GE Multilin
C60 Breaker Protection System
5-269
5 SETTINGS
5.8 INPUTS AND OUTPUTS
5
5.8.11 TELEPROTECTION INPUTS AND OUTPUTS
a) OVERVIEW
The relay provides sixteen teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and sixteen
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only, num-
bered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by assigning
FlexLogic operands to be sent via the selected communications channel. This allows the user to create distributed protec-
tion and control schemes via dedicated communications channels. Some examples are directional comparison pilot
schemes and direct transfer tripping. It should be noted that failures of communications channels will affect teleprotection
functionality. The teleprotection function must be enabled to utilize the inputs.
b) TELEPROTECTION INPUTS
PATH: SETTINGS
INPUTS/OUTPUTS
TELEPROTECTION
TELEPROT INPUTS
Setting the
TELEPROT INPUT ~~ DEFAULT
setting to “On” defaults the input to logic 1 when the channel fails. A value of “Off”
defaults the input to logic 0 when the channel fails.
The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known,
such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/On”
and logic 0 for “Latest/Off”.
TELEPROT INPUTS
TELEPROT INPUT 1-1
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
MESSAGE
TELEPROT INPUT 1-2
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
↓
MESSAGE
TELEPROT INPUT 1-16
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
MESSAGE
TELEPROT INPUT 2-1
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
MESSAGE
TELEPROT INPUT 2-2
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
↓
MESSAGE
TELEPROT INPUT 2-16
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...