filename before writing it To read from a specific time to the end of the log space startTime To read a specific range of records space startTime space endTime Replace startTime and endTime with the number of seconds since Jan 1 1970 as numeric text f READING EVENT RECORDER FILES To read the entire event recorder contents in ASCII format the only available format use the following ...

Page 501: ...upplier Serial Number F203 none 00C0 Ethernet Sub Module Serial Number 8 items F203 none Product Information Read Only Written by Factory 0110 FPGA Version F206 none 0113 FPGA Date 0 to 4294967295 1 F050 0 Product Information Read Write 0120 Undefined 0 to 1 1 F102 0 Self Test Targets Read Only 0200 Self Test States 4 items 0 to 4294967295 0 1 F143 0 Front Panel Read Only 0208 LED Column n State n...

Page 502: ... Virtual Input 41 State 0 to 1 1 F108 0 Off 0429 Virtual Input 42 State 0 to 1 1 F108 0 Off 042A Virtual Input 43 State 0 to 1 1 F108 0 Off 042B Virtual Input 44 State 0 to 1 1 F108 0 Off 042C Virtual Input 45 State 0 to 1 1 F108 0 Off 042D Virtual Input 46 State 0 to 1 1 F108 0 Off 042E Virtual Input 47 State 0 to 1 1 F108 0 Off 042F Virtual Input 48 State 0 to 1 1 F108 0 Off 0430 Virtual Input 4...

Page 503: ...nput 23 05E0 Repeated for Binary Input 24 05E4 Repeated for Binary Input 25 05E8 Repeated for Binary Input 26 05EC Repeated for Binary Input 27 05F0 Repeated for Binary Input 28 05F4 Repeated for Binary Input 29 05F8 Repeated for Binary Input 30 05FC Repeated for Binary Input 31 0600 Repeated for Binary Input 32 0604 Repeated for Binary Input 33 0608 Repeated for Binary Input 34 060C Repeated for ...

Page 504: ...peated for Binary Input 81 06C8 Repeated for Binary Input 82 06CC Repeated for Binary Input 83 06D0 Repeated for Binary Input 84 06D4 Repeated for Binary Input 85 06D8 Repeated for Binary Input 86 06DC Repeated for Binary Input 87 06E0 Repeated for Binary Input 88 06E4 Repeated for Binary Input 89 06E8 Repeated for Binary Input 90 06EC Repeated for Binary Input 91 06F0 Repeated for Binary Input 92...

Page 505: ...Factor 9 0 to 65 535 0 001 F001 1000 0722 IEC103 ASDU 1 Analog Offset 9 32768 to 32767 1 F002 0 0723 Repeated for IEC103 ASDU 2 0742 Repeated for IEC103 ASDU 3 0761 Repeated for IEC103 ASDU 4 IEC 103 Commands Read Write Setting 32 modules 0780 IEC103 Command 1 FUN 0 to 255 1 F001 0 0781 IEC103 Command 1 INF 0 to 255 1 F001 0 0782 IEC103 Command 1 Param ON 0 to 64 1 F631 0 OFF 0783 IEC103 Command 1...

Page 506: ...56 items 0 to 65535 1 F001 0 Element Targets Read Only 14E0 Target Sequence 0 to 65535 1 F001 0 14E1 Number of Targets 0 to 65535 1 F001 0 Element Targets Read Write 14E2 Target to Read 0 to 65535 1 F001 0 Element Targets Read Only 14E3 Target Message F200 Contact Input Output States Read Only 1500 Contact Input States 6 items 0 to 65535 1 F500 0 1508 Virtual Input States 8 items 0 to 65535 1 F500...

Page 507: ...00 0 160B Field Latching Output Physical States 0 to 65535 1 F500 0 160C Field Unit Online Offline States 0 to 65535 1 F500 0 160D Field RTD Input Trouble States 0 to 65535 1 F500 0 160E Field Transducer Input Trouble States 0 to 65535 1 F500 0 Ethernet Fibre Channel Status Read Only 1610 Ethernet Primary Fibre Channel Status 0 to 2 1 F134 0 Fail 1611 Ethernet Secondary Fibre Channel Status 0 to 2...

Page 508: ...rce 1 Differential Ground Current Angle 359 9 to 0 degrees 0 1 F002 0 1825 Reserved 27 items F001 0 1840 Repeated for Source 2 1880 Repeated for Source 3 18C0 Repeated for Source 4 Source Voltage Read Only 4 modules 1A00 Source 1 Phase AG Voltage RMS 0 to 999999 999 V 0 001 F060 0 1A02 Source 1 Phase BG Voltage RMS 0 to 999999 999 V 0 001 F060 0 1A04 Source 1 Phase CG Voltage RMS 0 to 999999 999 V...

Page 509: ... VA 0 001 F060 0 1C12 Source 1 Phase A Apparent Power 1000000000000 to 1000000000000 VA 0 001 F060 0 1C14 Source 1 Phase B Apparent Power 1000000000000 to 1000000000000 VA 0 001 F060 0 1C16 Source 1 Phase C Apparent Power 1000000000000 to 1000000000000 VA 0 001 F060 0 1C18 Source 1 Three Phase Power Factor 0 999 to 1 0 001 F013 0 1C19 Source 1 Phase A Power Factor 0 999 to 1 0 001 F013 0 1C1A Sour...

Page 510: ...ng 2 modules 2196 Breaker Flashover 1 Function 0 to 1 1 F102 0 Disabled 2197 Breaker Flashover 1 Side 1 Source 0 to 5 1 F167 0 SRC 1 2198 Breaker Flashover 1 Side 2 Source 0 to 6 1 F211 0 None 2199 Breaker Flashover 1 Status Closed A 0 to 4294967295 1 F300 0 219B Breaker Flashover 1 Status Closed B 0 to 4294967295 1 F300 0 219D Breaker Flashover 1 Status Closed C 0 to 4294967295 1 F300 0 219F Brea...

Page 511: ... F002 0 2346 Fault 1 Prefault Phase C Current Magnitude 0 to 999999 999 A 0 001 F060 0 2348 Fault 1 Prefault Phase C Current Angle 359 9 to 0 degrees 0 1 F002 0 2349 Fault 1 Prefault Phase A Voltage Magnitude 0 to 999999 999 V 0 001 F060 0 234B Fault 1 Prefault Phase A Voltage Angle 359 9 to 0 degrees 0 1 F002 0 234C Fault 1 Prefault Phase B Voltage Magnitude 0 to 999999 999 V 0 001 F060 0 234E Fa...

Page 512: ...001 F060 0 2575 PMU 1 Phase C Voltage Angle 180 to 180 0 01 F002 0 2576 PMU 1 Auxiliary Voltage Magnitude 0 to 999999 999 V 0 001 F060 0 2578 PMU 1 Auxiliary Voltage Angle 180 to 180 0 01 F002 0 2579 PMU 1 Positive Sequence Voltage Magnitude 0 to 999999 999 V 0 001 F060 0 257B PMU 1 Positive Sequence Voltage Angle 180 to 180 0 01 F002 0 257C PMU 1 Negative Sequence Voltage Magnitude 0 to 999999 99...

Page 513: ...ed Integers Read Only Actual Values 16 modules 26F0 IEC 61850 Received uinteger 1 0 to 4294967295 1 F003 0 26F2 IEC 61850 Received uinteger 2 0 to 4294967295 1 F003 0 26F4 IEC 61850 Received uinteger 3 0 to 4294967295 1 F003 0 26F6 IEC 61850 Received uinteger 4 0 to 4294967295 1 F003 0 26F8 IEC 61850 Received uinteger 5 0 to 4294967295 1 F003 0 26FA IEC 61850 Received uinteger 6 0 to 4294967295 1 ...

Page 514: ...Time 0 to 4294967295 1 F050 0 3046 Fault Report 12 Time 0 to 4294967295 1 F050 0 3048 Fault Report 13 Time 0 to 4294967295 1 F050 0 304A Fault Report 14 Time 0 to 4294967295 1 F050 0 304C Fault Report 15 Time 0 to 4294967295 1 F050 0 Modbus File Transfer Read Write 3100 Name of file to read F204 none Modbus File Transfer Values Read Only 3200 Character position of current block within file 0 to 42...

Page 515: ...bled 3338 Bypass Access 0 to 3 1 F628 0 Disabled 333A Serial Inactivity Timeout 1 to 9999 1 F001 1 Security Command Read Write Command 3350 Operator Logoff 0 to 1 1 F126 0 No 3351 Engineer Logoff 0 to 1 1 F126 0 No 3352 Administrator Logoff 0 to 1 1 F126 0 No 3353 Clear Security Data 0 to 1 1 F126 0 No Security Reserved Modbus Registers Read Write 3360 Address 0x3360 reserved for serial login 20 i...

Page 516: ...67 C 1 F002 0 34F7 RTD Input 8 Value 32768 to 32767 C 1 F002 0 34F8 RTD Input 9 Value 32768 to 32767 C 1 F002 0 34F9 RTD Input 10 Value 32768 to 32767 C 1 F002 0 34FA RTD Input 11 Value 32768 to 32767 C 1 F002 0 34FB RTD Input 12 Value 32768 to 32767 C 1 F002 0 34FC RTD Input 13 Value 32768 to 32767 C 1 F002 0 34FD RTD Input 14 Value 32768 to 32767 C 1 F002 0 34FE RTD Input 15 Value 32768 to 32767...

Page 517: ... F001 1813 373F RADIUS Authentication Method 1 F619 0 EAP TTLS 3740 RADIUS Vendor ID 1 to 65535 1 F001 2910 3741 Authentication Timeout 0 to 9999 sec 1 F001 10 3742 Authentication Retries 0 to 9999 1 F001 3 3743 RADIUS Authentication Shared Secret F202 none PTP Basic Configuration Read Write Setting 3750 PTP Strict Power Profile 0 to 1 1 F102 0 Disabled 3751 PTP Domain Number 0 to 255 1 F001 0 375...

Page 518: ...hase CT 1 Primary 1 to 65000 1 F001 1 3896 Remote Phase CT 1 Secondary 0 to 1 1 F123 0 1 A 3897 Remote Ground CT 1 Primary 1 to 65000 1 F001 1 3898 Remote Ground CT 1 Secondary 0 to 1 1 F123 0 1 A 3899 Remote Phase VT 1 Connection 0 to 1 1 F100 0 Wye 389A Remote Phase VT 1 Secondary 25 to 240 0 1 F001 664 389B Remote Phase VT 1 Ratio 1 to 24000 1 F060 1 389D Remote Auxiliary VT 1 Connection 0 to 6...

Page 519: ...Input 34 3A76 Repeated for Field Contact Input 35 3A81 Repeated for Field Contact Input 36 3A8C Repeated for Field Contact Input 37 3A97 Repeated for Field Contact Input 38 3AA2 Repeated for Field Contact Input 39 3AAD Repeated for Field Contact Input 40 Field Unit Shared Inputs Read Write Setting 16 modules 3B00 Field Shared Input 1 ID 0 to 65535 1 F205 SI 1 3B06 Field Shared Input 1 Unit Origin ...

Page 520: ...Setting 16 modules 3E30 Field Shared Output 1 ID 0 to 65535 1 F205 SO 1 3E36 Field Shared Output 1 Operate 0 to 4294967295 1 F300 0 3E38 Field Shared Output 1 Unit Dest 1 0 to 8 1 F256 0 None 3E39 Field Shared Output 1 Channel Dest 1 1 to 15 1 F001 1 3E3A Field Shared Output 1 Unit Dest 2 0 to 8 1 F256 0 None 3E3B Field Shared Output 1 Channel Dest 2 1 to 15 1 F001 1 3E3C Field Shared Output 1 Eve...

Page 521: ... 3FC1 Repeated for Field Unit 2 3FCA Repeated for Field Unit 3 3FD3 Repeated for Field Unit 4 3FDC Repeated for Field Unit 5 3FE5 Repeated for Field Unit 6 3FEE Repeated for Field Unit 7 3FF7 Repeated for Field Unit 8 Passwords Read Write Command 4000 Command Password Setting 0 to 4294967295 1 F202 none Passwords Read Write Setting 400A Setting Password Setting 0 to 4294967295 1 F202 none Password...

Page 522: ... to 1 1 F102 0 Disabled 409A DNP Channel 1 Port 0 to 5 1 F177 0 None 409B DNP Channel 2 Port 0 to 5 1 F177 0 None 409C DNP Address 0 to 65519 1 F001 1 409E DNP Client Addresses 2 items 0 to 4294967295 1 F003 0 40A3 TCP Port Number for the Modbus protocol 0 to 65535 1 F001 502 40A4 TCP UDP Port Number for the DNP Protocol 0 to 65535 1 F001 20000 40A5 TCP Port Number for the HTTP Web Server Protocol...

Page 523: ...ubnet Mask 0 to 4294967295 1 F003 4278190080 4109 Port 2 Gateway IP Address 0 to 4294967295 1 F003 56554497 410B PRT2 Ethernet Operation Mode 0 to 1 1 F192 1 Full Duplex 410C PRT2 Redundancy Enabled 0 to 2 1 F627 0 None 410D Port 3 IP Address 0 to 4294967295 1 F003 2130706433 410F Port 3 IP Subnet Mask 0 to 4294967295 1 F003 4278190080 4111 Port 3 Gateway IP Address 0 to 4294967295 1 F003 56554497...

Page 524: ...tart Hour 0 to 23 1 F001 2 41AE Daylight Savings Time DST Stop Month 0 to 11 1 F237 0 January 41AF Daylight Savings Time DST Stop Day 0 to 6 1 F238 0 Sunday 41B0 Daylight Savings Time DST Stop Day Instance 0 to 4 1 F239 0 First 41B1 Daylight Savings Time DST Stop Hour 0 to 23 1 F001 2 Fault Report Commands Read Write Command 41B2 Fault Reports Clear Data Command 0 to 1 1 F126 0 No Oscillography Re...

Page 525: ...ated for User Programmable LED 34 4326 Repeated for User Programmable LED 35 4329 Repeated for User Programmable LED 36 432C Repeated for User Programmable LED 37 432F Repeated for User Programmable LED 38 4332 Repeated for User Programmable LED 39 4335 Repeated for User Programmable LED 40 4338 Repeated for User Programmable LED 41 433B Repeated for User Programmable LED 42 433E Repeated for User...

Page 526: ... 6 modules 4480 Phase CT 1 Primary 1 to 65000 A 1 F001 1 4481 Phase CT 1 Secondary 0 to 1 1 F123 0 1 A 4482 Ground CT 1 Primary 1 to 65000 A 1 F001 1 4483 Ground CT 1 Secondary 0 to 1 1 F123 0 1 A 4484 Repeated for CT Bank 2 4488 Repeated for CT Bank 3 448C Repeated for CT Bank 4 4490 Repeated for CT Bank 5 4494 Repeated for CT Bank 6 VT Settings Read Write Setting 6 modules 4500 Phase VT 1 Connec...

Page 527: ...7F4 Reserved 0 to 65535 s 1 F001 0 47F5 Repeated for Breaker 2 481A Repeated for Breaker 3 483F Repeated for Breaker 4 Demand Read Write Setting 490A Demand Current Method 0 to 2 1 F139 0 Thermal Exponential 490B Demand Power Method 0 to 2 1 F139 0 Thermal Exponential 490C Demand Interval 0 to 5 1 F132 2 15 MIN 490D Demand Input 0 to 4294967295 1 F300 0 Demand Read Write Command 490F Demand Clear ...

Page 528: ...Field Data DC3 0 to 0 001 V 0 001 F002 0 4E1B Raw Field Data FCI States 2 items 0 to 1 1 F500 0 4E1D Raw Field Data SI States 0 to 1 1 F500 0 4E1E Raw Field Data SI Test States 0 to 1 1 F500 0 4E1F Raw Field Data Brick ADC Temperature 0 to 1 degree 1 F002 0 4E20 Raw Field Data Brick Transceiver Temperature 0 to 1 degree 1 F002 0 4E21 Raw Field Data Brick Transceiver Voltage 0 to 0 01 V 0 01 F001 0...

Page 529: ...7 561C Repeated for RTD Input 28 5630 Repeated for RTD Input 29 5644 Repeated for RTD Input 30 5658 Repeated for RTD Input 31 566C Repeated for RTD Input 32 5680 Repeated for RTD Input 33 5694 Repeated for RTD Input 34 56A8 Repeated for RTD Input 35 56BC Repeated for RTD Input 36 56D0 Repeated for RTD Input 37 56E4 Repeated for RTD Input 38 56F8 Repeated for RTD Input 39 570C Repeated for RTD Inpu...

Page 530: ...Overcurrent 1 Signal Source 0 to 5 1 F167 0 SRC 1 5902 Phase Time Overcurrent 1 Input 0 to 1 1 F122 0 Phasor 5903 Phase Time Overcurrent 1 Pickup 0 to 30 pu 0 001 F001 1000 5904 Phase Time Overcurrent 1 Curve 0 to 16 1 F103 0 IEEE Mod Inv 5905 Phase Time Overcurrent 1 Multiplier 0 to 600 0 01 F001 100 5906 Phase Time Overcurrent 1 Reset 0 to 1 1 F104 0 Instantaneous 5907 Phase Time Overcurrent 1 V...

Page 531: ...al Instantaneous Overcurrent Read Write Grouped Setting 8 modules 5C00 Neutral Instantaneous Overcurrent 1 Function 0 to 1 1 F102 0 Disabled 5C01 Neutral Instantaneous Overcurrent 1 Signal Source 0 to 5 1 F167 0 SRC 1 5C02 Neutral Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0 001 F001 1000 5C03 Neutral Instantaneous Overcurrent 1 Delay 0 to 600 s 0 01 F001 0 5C04 Neutral Instantaneous Overcurren...

Page 532: ...rite Setting 5F70 Setting Group for Modbus Comms 0 means group 1 0 to 5 1 F001 0 5F71 Setting Groups Block 0 to 4294967295 1 F300 0 5F73 FlexLogic Operands to Activate Groups 2 through 6 5 items 0 to 4294967295 1 F300 0 5F7D Setting Group Function 0 to 1 1 F102 0 Disabled 5F7E Setting Group Events 0 to 1 1 F102 0 Disabled Setting Groups Read Only 5F7F Current Setting Group 0 to 5 1 F001 0 Setting ...

Page 533: ...o 4294967295 1 F300 0 686D Autoreclose 3P TD Initiate 0 to 4294967295 1 F300 0 686F Autoreclose Multi Phase Fault 0 to 4294967295 1 F300 0 6871 Autoreclose Breaker 1 Pole Open 0 to 4294967295 1 F300 0 6873 Autoreclose Breaker 3 Pole Open 0 to 4294967295 1 F300 0 6875 Autoreclose 3 Pole Dead Time 1 0 to 655 35 s 0 01 F001 50 6876 Autoreclose 3 Pole Dead Time 2 0 to 655 35 s 0 01 F001 120 6877 Autor...

Page 534: ...ltage 1 Reset Delay 0 to 600 s 0 01 F001 100 7045 Phase Overvoltage 1 Block 0 to 4294967295 1 F300 0 7047 Phase Overvoltage 1 Target 0 to 2 1 F109 0 Self reset 7048 Phase Overvoltage 1 Events 0 to 1 1 F102 0 Disabled 7049 Repeated for Phase Overvoltage 2 7052 Repeated for Phase Overvoltage 3 Breaker Arcing Current Settings Read Write Setting 4 modules 7290 Breaker 1 Arcing Amp Function 0 to 1 1 F1...

Page 535: ... Thermal Protection 1 Base Current 0 2 to 3 pu 0 01 F001 80 778B Thermal Protection 1 K Factor 1 to 1 2 0 05 F001 110 778C Thermal Protection 1 Trip Time Constant 0 to 1000 min 1 F001 45 778D Thermal Protection 1 Reset Time Constant 0 to 1000 min 1 F001 45 778E Thermal Protection 1 Minimum Reset Time 0 to 1000 min 1 F001 20 778F Thermal Protection 1 Reset 0 to 4294967295 1 F300 0 7791 Thermal Prot...

Page 536: ...button 1 On Text F202 none 7B75 User Programmable Pushbutton 1 Off Text F202 none 7B7F User Programmable Pushbutton 1 Drop Out Time 0 to 60 s 0 05 F001 0 7B80 User Programmable Pushbutton 1 Target 0 to 2 1 F109 0 Self reset 7B81 User Programmable Pushbutton 1 Events 0 to 1 1 F102 0 Disabled 7B82 User Programmable Pushbutton 1 LED Operand 0 to 4294967295 1 F300 0 7B84 User Programmable Pushbutton 1...

Page 537: ...d for Auxiliary Undervoltage 2 Auxiliary Overvoltage Read Write Grouped Setting 2 modules 7FA0 Auxiliary Overvoltage 1 Function 0 to 1 1 F102 0 Disabled 7FA1 Auxiliary Overvoltage 1 Signal Source 0 to 5 1 F167 0 SRC 1 7FA2 Auxiliary Overvoltage 1 Pickup 0 to 3 pu 0 001 F001 300 7FA3 Auxiliary Overvoltage 1 Pickup Delay 0 to 600 s 0 01 F001 100 7FA4 Auxiliary Overvoltage 1 Reset Delay 0 to 600 s 0 ...

Page 538: ...ailure 1 Use Timer 1 0 to 1 1 F126 1 Yes 860C Breaker Failure 1 Timer 1 Pickup 0 to 65 535 s 0 001 F001 0 860D Breaker Failure 1 Use Timer 2 0 to 1 1 F126 1 Yes 860E Breaker Failure 1 Timer 2 Pickup 0 to 65 535 s 0 001 F001 0 860F Breaker Failure 1 Use Timer 3 0 to 1 1 F126 1 Yes 8610 Breaker Failure 1 Timer 3 Pickup 0 to 65 535 s 0 001 F001 0 8611 Breaker Failure 1 Breaker Status 1 Phase A 3P 0 t...

Page 539: ... Repeated for Digital Element 13 8B1E Repeated for Digital Element 14 8B34 Repeated for Digital Element 15 8B4A Repeated for Digital Element 16 8B60 Repeated for Digital Element 17 8B76 Repeated for Digital Element 18 8B8C Repeated for Digital Element 19 8BA2 Repeated for Digital Element 20 8BB8 Repeated for Digital Element 21 8BCE Repeated for Digital Element 22 8BE4 Repeated for Digital Element ...

Page 540: ...IGNED 9008 FlexElement 1 Direction 0 to 1 1 F517 0 OVER 9009 FlexElement 1 Hysteresis 0 1 to 50 0 1 F001 30 900A FlexElement 1 Pickup 90 to 90 pu 0 001 F004 1000 900C FlexElement 1 DeltaT Units 0 to 2 1 F518 0 Milliseconds 900D FlexElement 1 DeltaT 20 to 86400 1 F003 20 900F FlexElement 1 Pickup Delay 0 to 65 535 s 0 001 F001 0 9010 FlexElement 1 Reset Delay 0 to 65 535 s 0 001 F001 0 9011 FlexEle...

Page 541: ...d for DCmA Output 11 93A2 Repeated for DCmA Output 12 93A8 Repeated for DCmA Output 13 93AE Repeated for DCmA Output 14 93B4 Repeated for DCmA Output 15 93BA Repeated for DCmA Output 16 93C0 Repeated for DCmA Output 17 93C6 Repeated for DCmA Output 18 93CC Repeated for DCmA Output 19 93D2 Repeated for DCmA Output 20 93D8 Repeated for DCmA Output 21 93DE Repeated for DCmA Output 22 93E4 Repeated fo...

Page 542: ...r 10 98BE Repeated for IEC61850 GOOSE uinteger 11 98C1 Repeated for IEC61850 GOOSE uinteger 12 98C4 Repeated for IEC61850 GOOSE uinteger 13 98C7 Repeated for IEC61850 GOOSE uinteger 14 98CA Repeated for IEC61850 GOOSE uinteger 15 98CD Repeated for IEC61850 GOOSE uinteger 16 FlexElement Actual Values Read Only 8 modules 9900 FlexElement 1 Actual 2147483 647 to 2147483 647 0 001 F004 0 9902 FlexElem...

Page 543: ... 1 F134 2 n a 9AAF Teleprotection Channel 1 Input States 0 to 1 1 F500 0 9AB0 Teleprotection Channel 2 Input States 0 to 1 1 F500 0 9AC0 Teleprotection Input 1 States 1 per register 16 items 0 to 1 1 F108 0 Off 9AD0 Teleprotection Input 2 States 1 per register 16 items 0 to 1 1 F108 0 Off VT Fuse Failure Read Write Setting 4 modules A09A VT Fuse Failure1 Function 0 to 1 1 F102 0 Disabled A09B VT F...

Page 544: ... Digital Counter 4 A3A0 Repeated for Digital Counter 5 A3C8 Repeated for Digital Counter 6 A3F0 Repeated for Digital Counter 7 A418 Repeated for Digital Counter 8 FlexCurves C and D Read Write Setting A600 FlexCurve C 120 items 0 to 65535 ms 1 F011 0 A680 FlexCurve D 120 items 0 to 65535 ms 1 F011 0 Non Volatile Latches Read Write Setting 16 modules A700 Non Volatile Latch 1 Function 0 to 1 1 F102...

Page 545: ...og Input 20 AA8C Repeated for IEC 61850 GOOSE Analog Input 21 AA93 Repeated for IEC 61850 GOOSE Analog Input 22 AA9A Repeated for IEC 61850 GOOSE Analog Input 23 AAA1 Repeated for IEC 61850 GOOSE Analog Input 24 AAA8 Repeated for IEC 61850 GOOSE Analog Input 25 AAAF Repeated for IEC 61850 GOOSE Analog Input 26 AAB6 Repeated for IEC 61850 GOOSE Analog Input 27 AABD Repeated for IEC 61850 GOOSE Anal...

Page 546: ...1 Deadband 0 001 to 100 0 001 F003 100000 AF13 IEC 61850 GGIO4 Analog Input 1 Minimum 1000000000000 to 1000000000000 0 001 F060 0 AF15 IEC 61850 GGIO4 Analog Input 1 Maximum 1000000000000 to 1000000000000 0 001 F060 1000000 AF17 Repeated for IEC 61850 GGIO4 Analog Input 2 AF1E Repeated for IEC 61850 GGIO4 Analog Input 3 AF25 Repeated for IEC 61850 GGIO4 Analog Input 4 AF2C Repeated for IEC 61850 G...

Page 547: ... to 100 0 001 F003 10000 B0C6 IEC 61850 MMXU TotPF Deadband 1 0 001 to 100 0 001 F003 10000 B0C8 IEC 61850 MMXU Hz Deadband 1 0 001 to 100 0 001 F003 10000 B0CA IEC 61850 MMXU PPV phsAB Deadband 1 0 001 to 100 0 001 F003 10000 B0CC IEC 61850 MMXU PPV phsBC Deadband 1 0 001 to 100 0 001 F003 10000 B0CE IEC 61850 MMXU PPV phsCA Deadband 1 0 001 to 100 0 001 F003 10000 B0D0 IEC 61850 MMXU PhV phsA De...

Page 548: ...3A Repeated for Received Analog 22 B23C Repeated for Received Analog 23 B23E Repeated for Received Analog 24 B240 Repeated for Received Analog 25 B242 Repeated for Received Analog 26 B244 Repeated for Received Analog 27 B246 Repeated for Received Analog 28 B248 Repeated for Received Analog 29 B24A Repeated for Received Analog 30 B24C Repeated for Received Analog 31 B24E Repeated for Received Analo...

Page 549: ...OSE ETYPE APPID 0 to 16383 1 F001 0 B5C8 IEC 61850 Configurable GOOSE ConfRev Configuration Revision 1 to 4294967295 1 F003 1 B5CA IEC 61850 Configurable GOOSE Retransmission Curve 0 to 3 1 F611 3 Relaxed B5CB Configurable GOOSE Dataset Items for Transmission 64 items 0 to 1008 1 F616 0 None B60B Repeated for module number 2 B676 Repeated for module number 3 B6E1 Repeated for module number 4 B74C ...

Page 550: ...t 23 BBB8 Repeated for Contact Input 24 BBC0 Repeated for Contact Input 25 BBC8 Repeated for Contact Input 26 BBD0 Repeated for Contact Input 27 BBD8 Repeated for Contact Input 28 BBE0 Repeated for Contact Input 29 BBE8 Repeated for Contact Input 30 BBF0 Repeated for Contact Input 31 BBF8 Repeated for Contact Input 32 BC00 Repeated for Contact Input 33 BC08 Repeated for Contact Input 34 BC10 Repea...

Page 551: ...D78 Repeated for Contact Input 80 BD80 Repeated for Contact Input 81 BD88 Repeated for Contact Input 82 BD90 Repeated for Contact Input 83 BD98 Repeated for Contact Input 84 BDA0 Repeated for Contact Input 85 BDA8 Repeated for Contact Input 86 BDB0 Repeated for Contact Input 87 BDB8 Repeated for Contact Input 88 BDC0 Repeated for Contact Input 89 BDC8 Repeated for Contact Input 90 BDD0 Repeated fo...

Page 552: ...for Virtual Input 29 BF8C Repeated for Virtual Input 30 BF98 Repeated for Virtual Input 31 BFA4 Repeated for Virtual Input 32 BFB0 Repeated for Virtual Input 33 BFBC Repeated for Virtual Input 34 BFC8 Repeated for Virtual Input 35 BFD4 Repeated for Virtual Input 36 BFE0 Repeated for Virtual Input 37 BFEC Repeated for Virtual Input 38 BFF8 Repeated for Virtual Input 39 C004 Repeated for Virtual Inp...

Page 553: ...d for Virtual Output 16 C1B0 Repeated for Virtual Output 17 C1B8 Repeated for Virtual Output 18 C1C0 Repeated for Virtual Output 19 C1C8 Repeated for Virtual Output 20 C1D0 Repeated for Virtual Output 21 C1D8 Repeated for Virtual Output 22 C1E0 Repeated for Virtual Output 23 C1E8 Repeated for Virtual Output 24 C1F0 Repeated for Virtual Output 25 C1F8 Repeated for Virtual Output 26 C200 Repeated fo...

Page 554: ...Output 70 C360 Repeated for Virtual Output 71 C368 Repeated for Virtual Output 72 C370 Repeated for Virtual Output 73 C378 Repeated for Virtual Output 74 C380 Repeated for Virtual Output 75 C388 Repeated for Virtual Output 76 C390 Repeated for Virtual Output 77 C398 Repeated for Virtual Output 78 C3A0 Repeated for Virtual Output 79 C3A8 Repeated for Virtual Output 80 C3B0 Repeated for Virtual Outp...

Page 555: ...5 1 F300 0 C470 Clear Platform Direct Input Output Statistics Operand 0 to 4294967295 1 F300 0 C472 Reserved 13 items F001 0 Platform Direct Outputs Read Write Setting 32 modules C600 Direct Output 1 Operand 0 to 4294967295 1 F300 0 C602 Direct Output 1 Events 0 to 1 1 F102 0 Disabled C603 Repeated for Direct Output 2 C606 Repeated for Direct Output 3 C609 Repeated for Direct Output 4 C60C Repeate...

Page 556: ...1 F126 0 No C884 Platform Direct I O Crossover Function 0 to 1 1 F102 0 Disabled Direct Input Output Commands Read Write Command C888 Direct Input Output Clear Counters Command 0 to 1 1 F126 0 No Direct inputs Read Write Setting 32 modules C890 Direct Input 1 Device Number 0 to 16 1 F001 0 C891 Direct Input 1 Number 0 to 96 1 F001 0 C892 Direct Input 1 Default State 0 to 3 1 F086 0 Off C893 Direct...

Page 557: ...10000 1 F001 600 CAE2 Direct Input Output Ch 1 Unreturned Messages Alarm Threshold 1 to 1000 1 F001 10 CAE3 Direct Input Output Ch 1 Unreturned Messages Alarm Events 0 to 1 1 F102 0 Disabled CAE4 Reserved 4 items 1 to 1000 1 F001 10 CAE8 Direct Input Output Ch 2 Unreturned Messages Alarm Function 0 to 1 1 F102 0 Disabled CAE9 Direct Input Output Ch 2 Unreturned Messages Alarm Msg Count 100 to 1000...

Page 558: ... Repeated for Remote Input 19 D05E Repeated for Remote Input 20 D068 Repeated for Remote Input 21 D072 Repeated for Remote Input 22 D07C Repeated for Remote Input 23 D086 Repeated for Remote Input 24 D090 Repeated for Remote Input 25 D09A Repeated for Remote Input 26 D0A4 Repeated for Remote Input 27 D0AE Repeated for Remote Input 28 D0B8 Repeated for Remote Input 29 D0C2 Repeated for Remote Input...

Page 559: ...ated for Remote Output 2 D2A8 Repeated for Remote Output 3 D2AC Repeated for Remote Output 4 D2B0 Repeated for Remote Output 5 D2B4 Repeated for Remote Output 6 D2B8 Repeated for Remote Output 7 D2BC Repeated for Remote Output 8 D2C0 Repeated for Remote Output 9 D2C4 Repeated for Remote Output 10 D2C8 Repeated for Remote Output 11 D2CC Repeated for Remote Output 12 D2D0 Repeated for Remote Output ...

Page 560: ...Model Value 0 to 2 1 F001 1 D339 IEC 61850 GGIO2 CF SPCSO26 ctlModel Value 0 to 2 1 F001 1 D33A IEC 61850 GGIO2 CF SPCSO27 ctlModel Value 0 to 2 1 F001 1 D33B IEC 61850 GGIO2 CF SPCSO28 ctlModel Value 0 to 2 1 F001 1 D33C IEC 61850 GGIO2 CF SPCSO29 ctlModel Value 0 to 2 1 F001 1 D33D IEC 61850 GGIO2 CF SPCSO30 ctlModel Value 0 to 2 1 F001 1 D33E IEC 61850 GGIO2 CF SPCSO31 ctlModel Value 0 to 2 1 F...

Page 561: ...mote Device 8 D380 Repeated for Remote Device 9 D384 Repeated for Remote Device 10 D388 Repeated for Remote Device 11 D38C Repeated for Remote Device 12 D390 Repeated for Remote Device 13 D394 Repeated for Remote Device 14 D398 Repeated for Remote Device 15 D39C Repeated for Remote Device 16 Contact Outputs Read Write Setting 64 modules D3E0 Contact Output 1 Name F205 Cont Op 1 D3E6 Contact Output...

Page 562: ...Contact Output 43 D665 Repeated for Contact Output 44 D674 Repeated for Contact Output 45 D683 Repeated for Contact Output 46 D692 Repeated for Contact Output 47 D6A1 Repeated for Contact Output 48 D6B0 Repeated for Contact Output 49 D6BF Repeated for Contact Output 50 D6CE Repeated for Contact Output 51 D6DD Repeated for Contact Output 52 D6EC Repeated for Contact Output 53 D6FB Repeated for Cont...

Page 563: ... 1 V1 Source 0 to 5 1 F167 0 SRC 1 DC72 Synchrocheck 1 V2 Source 0 to 5 1 F167 1 SRC 2 DC73 Synchrocheck 1 Maximum Voltage Difference 0 to 400000 V 1 F060 10000 DC75 Synchrocheck 1 Maximum Angle Difference 0 to 100 degrees 1 F001 30 DC76 Synchrocheck 1 Maximum Frequency Difference 0 to 2 Hz 0 01 F001 100 DC77 Synchrocheck 1 Dead Source Select 0 to 5 1 F176 1 LV1 and DV2 DC78 Synchrocheck 1 Dead V1...

Page 564: ...S 1 to 4 1 F001 1 E8D6 PMU Aggregator 1 Port 1 to 3 1 F001 1 E8D7 PMU Aggregator 1 Reserved 3 items 0 to 1 1 F001 0 E8D8 Repeated for PMU Aggregator 2 Phasor Measurement Unit Aggregator Control Block Read Write Setting 2 modules E9C8 PMU Aggregator 1 Control Block SvEna 0 to 4294967295 1 F300 0 E9CA PMU Aggregator 1 Control Block Client Control 0 to 4294967295 1 F300 0 E9CC PMU Aggregator 1 CB SvE...

Page 565: ... 01 F001 4900 EAEE PMU 1 Frequency Trigger High Frequency 20 to 70 Hz 0 01 F001 6100 EAEF PMU 1 Frequency Trigger Pickup Time 0 to 600 s 0 01 F001 10 EAF0 PMU 1 Frequency Trigger Dropout Time 0 to 600 s 0 01 F001 100 EAF1 PMU 1 Frequency Trigger Block 3 items 0 to 4294967295 1 F300 0 EAF7 PMU 1 Frequency Trigger Target 0 to 2 1 F109 0 Self reset EAF8 PMU 1 Frequency Trigger Events 0 to 1 1 F102 0 ...

Page 566: ...1000 EBEA PMU 1 Ig Calibration Angle 5 to 5 0 05 F002 0 EBEB PMU 1 Ig Calibration Magnitude 95 to 105 0 1 F002 1000 EBEC PMU 1 Sequence Voltage Shift Angle 180 to 180 30 F002 0 EBED PMU 1 Sequence Current Shift Angle 180 to 180 30 F002 0 EBEE Repeated for PMU 2 Phasor Measurement Unit Network Reporting Configuration Read Write Setting EC48 PMU Network Reporting Function 0 to 1 1 F102 0 Disabled EC...

Page 567: ...UR_UINT32 TIME and DATE UNSIGNED 32 BIT INTEGER Gives the current time in seconds elapsed since 00 00 00 January 1 1970 F051 UR_UINT32 DATE in SR format alternate format for F050 First 16 bits are Month Day MM DD xxxx Month 1 January 2 February 12 December Day 1 to 31 in steps of 1 Last 16 bits are Year xx xx YYYY 1970 to 2106 in steps of 1 F052 UR_UINT32 TIME in SR format alternate format for F05...

Page 568: ...Automatic Overwrite 1 Protected F122 ENUMERATION ELEMENT INPUT SIGNAL TYPE 0 Phasor 1 RMS F123 ENUMERATION CT SECONDARY 0 1 A 1 5 A F124 ENUMERATION LIST OF ELEMENTS Bitmask Curve shape Bitmask Curve shape 0 IEEE Mod Inv 9 IAC Inverse 1 IEEE Very Inv 10 IAC Short Inv 2 IEEE Ext Inv 11 I2t 3 IEC Curve A 12 Definite Time 4 IEC Curve B 13 FlexCurve A 5 IEC Curve C 14 FlexCurve B 6 IEC Short Inv 15 Fl...

Page 569: ...er Failure 2 288 Breaker Arcing Current 1 289 Breaker Arcing Current 2 290 Breaker Arcing Current 3 291 Breaker Arcing Current 4 294 Breaker 1 Flashover 295 Breaker 2 Flashover 311 Phasor measurement unit one shot 312 Synchrocheck 1 313 Synchrocheck 2 314 Synchrocheck 3 315 Synchrocheck 4 Bitmask Element 336 Setting Group 337 Reset 363 Open Pole Detector 375 Autoreclose single pole three pole 388 ...

Page 570: ...Phasor Measurement Unit 1 Voltage 747 Phasor Measurement Unit 2 Voltage 752 Phasor Measurement Unit 1 Current 753 Phasor Measurement Unit 2 Current 758 Phasor Measurement Unit 1 Power 759 Phasor Measurement Unit 2 Power 764 PMU 1 Rate of Change of Frequency 765 PMU 2 Rate of Change of Frequency 823 Phasor Measurement Unit 1 824 Phasor Measurement Unit 2 842 Trip Bus 1 Bitmask Element 843 Trip Bus ...

Page 571: ...shbutton 5 905 User Programmable Pushbutton 6 906 User Programmable Pushbutton 7 907 User Programmable Pushbutton 8 908 User Programmable Pushbutton 9 909 User Programmable Pushbutton 10 910 User Programmable Pushbutton 11 911 User Programmable Pushbutton 12 912 User Programmable Pushbutton 13 913 User Programmable Pushbutton 14 914 User Programmable Pushbutton 15 915 User Programmable Pushbutton ...

Page 572: ... Module Failure 05 79 Module Failure 06 80 Module Failure 07 81 Module Failure 08 82 Module Failure 09 83 Incompatible H W 84 Module Failure 10 85 Module Failure 11 86 Module Failure 12 87 High ENET Traffic 89 Relay Restart 90 FGM Failure 91 FGM Failure 92 FGM Failure 93 FGM Failure 94 FGM Failure 95 FGM Error 96 Maintenance Alert Bitmask Error 97 PHY Monitor 98 Storage Media Alarm 99 Wrong Transc...

Page 573: ...erSt 4 2 DNA 2 37 UserSt 5 3 DNA 3 38 UserSt 6 4 DNA 4 39 UserSt 7 5 DNA 5 40 UserSt 8 6 DNA 6 41 UserSt 9 7 DNA 7 42 UserSt 10 8 DNA 8 43 UserSt 11 9 DNA 9 44 UserSt 12 10 DNA 10 45 UserSt 13 11 DNA 11 46 UserSt 14 12 DNA 12 47 UserSt 15 13 DNA 13 48 UserSt 16 14 DNA 14 49 UserSt 17 15 DNA 15 50 UserSt 18 16 DNA 16 51 UserSt 19 17 DNA 17 52 UserSt 20 18 DNA 18 53 UserSt 21 19 DNA 19 54 UserSt 22 ...

Page 574: ...ion 0 Off 1 8 samples cycle 2 16 samples cycle 3 32 samples cycle 4 64 samples cycle Value IEC 61850 dataset 0 Off 1 GooseIn 1 2 GooseIn 2 3 GooseIn 3 4 GooseIn 4 5 GooseIn 5 6 GooseIn 6 7 GooseIn 7 8 GooseIn 8 9 GooseIn 9 10 GooseIn 10 11 GooseIn 11 12 GooseIn 12 13 GooseIn 13 14 GooseIn 14 15 GooseIn 15 16 GooseIn 16 Bitmask Keypress Bitmask Keypress 0 No key use between real keys 23 Reset 24 Us...

Page 575: ... MX PhV phsC cVal ang f 274 MMXU1 MX A phsA cVal mag f 275 MMXU1 MX A phsA cVal ang f 276 MMXU1 MX A phsB cVal mag f 277 MMXU1 MX A phsB cVal ang f 278 MMXU1 MX A phsC cVal mag f 279 MMXU1 MX A phsC cVal ang f 280 MMXU1 MX A neut cVal mag f 281 MMXU1 MX A neut cVal ang f 282 MMXU1 MX W phsA cVal mag f 283 MMXU1 MX W phsB cVal mag f 284 MMXU1 MX W phsC cVal mag f 285 MMXU1 MX VAr phsA cVal mag f 28...

Page 576: ...MX PF phsB cVal mag f 367 MMXU3 MX PF phsC cVal mag f 368 MMXU4 MX TotW mag f 369 MMXU4 MX TotVAr mag f Value IEC 61850 Tx dataset item 370 MMXU4 MX TotVA mag f 371 MMXU4 MX TotPF mag f 372 MMXU4 MX Hz mag f 373 MMXU4 MX PPV phsAB cVal mag f 374 MMXU4 MX PPV phsAB cVal ang f 375 MMXU4 MX PPV phsBC cVal mag f 376 MMXU4 MX PPV phsBC cVal ang f 377 MMXU4 MX PPV phsCA cVal mag f 378 MMXU4 MX PPV phsCA...

Page 577: ...8 MMXU6 MX W phsB cVal mag f 469 MMXU6 MX W phsC cVal mag f 470 MMXU6 MX VAr phsA cVal mag f 471 MMXU6 MX VAr phsB cVal mag f 472 MMXU6 MX VAr phsC cVal mag f 473 MMXU6 MX VA phsA cVal mag f 474 MMXU6 MX VA phsB cVal mag f 475 MMXU6 MX VA phsC cVal mag f Value IEC 61850 Tx dataset item 476 MMXU6 MX PF phsA cVal mag f 477 MMXU6 MX PF phsB cVal mag f 478 MMXU6 MX PF phsC cVal mag f 479 GGIO4 MX AnIn...

Page 578: ...7 GGIO3 MX AnIn19 mag f 148 GGIO3 MX AnIn20 mag f 149 GGIO3 MX AnIn21 mag f 150 GGIO3 MX AnIn22 mag f 151 GGIO3 MX AnIn23 mag f 152 GGIO3 MX AnIn24 mag f Value IEC 61850 Tx dataset item 153 GGIO3 MX AnIn25 mag f 154 GGIO3 MX AnIn26 mag f 155 GGIO3 MX AnIn27 mag f 156 GGIO3 MX AnIn28 mag f 157 GGIO3 MX AnIn29 mag f 158 GGIO3 MX AnIn30 mag f 159 GGIO3 MX AnIn31 mag f 160 GGIO3 MX AnIn32 mag f 161 GG...

Page 579: ...ruary 2 March 3 April 4 May 5 June 6 July 7 August 8 September 9 October 10 November 11 December Value Day 0 Sunday 1 Monday 2 Tuesday 3 Wednesday 4 Thursday 5 Friday 6 Saturday Value Instance 0 First 1 Second 2 Third 3 Fourth 4 Last Value Instance 0 Disabled 1 Isolated 2 Forcible Value Month Value Description 0 5 5V 1 1 1mA 2 0 1mA 3 0 1mA 4 0 5mA 5 0 10mA 6 0 20mA 7 4 20mA 8 potentiometer 9 tap ...

Page 580: ...n be a total 65535 BASE type ele ments 131071 protection element IDs and 16383 element states There can be a total of 65535 descriptors of each type 0 Off 0 This is boolean FALSE value 1 On 1 This is boolean TRUE value 2 CONTACT INPUTS 1 to 96 3 CONTACT INPUTS OFF 1 to 96 4 VIRTUAL INPUTS 1 to 32 6 VIRTUAL OUTPUTS 1 to 64 8 CONTACT OUTPUTS 10 CONTACT OUTPUTS VOLTAGE DETECTED 1 to 64 11 CONTACT OUT...

Page 581: ...atus with bit 0 representing the top LED and bit 7 the bottom LED A bit value of 1 indicates the LED is on 0 indicates the LED is off 0 Off 1 On F502 BITFIELD ELEMENT OPERATE STATES Each bit contains the operate state for an element See the F124 format code for a list of element IDs The operate bit for element ID X is bit X mod 16 in register X 16 F515 ENUMERATION ELEMENT INPUT MODE 0 Signed 1 Abs...

Page 582: ...NUMERATION COM2 PORT USAGE F605 ENUMERATION REMOTE DOUBLE POINT STATUS INPUT STATUS Value Keypress Value Keypress Value Keypress 0 None 15 3 33 User PB 3 1 Menu 16 Enter 34 User PB 4 2 Message Up 17 Message Down 35 User PB 5 3 7 18 0 36 User PB 6 4 8 19 Decimal 37 User PB 7 5 9 20 38 User PB 8 6 Help 21 Value Up 39 User PB 9 7 Message Left 22 Value Down 40 User PB 10 8 4 23 Reset 41 User PB 11 9 5...

Page 583: ...Str general 14 PDIS3 ST Op general 15 PDIS4 ST Str general 16 PDIS4 ST Op general 17 PDIS5 ST Str general 18 PDIS5 ST Op general 19 PDIS6 ST Str general 20 PDIS6 ST Op general 21 PDIS7 ST Str general 22 PDIS7 ST Op general 23 PDIS8 ST Str general 24 PDIS8 ST Op general 25 PDIS9 ST Str general 26 PDIS9 ST Op general 27 PDIS10 ST Str general 28 PDIS10 ST Op general 29 PIOC1 ST Str general 30 PIOC1 S...

Page 584: ...neral 118 PIOC45 ST Op general 119 PIOC46 ST Str general 120 PIOC46 ST Op general Enumeration IEC 61850 report dataset items 121 PIOC47 ST Str general 122 PIOC47 ST Op general 123 PIOC48 ST Str general 124 PIOC48 ST Op general 125 PIOC49 ST Str general 126 PIOC49 ST Op general 127 PIOC50 ST Str general 128 PIOC50 ST Op general 129 PIOC51 ST Str general 130 PIOC51 ST Op general 131 PIOC52 ST Str ge...

Page 585: ... Op general 223 PTOV2 ST Str general 224 PTOV2 ST Op general 225 PTOV3 ST Str general 226 PTOV3 ST Op general Enumeration IEC 61850 report dataset items 227 PTOV4 ST Str general 228 PTOV4 ST Op general 229 PTOV5 ST Str general 230 PTOV5 ST Op general 231 PTOV6 ST Str general 232 PTOV6 ST Op general 233 PTOV7 ST Str general 234 PTOV7 ST Op general 235 PTOV8 ST Str general 236 PTOV8 ST Op general 23...

Page 586: ...27 RFLO1 MX FltDiskm mag f 328 RFLO2 MX FltDiskm mag f 329 RFLO3 MX FltDiskm mag f 330 RFLO4 MX FltDiskm mag f 331 RFLO5 MX FltDiskm mag f 332 RPSB1 ST Str general Enumeration IEC 61850 report dataset items 333 RPSB1 ST Op general 334 RPSB1 ST BlkZn stVal 335 RREC1 ST Op general 336 RREC1 ST AutoRecSt stVal 337 RREC2 ST Op general 338 RREC2 ST AutoRecSt stVal 339 RREC3 ST Op general 340 RREC3 ST A...

Page 587: ...9 stVal 436 GGIO1 ST Ind30 stVal 437 GGIO1 ST Ind31 stVal 438 GGIO1 ST Ind32 stVal Enumeration IEC 61850 report dataset items 439 GGIO1 ST Ind33 stVal 440 GGIO1 ST Ind34 stVal 441 GGIO1 ST Ind35 stVal 442 GGIO1 ST Ind36 stVal 443 GGIO1 ST Ind37 stVal 444 GGIO1 ST Ind38 stVal 445 GGIO1 ST Ind39 stVal 446 GGIO1 ST Ind40 stVal 447 GGIO1 ST Ind41 stVal 448 GGIO1 ST Ind42 stVal 449 GGIO1 ST Ind43 stVal...

Page 588: ...tems 545 MMXU1 MX PPV phsCA cVal ang f 546 MMXU1 MX PhV phsA cVal mag f 547 MMXU1 MX PhV phsA cVal ang f 548 MMXU1 MX PhV phsB cVal mag f 549 MMXU1 MX PhV phsB cVal ang f 550 MMXU1 MX PhV phsC cVal mag f 551 MMXU1 MX PhV phsC cVal ang f 552 MMXU1 MX A phsA cVal mag f 553 MMXU1 MX A phsA cVal ang f 554 MMXU1 MX A phsB cVal mag f 555 MMXU1 MX A phsB cVal ang f 556 MMXU1 MX A phsC cVal mag f 557 MMXU...

Page 589: ...648 MMXU4 MX TotVA mag f 649 MMXU4 MX TotPF mag f 650 MMXU4 MX Hz mag f Enumeration IEC 61850 report dataset items 651 MMXU4 MX PPV phsAB cVal mag f 652 MMXU4 MX PPV phsAB cVal ang f 653 MMXU4 MX PPV phsBC cVal mag f 654 MMXU4 MX PPV phsBC cVal ang f 655 MMXU4 MX PPV phsCA cVal mag f 656 MMXU4 MX PPV phsCA cVal ang f 657 MMXU4 MX PhV phsA cVal mag f 658 MMXU4 MX PhV phsA cVal ang f 659 MMXU4 MX Ph...

Page 590: ... phsA cVal mag f 749 MMXU6 MX VAr phsB cVal mag f 750 MMXU6 MX VAr phsC cVal mag f 751 MMXU6 MX VA phsA cVal mag f 752 MMXU6 MX VA phsB cVal mag f 753 MMXU6 MX VA phsC cVal mag f 754 MMXU6 MX PF phsA cVal mag f 755 MMXU6 MX PF phsB cVal mag f 756 MMXU6 MX PF phsC cVal mag f Enumeration IEC 61850 report dataset items 757 GGIO4 MX AnIn1 mag f 758 GGIO4 MX AnIn2 mag f 759 GGIO4 MX AnIn3 mag f 760 GGI...

Page 591: ...ST Ind2 q 4 GGIO1 ST Ind2 stVal 5 GGIO1 ST Ind3 q 6 GGIO1 ST Ind3 stVal 7 GGIO1 ST Ind4 q 8 GGIO1 ST Ind4 stVal Enumeration IEC 61850 report dataset items 9 GGIO1 ST Ind5 q 10 GGIO1 ST Ind5 stVal 11 GGIO1 ST Ind6 q 12 GGIO1 ST Ind6 stVal 13 GGIO1 ST Ind7 q 14 GGIO1 ST Ind7 stVal 15 GGIO1 ST Ind8 q 16 GGIO1 ST Ind8 stVal 17 GGIO1 ST Ind9 q 18 GGIO1 ST Ind9 stVal 19 GGIO1 ST Ind10 q 20 GGIO1 ST Ind1...

Page 592: ...111 GGIO1 ST Ind56 q 112 GGIO1 ST Ind56 stVal 113 GGIO1 ST Ind57 q 114 GGIO1 ST Ind57 stVal Enumeration GOOSE dataset items 115 GGIO1 ST Ind58 q 116 GGIO1 ST Ind58 stVal 117 GGIO1 ST Ind59 q 118 GGIO1 ST Ind59 stVal 119 GGIO1 ST Ind60 q 120 GGIO1 ST Ind60 stVal 121 GGIO1 ST Ind61 q 122 GGIO1 ST Ind61 stVal 123 GGIO1 ST Ind62 q 124 GGIO1 ST Ind62 stVal 125 GGIO1 ST Ind63 q 126 GGIO1 ST Ind63 stVal ...

Page 593: ...T Ind110 q 220 GGIO1 ST Ind110 stVal Enumeration GOOSE dataset items 221 GGIO1 ST Ind111 q 222 GGIO1 ST Ind111 stVal 223 GGIO1 ST Ind112 q 224 GGIO1 ST Ind112 stVal 225 GGIO1 ST Ind113 q 226 GGIO1 ST Ind113 stVal 227 GGIO1 ST Ind114 q 228 GGIO1 ST Ind114 stVal 229 GGIO1 ST Ind115 q 230 GGIO1 ST Ind115 stVal 231 GGIO1 ST Ind116 q 232 GGIO1 ST Ind116 stVal 233 GGIO1 ST Ind117 q 234 GGIO1 ST Ind117 s...

Page 594: ... VAr phsB cVal mag f 324 MMXU2 MX VAr phsC cVal mag f 325 MMXU2 MX VA phsA cVal mag f 326 MMXU2 MX VA phsB cVal mag f Enumeration GOOSE dataset items 327 MMXU2 MX VA phsC cVal mag f 328 MMXU2 MX PF phsA cVal mag f 329 MMXU2 MX PF phsB cVal mag f 330 MMXU2 MX PF phsC cVal mag f 331 MMXU3 MX TotW mag f 332 MMXU3 MX TotVAr mag f 333 MMXU3 MX TotVA mag f 334 MMXU3 MX TotPF mag f 335 MMXU3 MX Hz mag f ...

Page 595: ...ag f 429 MMXU5 MX A neut cVal ang f 430 MMXU5 MX W phsA cVal mag f 431 MMXU5 MX W phsB cVal mag f 432 MMXU5 MX W phsC cVal mag f Enumeration GOOSE dataset items 433 MMXU5 MX VAr phsA cVal mag f 434 MMXU5 MX VAr phsB cVal mag f 435 MMXU5 MX VAr phsC cVal mag f 436 MMXU5 MX VA phsA cVal mag f 437 MMXU5 MX VA phsB cVal mag f 438 MMXU5 MX VA phsC cVal mag f 439 MMXU5 MX PF phsA cVal mag f 440 MMXU5 MX...

Page 596: ... 534 GGIO5 ST UIntIn12 stVal 535 GGIO5 ST UIntIn13 q 536 GGIO5 ST UIntIn13 stVal 537 GGIO5 ST UIntIn14 q 538 GGIO5 ST UIntIn14 stVal Enumeration GOOSE dataset items 539 GGIO5 ST UIntIn15 q 540 GGIO5 ST UIntIn15 stVal 541 GGIO5 ST UIntIn16 q 542 GGIO5 ST UIntIn16 stVal 543 PDIF1 ST Str general 544 PDIF1 ST Op general 545 PDIF2 ST Str general 546 PDIF2 ST Op general 547 PDIF3 ST Str general 548 PDIF...

Page 597: ...eneral 641 PIOC36 ST Str general 642 PIOC36 ST Op general 643 PIOC37 ST Str general 644 PIOC37 ST Op general Enumeration GOOSE dataset items 645 PIOC38 ST Str general 646 PIOC38 ST Op general 647 PIOC39 ST Str general 648 PIOC39 ST Op general 649 PIOC40 ST Str general 650 PIOC40 ST Op general 651 PIOC41 ST Str general 652 PIOC41 ST Op general 653 PIOC42 ST Str general 654 PIOC42 ST Op general 655 ...

Page 598: ...TOC16 ST Op general 747 PTOC17 ST Str general 748 PTOC17 ST Op general 749 PTOC18 ST Str general 750 PTOC18 ST Op general Enumeration GOOSE dataset items 751 PTOC19 ST Str general 752 PTOC19 ST Op general 753 PTOC20 ST Str general 754 PTOC20 ST Op general 755 PTOC21 ST Str general 756 PTOC21 ST Op general 757 PTOC22 ST Str general 758 PTOC22 ST Op general 759 PTOC23 ST Str general 760 PTOC23 ST Op...

Page 599: ...16 ST OpIn general 853 RBRF17 ST OpEx general 854 RBRF17 ST OpIn general 855 RBRF18 ST OpEx general 856 RBRF18 ST OpIn general Enumeration GOOSE dataset items 857 RBRF19 ST OpEx general 858 RBRF19 ST OpIn general 859 RBRF20 ST OpEx general 860 RBRF20 ST OpIn general 861 RBRF21 ST OpEx general 862 RBRF21 ST OpIn general 863 RBRF22 ST OpEx general 864 RBRF22 ST OpIn general 865 RBRF23 ST OpEx genera...

Page 600: ...stVal 955 XSWI4 ST Loc stVal 956 XSWI4 ST Pos stVal 957 XSWI5 ST Loc stVal 958 XSWI5 ST Pos stVal 959 XSWI6 ST Loc stVal 960 XSWI6 ST Pos stVal 961 XSWI7 ST Loc stVal 962 XSWI7 ST Pos stVal Enumeration GOOSE dataset items 963 XSWI8 ST Loc stVal 964 XSWI8 ST Pos stVal 965 XSWI9 ST Loc stVal 966 XSWI9 ST Pos stVal 967 XSWI10 ST Loc stVal 968 XSWI10 ST Pos stVal 969 XSWI11 ST Loc stVal 970 XSWI11 ST ...

Page 601: ...NCY MODE F628 ENUMERATION SECURITY BYPASS ACCESS Disables security on local access remote access or both F629 ENUMERATION SCADA PROTOCOL 0 DNP 3 0 1 IEC 60870 5 104 2 IEC 60870 5 103 Enumeration Role 0 None 1 Administrator 2 Supervisor 3 Engineer 4 Operator 5 Factory Enumeration Role 0 None 1 Administrator 2 Supervisor 3 Engineer 4 Operator 5 Observer Enumeration Mode 0 Mode 1 1 and 3 Pole 1 Mode ...

Page 602: ...Multilin B 4 MEMORY MAPPING APPENDIX B B F630 ENUMERATION IEC 103 ASDU TYPE 0 3 1 9 F631 ENUMERATION VIRTUAL INPUTS FOR IEC 103 Enumeration Item 0 OFF 1 Virtual Input 1 2 Virtual Input 2 3 Virtual Input 3 64 Virtual Input 64 Enumeration Item ...

Page 603: ...that all those involved with any IEC 61850 implementation obtain this document set C 1 2 COMMUNICATION PROFILES IEC 61850 specifies the use of the Manufacturing Message Specification MMS at the upper application layer for transfer of real time data This protocol has been in existence for several of years and provides a set of services suitable for the transfer of data within a substation LAN envir...

Page 604: ...orer window click the Tools menu and access the SISCO File Transfer Utility 2 Select the Remote AR Name from the drop down list Available files appear in the File Specification area on the right side of the window 3 With the Copy option active select a file to transfer and click the Go button The file is copied and displays in the Local list on the left side of the window 4 Repeat the process to t...

Page 605: ... be used for SOE logs since the buffering capability reduces the chances of missing data state changes Unbuffered reporting should generally be used for local status display C 2 3 GGIO2 DIGITAL CONTROL VALUES The GGIO2 logical node is available to provide access to the C60 virtual inputs Virtual inputs are single point control binary values that can be written by clients They are generally used as...

Page 606: ...r MMXU1 MX Hz frequency MMXU1 MX PPV phsAB phase AB voltage magnitude and angle MMXU1 MX PPV phsBC phase BC voltage magnitude and angle MMXU1 MX PPV phsCA Phase CA voltage magnitude and angle MMXU1 MX PhV phsA phase AG voltage magnitude and angle MMXU1 MX PhV phsB phase BG voltage magnitude and angle MMXU1 MX PhV phsC phase CG voltage magnitude and angle MMXU1 MX A phsA phase A current magnitude a...

Page 607: ...locator function The XCBR logical node is directly associated with the breaker control feature XCBR1 ST Loc This is the state of the XCBR1 local remote switch A setting is provided to assign a FlexLogic operand to determine the state When local mode is true IEC 61850 client commands will be rejected XCBR1 ST Opcnt This is an operation counter as defined in IEC 61850 Command settings are provided t...

Page 608: ... of the last change of either the value or quality flags of the data item To accomplish this functionality all IEC 61850 data items must be regularly scanned for data changes and the timestamp updated when a change is detected regardless of the connection status of any IEC 61850 cli ents For applications where there is no IEC 61850 client in use the IEC 61850 SERVER SCANNING setting can be pro gra...

Page 609: ...ction for greater than two minutes the connection will be aborted by the C60 This frees up the con nection to be used by other clients Therefore when using IEC 61850 reporting clients should configure report control block items such that an integrity report will be issued at least every 2 minutes 120000 ms This ensures that the C60 will not abort the connection If other MMS data is being polled on...

Page 610: ...two pre defined data structures named DNA and UserSt Each DNA and UserSt item is referred to as a bit pair GSSE messages are transmit ted in response to state changes in any of the data points contained in the message GSSE messages always contain the same number of DNA and UserSt bit pairs Depending the on the configuration only some of these bit pairs may have val ues that are of interest to rece...

Page 611: ... for applications that require GOOSE data transfer between UR series IEDs and devices from other manufacturers Fixed GOOSE is recommended for applications that require GOOSE data transfer between UR series IEDs IEC 61850 GOOSE messaging contains a number of configurable parameters all of which must be correct to achieve the successful transfer of data It is critical that the configured datasets at...

Page 612: ...ICATION IEC 61850 PROTOCOL GSSE GOOSE CONFIGURATION RECEPTION CONFIGURABLE GOOSE CONFIGURABLE GOOSE 1 CONFIG GSE 1 DATASET ITEMS settings menu Set ITEM 1 to GGIO3 ST Ind1 q to indicate quality flags for GGIO3 status indication 1 Set ITEM 2 to GGIO3 ST Ind1 stVal to indicate the status value for GGIO3 status indication 1 The reception dataset now contains a set of quality flags a single point statu...

Page 613: ...nfigured to use an automated multicast MAC scheme If the C60 destination MAC address setting is not a valid multicast address that is the least significant bit of the first byte is not set the address used as the destina tion MAC will be the same as the local MAC address but with the multicast bit set Thus if the local MAC address is 00 A0 F4 01 02 03 then the destination MAC address will be 01 A0...

Page 614: ...ation process for IEC 61850 BDA Basic Data Attribute that is not structured DAI Instantiated Data Attribute DO Data Object type or instance depending on the context 842790A2 CDR Ethernet System configurator SCD file System specification tool SSD file System specification data ICD file 2 Process of creating ICD vendor 2 Creating ICD GE Multilin EnerVista UR Setup ICD file 1 IED UR series OR ICD fil...

Page 615: ...L file SCD to set communication configuration parame ters that is required addresses reception GOOSE datasets IDs of incoming GOOSE datasets etc for the IED The IED configurator functionality is implemented in the EnerVista UR Setup software C 5 2 CONFIGURING IEC 61850 SETTINGS Before creating an ICD file the user can customize the IEC 61850 related settings for the IED For example the IED name an...

Page 616: ...tors we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD and strictly within EnerVista UR Setup software or the front panel display access through the Settings Product Setup Com munications IEC 61850 GSSE GOOSE Configuration Transmission Tx Configurable GOOSE menu tree in EnerVista UR Setup Configurable reception GOOSE which includes eight configurable datasets...

Page 617: ...ss node contains the address parameters of the access point The GSE node provides the address element for stat ing the control block related address parameters where IdInst is the instance identification of the logical device within the IED on which the control block is located and cbName is the name of the control block The IED node describes the pre configuration of an IED its access points the ...

Page 618: ...ataSet name Other DataSet elements FCDA fc doName daName IdInst prefix InClass InInst Other FCDA elements DOI name SDI name Val Text Other DOI elements GSEControl name datSet type confRev appID LN InType InClass prefix inst DataSet name FCDA IdInst prefix InClass InInst doName fc Other FCDA elements ReportControl name datSet intgPd rptID confRev buffered TrgOps dchg OptFields seqNum RptEnabled Oth...

Page 619: ...DO The attribute DA has a func tional constraint and can either have a basic type be an enumeration or a structure of a DAType The DAType is built from BDA elements defining the structure elements which again can be BDA elements of have a base type such as DA Figure C 5 ICD FILE STRUCTURE DATATYPETEMPLATES NODE 842798A1 CDR DataTypeTemplates LNodeType id InClass DO name type Other LNodeType elemen...

Page 620: ...procedure is pretty much the same First a substation project must be created either as an empty template or with some system information by importing a system specification file SSD Then IEDs are added to the substation Since each IED is represented by its associated ICD the ICD files are imported into the substation project and the system configurator validates the ICD files during the importing ...

Page 621: ...ile and its version and specifies options for the mapping of names to signals The Substation node describes the substation parameters Figure C 7 SCD FILE STRUCTURE SUBSTATION NODE 842791A1 CDR SCL Header id version revision toolID nameStructure IED Section IED 2 Communication IED Section IED 1 Substation Other IED Sections DataTypeTemplates 842792A1 CDR Substation EquipmentContainer VoltageLevel F...

Page 622: ...ctedAP node describes the IED access point connected to this sub network The Address node contains the address parameters of the access point The GSE node provides the address element for stat ing the control block related address parameters where IdInst is the instance identification of the logical device within the IED on which the control block is located and cbName is the name of the control b...

Page 623: ...ate the C60 with the new configuration from an SCD file with the EnerVista UR Setup software 1 Right click anywhere in the files panel and select the Import Contents From SCD File item 2 Select the saved SCD file and click Open 842794A1 CDR IED Section IED 1 AccessPoint name Server Authentication none LDevice inst LN0 InType InClass inst DataSet elements DOI elements Inputs GSEControl elements Rep...

Page 624: ...one GE Multilin IED defined in the SCD file the software prompt the user to save a UR series set tings file for each IED 4 After the URS file is created modify any settings if required 5 To update the relay with the new settings right click on the settings file in the settings tree and select the Write Set tings File to Device item 6 The software will prompt for the target device Select the target...

Page 625: ...CSM IEC 61850 9 2 used B24 SCSM other GENERIC SUBSTATION EVENT MODEL GSE B31 Publisher side O Yes B32 Subscriber side Yes TRANSMISSION OF SAMPLED VALUE MODEL SVC B41 Publisher side O B42 Subscriber side SERVICES SERVER PUBLISHER UR FAMILY IF SERVER SIDE B11 SUPPORTED M1 Logical device c2 Yes M2 Logical node c3 Yes M3 Data c4 Yes M4 Data set c5 Yes M5 Substitution O M6 Setting group control O REPOR...

Page 626: ...t name M8 5 data reference M8 6 BufTm M8 7 IntgPd M8 8 GI Logging O M9 Log control O M9 1 IntgPd M10 Log O M11 Control M Yes IF GSE B31 32 IS SUPPORTED GOOSE O Yes M12 1 entryID M12 2 DataReflnc M13 GSSE O Yes IF SVC B41 B42 IS SUPPORTED M14 Multicast SVC O M15 Unicast SVC O M16 Time M Yes M17 File transfer O Yes SERVICES AA TP MC SERVER PUBLISHER UR FAMILY SERVER CLAUSE 7 S1 ServerDirectory TP M ...

Page 627: ...s S26 SetBRCBValues TP c6 Yes UNBUFFERED REPORT CONTROL BLOCK URCB S27 Report TP c6 Yes S27 1 data change dchg Yes S27 2 qchg change qchg S27 3 data update dupd S28 GetURCBValues TP c6 Yes S29 SetURCBValues TP c6 Yes LOGGING CLAUSE 17 LOG CONTROL BLOCK S30 GetLCBValues TP M S31 SetLCBValues TP M LOG S32 QueryLogByTime TP M S33 QueryLogByEntry TP M S34 GetLogStatusValues TP M GENERIC SUBSTATION EVE...

Page 628: ...ndMSVMessage MC c10 S46 GetMSVCBValues TP O S47 SetMSVCBValues TP O UNICAST SVC S48 SendUSVMessage MC c10 S49 GetUSVCBValues TP O S50 SetUSVCBValues TP O CONTROL CLAUSE 20 S51 Select O Yes S52 SelectWithValue TP O S53 Cancel TP O Yes S54 Operate TP M Yes S55 Command Termination TP O S56 TimeActivated Operate TP O FILE TRANSFER CLAUSE 23 S57 GetFile TP M Yes S58 SetFile TP O S59 DeleteFile TP O S60...

Page 629: ...ng A LOGICAL NODES FOR AUTOMATIC CONTROL ANCR Neutral current regulator ARCO Reactive power control ATCC Automatic tap changer controller AVCO Voltage control C LOGICAL NODES FOR CONTROL CALH Alarm handling CCGR Cooling group control CILO Interlocking CPOW Point on wave switching CSWI Switch controller Yes CSYN Synchronizer controller F LOGICAL NODES FOR FUNCTIONAL BLOCKS FCNT Counter FCSD Curve s...

Page 630: ... MSQI Sequence and imbalance Yes MSTA Metering statistics P LOGICAL NODES FOR PROTECTION FUNCTIONS PDIF Differential Yes PDIR Direction comparison PDIS Distance Yes PDOP Directional overpower PDUP Directional underpower PFRC Rate of change of frequency PHAR Harmonic restraint PHIZ Ground detector PIOC Instantaneous overcurrent Yes PMRI Motor restart inhibition PMSS Motor starting time supervision ...

Page 631: ...rential measurements RPSB Power swing detection blocking Yes RREC Autoreclosing Yes RSYN Synchronism check or synchronizing S LOGICAL NODES FOR SENSORS AND MONITORING SARC Monitoring and diagnostics for arcs SCBR Circuit breaker supervision SIMG Insulation medium supervision gas SIML Insulation medium supervision liquid SLTC Tap changer supervision SOPM Supervision of operating mechanism SPDC Moni...

Page 632: ...th fault neutralizer Petersen coil YLTC Tap changer YPSH Power shunt YPTR Power transformer Z LOGICAL NODES FOR FURTHER POWER SYSTEM EQUIPMENT ZAXN Auxiliary network ZBAT Battery ZBSH Bushing ZCAB Power cable ZCAP Capacitor bank ZCON Converter ZGEN Generator ZGIL Gas insulated line ZLIN Power overhead line ZMOT Motor ZREA Reactor ZRES Resistor ZRRC Rotating reactive component ZSAR Surge arrestor Z...

Page 633: ...roperability table Interoperability means that any required applica tion data in the device which can be coded into an IEC 60870 5 103 data type can be mapped into the IEC 60870 5 103 address space This data is recognized by any IEC 60870 5 103 master D 1 2 FACTOR AND OFFSET CALCULATION TO TRANSMIT MEASURAND The general formula for the transmitted value is Xt a X b where X is the measurand a is th...

Page 634: ...AYER Transmission mode for application data Mode 1 least significant octet first as defined in 4 10 of IEC 60870 5 4 is used exclusively in this companion stan dard Common address of ASDU One COMMON ADDRESS OF ASDU identical with station address More than one COMMON ADDRESS OF ASDU Selection of standard information numbers in monitor direction System functions in monitor direction INF Semantics 0 ...

Page 635: ...equence supervision 36 Trip circuit supervision 37 I back up operation 38 VT fuse failure 39 Teleprotection disturbed 46 Group warning 47 Group alarm Earth fault indications in monitor direction INF Semantics 48 Earth fault L1 49 Earth fault L2 50 Earth fault L3 51 Earth fault forward meaning line 52 Earth fault reverse meaning busbar Fault indications in monitor direction INF Semantics 64 Start p...

Page 636: ... IN Auto reclosure indications in monitor direction INF Semantics 128 CB on by AR 129 CB on by long time AR 130 AR blocked Measurands in monitor direction INF Semantics 144 Measurand I 145 Measurands I V 146 Measurands I V P Q 147 Measurands IN VEN 148 Measurands IL123 VL123 P Q f Generic functions in monitor direction INF Semantics 240 Read headings of all defined groups 241 Read values or attrib...

Page 637: ... 25 Activate characteristic 3 26 Activate characteristic 4 Generic functions in control direction INF Semantics 240 Read headings of all defined groups 241 Read values or attributes of all entries of one group 243 Read directory of a single entry 244 Read value or attribute of a single entry 245 General interrogation of generic data 248 Write entry 249 Write entry with confirmation 250 Write entry...

Page 638: ...D 6 C60 Breaker Protection System GE Multilin D 1 IEC 60870 5 103 APPENDIX D D Voltage L3 E Active power P Reactive power Q Frequency f Voltage L1 L2 MEASURAND MAX MVAL TIMES RATED VALUE 1 2 OR 2 4 ...

Page 639: ... V 24 V 28 Recommended if 1200 bits s Balanced Interchange Circuit X 24 X 27 100 bits sec 200 bits sec 300 bits sec 600 bits sec 1200 bits sec 2400 bits sec 4800 bits sec 9600 bits sec 2400 bits sec 4800 bits sec 9600 bits sec 19200 bits sec 38400 bits sec 56000 bits sec 64000 bits sec Unbalanced Interchange Circuit V 24 V 28 Standard Unbalanced Interchange Circuit V 24 V 28 Recommended if 1200 bi...

Page 640: ...he following used in standard direction not used cannot be selected in IEC 60870 5 104 standard Process information in monitor direction 1 Single point information M_SP_NA_1 2 Single point information with time tag M_SP_TA_1 3 Double point information M_DP_NA_1 4 Double point information with time tag M_DP_TA_1 5 Step position information M_ST_NA_1 6 Step position information with time tag M_ST_TA...

Page 641: ...otection equipment with time tag CP56Time2a M_EP_TE_1 40 Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1 45 Single command C_SC_NA_1 46 Double command C_DC_NA_1 47 Regulating step command C_RC_NA_1 48 Set point command normalized value C_SE_NA_1 49 Set point command scaled value C_SE_NB_1 50 Set point command short floating point value C_SE_NC_1 51 Bits...

Page 642: ...ory select file call file call section F_SC_NA_1 123 Last section last segment F_LS_NA_1 124 Ack file ack section F_AF_NA_1 125 Segment F_SG_NA_1 126 Directory blank or X available only in monitor standard direction C_CD_NA_1 TYPE IDENTIFICATION CAUSE OF TRANSMISSION NO MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 20 to 36 37 to 41 44 45 46 47 1 M_SP_NA_1 X X X X X 2 M_SP_TA_1 3 M_DP_NA_1 4 M_DP_TA_1 5 ...

Page 643: ... C_SE_NA_1 49 C_SE_NB_1 50 C_SE_NC_1 51 C_BO_NA_1 58 C_SC_TA_1 X X X X X 59 C_DC_TA_1 60 C_RC_TA_1 TYPE IDENTIFICATION CAUSE OF TRANSMISSION NO MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 20 to 36 37 to 41 44 45 46 47 PERIODIC CYCLIC BACKGROUND SCAN SPONTANEOUS INITIALIZED REQUEST OR REQUESTED ACTIVATION ACTIVATION CONFIRMATION DEACTIVATION DEACTIVATION CONFIRMATION ACTIVATION TERMINATION RETURN INFO C...

Page 644: ...E_NC_1 X X X 113 P_AC_NA_1 120 F_FR_NA_1 121 F_SR_NA_1 122 F_SC_NA_1 123 F_LS_NA_1 124 F_AF_NA_1 125 F_SG_NA_1 126 F_DR_TA_1 TYPE IDENTIFICATION CAUSE OF TRANSMISSION NO MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 20 to 36 37 to 41 44 45 46 47 PERIODIC CYCLIC BACKGROUND SCAN SPONTANEOUS INITIALIZED REQUEST OR REQUESTED ACTIVATION ACTIVATION CONFIRMATION DEACTIVATION DEACTIVATION CONFIRMATION ACTIVATION...

Page 645: ...umber M_ME_NC_1 M_ME_TC_1 and M_ME_TF_1 Station interrogation Clock synchronization Clock synchronization optional see Clause 7 6 Command transmission Direct command transmission Direct setpoint command transmission Select and execute command Select and execute setpoint command C_SE ACTTERM used No additional definition Short pulse duration duration determined by a system parameter in the outstati...

Page 646: ...f events Transmission of sequences of recorded analog values File transfer in control direction Transparent file Background scan Background scan Acquisition of transmission delay Acquisition of transmission delay Definition of time outs Maximum range of values for all time outs 1 to 255 s accuracy 1 s Maximum number of outstanding I format APDUs k and latest acknowledge APDUs w PARAMETER DEFAULT V...

Page 647: ...etermined by the Internet Architecture Board IAB It offers a broad spectrum of actual standards used in the Inter net The suitable selection of documents from RFC 2200 defined in this standard for given projects has to be chosen by the user of this standard Ethernet 802 3 Serial X 21 interface Other selection s from RFC 2200 list below if selected E 1 2 POINT LIST The IEC 60870 5 104 data points a...

Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...

Page 649: ... in addition to the Highest DNP Levels Supported the complete list is described in the attached table Binary Inputs Object 1 Binary Input Changes Object 2 Binary Outputs Object 10 Control Relay Output Block Object 12 Binary Counters Object 20 Frozen Counters Object 21 Counter Change Event Object 22 Frozen Counter Event Object 23 Analog Inputs Object 30 Analog Input Changes Object 32 Analog Deadban...

Page 650: ...nary Outputs Never Always Sometimes Configurable SELECT OPERATE Never Always Sometimes Configurable DIRECT OPERATE Never Always Sometimes Configurable DIRECT OPERATE NO ACK Never Always Sometimes Configurable Count 1 Never Always Sometimes Configurable Pulse On Never Always Sometimes Configurable Pulse Off Never Always Sometimes Configurable Latch On Never Always Sometimes Configurable Latch Off N...

Page 651: ...onfigurable Only certain objects Sometimes attach explanation ENABLE DISABLE unsolicited Function codes supported Sends Static Data in Unsolicited Responses Never When Device Restarts When Status Flags Change No other options are permitted Default Counter Object Variation No Counters Reported Configurable attach explanation Default Object 20 Default Variation 1 Point by point list attached Counter...

Page 652: ...sp 17 28 index 3 Binary Input Change with Relative Time 1 read 06 no range or all 07 08 limited quantity 10 0 Binary Output Status Variation 0 is used to request default variation 1 read 00 01 start stop 06 no range or all 07 08 limited quantity 17 28 index 2 Binary Output Status 1 read 00 01 start stop 06 no range or all 07 08 limited quantity 17 28 index 129 response 00 01 start stop 17 28 index...

Page 653: ...Variation 0 is used to request default variation 1 read 06 no range or all 07 08 limited quantity 1 32 Bit Counter Change Event 1 read 06 no range or all 07 08 limited quantity 129 response 130 unsol resp 17 28 index 2 16 Bit Counter Change Event 1 read 06 no range or all 07 08 limited quantity 129 response 130 unsol resp 17 28 index 5 32 Bit Counter Change Event with Time 1 read 06 no range or al...

Page 654: ...esponse 130 unsol resp 17 28 index 3 32 Bit Analog Change Event with Time 1 read 06 no range or all 07 08 limited quantity 129 response 130 unsol resp 17 28 index 4 16 Bit Analog Change Event with Time 1 read 06 no range or all 07 08 limited quantity 129 response 130 unsol resp 17 28 index 5 short floating point Analog Change Event without Time 1 read 06 no range or all 07 08 limited quantity 129 ...

Page 655: ... close 30 abort 5b free format 129 response 130 unsol resp 5b free format 5 File transfer 1 read 2 write 5b free format 129 response 130 unsol resp 5b free format 6 File transfer status 129 response 130 unsol resp 5b free format 7 File descriptor 28 get file info 5b free format 129 response 130 unsol resp 5b free format 80 1 Internal Indications 1 read 00 01 start stop index 7 129 response 00 01 s...

Page 656: ...rmed on a binary counter point the frozen value is available in the corresponding frozen counter point BINARY INPUT POINTS Static Steady State Object Number 1 Change Event Object Number 2 Request Function Codes supported 1 read 22 assign class Static Variation reported when variation 0 requested 2 Binary Input with status Configurable Change Event Variation reported when variation 0 requested 2 Bi...

Page 657: ...ual Input 15 15 Virtual Input 16 16 Virtual Input 17 17 Virtual Input 18 18 Virtual Input 19 19 Virtual Input 20 20 Virtual Input 21 21 Virtual Input 22 22 Virtual Input 23 23 Virtual Input 24 24 Virtual Input 25 25 Virtual Input 26 26 Virtual Input 27 27 Virtual Input 28 28 Virtual Input 29 29 Virtual Input 30 30 Virtual Input 31 31 Virtual Input 32 32 Virtual Input 33 33 Virtual Input 34 34 Virt...

Page 658: ...eeze and clear noack 22 assign class Static Variation reported when variation 0 requested 1 32 Bit Binary Counter with Flag Change Event Variation reported when variation 0 requested 1 32 Bit Counter Change Event without time Change Event Buffer Size 10 Default Class for all points 3 FROZEN COUNTERS Static Steady State Object Number 21 Change Event Object Number 23 Request Function Codes supported...

Page 659: ...g Input points are in the same units as the Analog Input quantity For example an Analog Input quantity measured in volts has a corresponding deadband in units of volts This is in conformance with DNP Technical Bul letin 9809 001 Analog Input Reporting Deadband Relay settings are available to set default deadband values according to data type Deadbands for individual Analog Input Points can be set ...

Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...

Page 661: ...er Tester with an Administrator role Tester User Password testpw GE PDC USER Role Administrator 4 In the clients conf file in the Path_to_Radius etc raddb folder add the following text to define the UR as a RADIUS client where the client IP address is 10 0 0 2 the subnet mask is 255 255 255 0 the shared secret specified here is also configured on the UR device for successful authentication and the...

Page 662: ... server Leave the GE vendor ID field at the default of 2910 Update the RADIUS shared secret as specified in the clients conf file Restart the relay for the IP address and port changes to take effect 9 Verify operation Log in to the UR software as follows In the login window select Server as the Authentication Type enter the user name entered for example user name Tester and password testpw Check t...

Page 663: ...1 February 2003 URC 036 1601 0100 C6 3 1x 11 February 2003 URC 037 1601 0100 D1 3 2x 11 February 2003 URC 039 1601 0100 D2 3 2x 02 June 2003 URX 084 1601 0100 E1 3 3x 01 May 2003 URX 080 1601 0100 E2 3 3x 29 May 2003 URX 083 1601 0100 F1 3 4x 10 December 2003 URX 111 1601 0100 F2 3 4x 09 February 2004 URX 115 1601 0100 G1 4 0x 23 March 2004 URX 123 1601 0100 G2 4 0x 17 May 2004 URX 136 1601 0100 H...

Page 664: ... MANUAL REVISION AA4 PAGE AA3 PAGE AA4 CHANGE DESCRIPTION Update General revision including updated branding from GE Digital Energy to GE Grid Solutions Delete Deleted EAC logo from title page and deleted EAC certification from Approvals specifications because document not translated into Russian Table H 4 MAJOR UPDATES FOR C60 MANUAL REVISION AA3 PAGE AA2 PAGE AA3 CHANGE DESCRIPTION Update Genera...

Page 665: ...SION Z1 PAGE Y3 PAGE Z1 CHANGE DESCRIPTION Add Added CPU options U and V to order code tables in chapter 2 a note above Rear Terminal View figure in chapter 3 and CPU Module Communications Wiring figure in chapter 3 Add Added Parallel Redundancy Protocol PRP to order code tables and specifications in chapter 2 section 5 2 5d Settings Product Setup Communications Network section 6 3 1 Actual Values...

Page 666: ...ll three Ethernet ports 5 18 5 18 Update Added 0 as valid number to section 5 2 4e Modbus Protocol section 5 40 5 Delete Deleted Local Time Offset Daylight Savings Time DST start stop for month day hour from Real Time Clock menu 5 5 40 Add Added submenus Precision Time Protocol SNTP Protocol and Local Time and Synchronizing Source settings to Real Time Clock menu 5 5 41 Add Added new Precision Tim...

Page 667: ... section for CyberSentry software option with overview and security menu subsections A A Add Added Flexanalog item PTP IRIG B Delta to Table A 1 Flexanalog Data Items B 8 B 8 Update Updated Modbus memory map table to include port 0 for Modbus slave address TCP DNP HTTP TFTP MMS and removed references to COM 1 RS485 port C 23 C 23 Update Updated tables in sections C 6 3 ACSI Services Conformance St...

Page 668: ...d FAIL Failure FD Fault Detector FDH Fault Detector high set FDL Fault Detector low set FLA Full Load Current FO Fiber Optic FREQ Frequency FSK Frequency Shift Keying FTP File Transfer Protocol FxE FlexElement FWD Forward G Generator GE General Electric GND Ground GNTR Generator GOOSE General Object Oriented Substation Event GPS Global Positioning System HARM Harmonic Harmonics HCT High Current Ti...

Page 669: ...re Detector RTU Remote Terminal Unit RX Rx Receive Receiver s second S Sensitive SAT CT Saturation SBO Select Before Operate SCADA Supervisory Control and Data Acquisition SEC Secondary SEL Select Selector Selection SENS Sensitive SEQ Sequence SFTP Secure Shell SSH File Transfer Protocol Secure File Transfer Protocol SIR Source Impedance Ratio SNTP Simple Network Time Protocol SRC Source SSB Singl...

Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...

Page 671: ... 1 October 2013 GE Grid Solutions warrants most of its GE manufactured products for 10 years For warranty details including any limitations and disclaimers see the GE Grid Solutions Terms and Conditions at https www gegridsolutions com multilin warranty htm For products shipped before 1 October 2013 the standard 24 month warranty applies ...

Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...

Page 673: ... 5 148 logic 5 198 Modbus registers B 45 settings 5 198 specifications 2 19 AUXILIARY VOLTAGE CHANNEL 3 12 AUXILIARY VOLTAGE METERING 6 18 AWG WIRE SIZE 3 11 3 35 3 38 3 40 B BANKS 5 6 5 102 5 103 BATTERY disposal 9 5 failure 7 9 replace 9 3 BATTERY FAILURE 7 9 BINARY INPUT POINTS F 8 BINARY OUTPUT POINTS F 9 BLOCK DIAGRAM 1 3 BLOCK SETTING 5 5 BREAKER ARCING CURRENT actual values 6 27 clearing 5 ...

Page 674: ...M 5 97 CRC 16 ALGORITHM B 2 CRITICAL FAILURE RELAY 2 25 3 10 CSA APPROVAL 2 30 CT BANKS settings 5 102 CT INPUTS 3 12 5 6 5 102 CT WIRING 3 12 CURRENT BANK 5 102 CURRENT DEMAND 5 76 CURRENT DIFFERENTIAL Modbus registers B 20 CURRENT METERING actual values 6 16 specifications 2 22 CURVES definite time 5 174 5 193 FlexCurves 5 115 5 174 I2T 5 174 IAC 5 173 IEC 5 172 IEEE 5 170 inverse time undervolt...

Page 675: ...ELECTROSTATIC DISCHARGE 2 29 ELEMENTS 5 4 EMAIL ADDRESS FOR SUPPORT 1 2 END OF LIFE 9 11 ENERGY METERING actual values 6 19 Modbus registers B 17 specifications 2 22 2 23 ENERGY METERING CLEARING 5 26 7 2 ENERVISTA UR SETUP creating a site list 4 1 event recorder 4 2 firmware upgrades 4 2 installation 1 5 introduction 4 1 oscillography 4 2 overview 4 1 requirements 1 5 EQUATIONS definite time curv...

Page 676: ...QUENCY METERING actual values 6 20 settings 5 104 specifications 2 23 FREQUENCY RATE OF CHANGE Modbus registers B 15 FREQUENCY TRACKING 5 104 6 21 FREQUENCY NOMINAL 5 104 FUNCTION SETTING 5 5 FUSE 2 24 FUSE FAILURE see VT FUSE FAILURE Fuses not field replaceable 9 9 G G 703 3 35 3 36 3 37 3 40 G 703 WIRE SIZE 3 35 GATEWAY ADDRESS 5 32 GE TYPE IAC CURVES 5 173 GROUND CURRENT METERING 6 17 GROUND IO...

Page 677: ... SYSTEM 5 22 LOST PASSWORD 5 8 M MAINTENANCE alert to replace battery 7 9 battery 9 3 module replacement 9 1 MAINTENANCE COMMANDS 7 4 MANUFACTURING DATE 6 28 MAXIMUM CT VT WIRE SIZE 3 11 MEMORY MAP DATA FORMATS B 75 MENU HIERARCHY 1 17 4 25 MENU NAVIGATION 1 17 4 23 METERING conventions 6 13 6 14 current 2 22 demand 2 23 frequency 2 23 power 2 22 voltage 2 22 METERING CONVENTIONS 6 14 MODBUS data ...

Page 678: ...CURVE TYPES 5 170 OVERCURRENT CURVES definite time 5 174 FlexCurves 5 174 I2T 5 174 IAC 5 173 IEC 5 172 IEEE 5 170 OVERVOLTAGE auxiliary 2 20 5 199 neutral 2 20 5 197 phase 2 20 5 196 P PANEL CUTOUT 3 1 3 2 PARALLEL REDUNDANCY PROTOCOL actual values 6 12 explained 5 31 settings 5 30 specifications 2 26 PARITY 5 27 PASSWORD SECURITY FlexLogic operands 5 154 PASSWORDS change does not take relay out ...

Page 679: ... 21 settings 5 260 statistics 6 7 REMOTE DPS INPUTS actual values 6 5 settings 5 263 REMOTE INPUTS actual values 6 4 FlexLogic operands 5 153 Modbus registers B 14 B 21 settings 5 262 specifications 2 23 REMOTE OUTPUTS DNA 1 bit pair 5 263 Modbus registers B 66 B 67 UserSt 1 bit pair 5 264 REMOTE SETTING AUTHORIZATION 4 2 REPAIR 9 9 H 9 REPLACEMENT MODULES 2 14 2 15 REQUIREMENTS FOR INSTALLATION 1...

Page 680: ... STORAGE TEMPERATURE 2 28 SUMMATOR Modbus registers B 45 SUPPORT TECHNICAL 1 2 SURGE IMMUNITY 2 29 SYMMETRICAL COMPONENTS METERING 6 14 SYNCHROCHECK actual values 6 10 6 21 6 22 FlexLogic operands 5 152 logic 5 218 Modbus registers B 20 B 71 settings 5 215 5 216 specifications 2 20 SYNCHROPHASORS actual values 6 23 clearing PMU records 7 2 commands 7 5 7 6 FlexLogic operands 5 150 5 151 phase meas...

Page 681: ...isters B 29 B 35 settings 5 89 5 91 specifications 2 21 USER PROGRAMMABLE LEDs defaults 4 17 description 4 15 4 16 Modbus registers B 32 settings 5 79 specifications 2 21 USER PROGRAMMABLE PUSHBUTTONS FlexLogic operands 5 154 Modbus registers B 36 B 44 settings 5 84 specifications 2 21 USER PROGRAMMABLE SELF TESTS Modbus registers B 34 settings 5 80 USERST 1 BIT PAIR 5 264 V VAR HOURS 2 23 6 19 VI...

Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...

Reviews: