5-64
C60 Breaker Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Transmitted voltage Vt = (8191/(Vn*2.4)) * V - 4096 =
= (8191/(500000 * 2.4) ) * V - 4096 = 0.0068 * V - 4096
a = 0.0068
Since the step is in increments of 0.001, we round it at:
a = 0.006
b = -4096
Vt = 0.006 * V - 4096
For max voltage 500000V * 2.4 = 1200000V, we transmit
Vt = 0.006 * 1200000 - 4096 = 7200 - 4096 = 3104
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC60870-5-103
IEC103 COMMANDS
Commands are received as General Command (Type Identification 20). The user can configure which action to perform
when an ASDU command comes.
A list of available mappings is provided on the C60. This includes 64 virtual inputs (see the following table). The ON and
OFF for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN), and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
IEC103 COMMANDS
COMMAND 0
Range: see sub-menu below
MESSAGE
COMMAND 1
Range: see sub-menu below
↓
MESSAGE
COMMAND 31
Range: see sub-menu below
COMMAND 0
COMMAND 0 FUN:
0
Range: 0 to 255 in steps of 1
MESSAGE
COMMAND 0 INF:
0
Range: 0 to 255 in steps of 1
MESSAGE
COMMAND 0 ON:
Off
Range: Virtual input
MESSAGE
COMMAND 0 OFF:
Off
Range: Virtual input
↓
COMMAND 31
COMMAND 31 FUN:
0
Range: 0 to 255 in steps of 1
MESSAGE
COMMAND 31 INF:
0
Range: 0 to 255 in steps of 1
MESSAGE
COMMAND 31 ON:
Off
Range: Virtual input
MESSAGE
COMMAND 31 OFF:
Off
Range: Virtual input
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...