7-12
C60 Breaker Protection System
GE Multilin
7.1 COMMANDS
7 COMMANDS AND TARGETS
7
•
What to do
: Remove the C60 from service and install in a location that meets operating temperature standards.
•
Latched target message
: Yes.
•
Description of problem
: Abnormal restart from modules being removed or inserted while the C60 is powered-up, when
there is an abnormal DC supply, or as a result of internal relay failure.
•
How often the test is performed
: Event driven.
•
What to do
: Contact the factory.
•
Latched target message
: Yes.
•
Description of problem
: A link loss detection on an Ethernet port. The link loss is due to unplugging the cable or the
switch port being down.
•
How often the test is performed
:
•
What to do
: Check the connection.
•
Latched target message
: No.
•
Description of problem
: The number of failures threshold was exceeded.
•
What to do
: Wait for the lockout interval and try to authenticate again.
•
Message
: "Unauthorized firmware attempt"
•
Latched target message
: No.
•
Description of problem
: A firmware upgrade operation was attempted while the lock relay setting was enabled.
•
What to do
: Ask the Supervisor to unlock the relay and try again.
•
Message
: "Unauthorized setting write"
•
Latched target message
: No.
•
Description of problem
: A setting write was attempted while the lock relay setting was enabled.
•
What to do
: Ask the Supervisor to unlock the settings and try again.
UNEXPECTED RESTART:
Press “RESET” key
FIRST ETHERNET FAIL
SECOND ETHERNET FAIL
THIRD ETHERNET FAIL
AUTHENTICATION FAIL
FIRMWARE LOCK
SETTING LOCK
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...