C60 Breaker Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–72: GROUND IOC1 SCHEME LOGIC
5.6.6 BREAKER FAILURE (ANSI 50BF)
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
BREAKER FAILURE
BREAKER FAILURE 1(2)
BREAKER FAILURE 1
BF1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
BF1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
BF1 SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
BF1 USE AMP SUPV:
Yes
Range: Yes, No
MESSAGE
BF1 USE SEAL-IN:
Yes
Range: Yes, No
MESSAGE
BF1 3-POLE INITIATE:
Off
Range: FlexLogic operand
MESSAGE
BF1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
BF1 PH AMP SUPV
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001
MESSAGE
BF1 N AMP SUPV
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001
MESSAGE
BF1 USE TIMER 1:
Yes
Range: Yes, No
MESSAGE
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BF1 USE TIMER 2:
Yes
Range: Yes, No
MESSAGE
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BF1 USE TIMER 3:
Yes
Range: Yes, No
SETTING
GROUND IOC1
FUNCTION:
Enabled = 1
SETTING
GROUND IOC1
SOURCE:
IG
GROUND IOC1
BLOCK:
Off = 0
FLEXLOGIC OPERANDS
GROUND IOIC DPO
GROUND IOC1 OP
SETTING
SETTING
IG
PICKUP
GROUND IOC1
PICKUP:
RUN
GROUND IOC1 PICKUP
DELAY:
SETTINGS
GROUND IOC1 RESET
DELAY:
t
PKP
t
RST
827037A5.VSD
AND
GROUND IOC1 PKP
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...