GE Multilin
C60 Breaker Protection System
B-47
APPENDIX B
B.4 MEMORY MAPPING
B
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
0 to 1
---
1
F102
0 (Disabled)
8A01
Digital Element 1 Name
---
---
---
F203
“Dig Element 1“
8A09
Digital Element 1 Input
0 to 4294967295
---
1
F300
0
8A0B
Digital Element 1 Pickup Delay
0 to 999999.999
s
0.001
F003
0
8A0D
Digital Element 1 Reset Delay
0 to 999999.999
s
0.001
F003
0
8A0F
Digital Element 1 Block
0 to 4294967295
---
1
F300
0
8A11
Digital Element 1 Target
0 to 2
---
1
F109
0 (Self-reset)
8A12
Digital Element 1 Events
0 to 1
---
1
F102
0 (Disabled)
8A13
Digital Element 1 Pickup LED
0 to 1
---
1
F102
1 (Enabled)
8A14
Reserved (2 items)
---
---
---
F001
0
8A16
...Repeated for Digital Element 2
8A2C
...Repeated for Digital Element 3
8A42
...Repeated for Digital Element 4
8A58
...Repeated for Digital Element 5
8A6E
...Repeated for Digital Element 6
8A84
...Repeated for Digital Element 7
8A9A
...Repeated for Digital Element 8
8AB0
...Repeated for Digital Element 9
8AC6
...Repeated for Digital Element 10
8ADC
...Repeated for Digital Element 11
8AF2
...Repeated for Digital Element 12
8B08
...Repeated for Digital Element 13
8B1E
...Repeated for Digital Element 14
8B34
...Repeated for Digital Element 15
8B4A
...Repeated for Digital Element 16
8B60
...Repeated for Digital Element 17
8B76
...Repeated for Digital Element 18
8B8C
...Repeated for Digital Element 19
8BA2
...Repeated for Digital Element 20
8BB8
...Repeated for Digital Element 21
8BCE
...Repeated for Digital Element 22
8BE4
...Repeated for Digital Element 23
8BFA
...Repeated for Digital Element 24
8C10
...Repeated for Digital Element 25
8C26
...Repeated for Digital Element 26
8C3C
...Repeated for Digital Element 27
8C52
...Repeated for Digital Element 28
8C68
...Repeated for Digital Element 29
8C7E
...Repeated for Digital Element 30
8C94
...Repeated for Digital Element 31
8CAA
...Repeated for Digital Element 32
8CC0
...Repeated for Digital Element 33
8CD6
...Repeated for Digital Element 34
8CEC
...Repeated for Digital Element 35
8D02
...Repeated for Digital Element 36
8D18
...Repeated for Digital Element 37
8D2E
...Repeated for Digital Element 38
8D44
...Repeated for Digital Element 39
8D5A
...Repeated for Digital Element 40
8D70
...Repeated for Digital Element 41
8D86
...Repeated for Digital Element 42
8D9C
...Repeated for Digital Element 43
8DB2
...Repeated for Digital Element 44
Table B–10: MODBUS MEMORY MAP (Sheet 39 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...