B-46
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
83F1
EGD Slow Producer Exchange 1 Configuration Time
0 to 4294967295
---
---
F003
0
83F3
EGD Slow Producer Exchange 1 Size
0 to 65535
---
1
F001
0
83F4
...Repeated for EGD Slow Producer Exchange 2
EGD Fast Production (Read/Write Setting)
8400
EGD Fast Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
8401
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
8403
EGD Fast Producer Exchange 1 Data Rate
50 to 1000
ms
50
F001
1000
8404
EGD Fast Producer Exchange 1 Data Item 1 (20 items)
0 to 65535
---
1
F001
0
8418
Reserved (80 items)
---
---
---
F001
0
EGD Slow Production (Read/Write Setting) (2 modules)
8468
EGD Slow Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
8469
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
846B
EGD Slow Producer Exchange 1 Data Rate
500 to 1000
ms
50
F001
1000
846C
EGD Slow Producer Exchange 1 Data Item 1 (50 items)
0 to 65535
---
1
F001
0
849E
Reserved (50 items)
---
---
---
F001
0
84D0
...Repeated for EGD Exchange 2
Breaker Failure (Read/Write Grouped Setting) (2 modules)
8600
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
8601
Breaker Failure 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
8602
Breaker Failure 1 Source
0 to 5
---
1
F167
0 (SRC 1)
8603
Breaker Failure 1 Amp Supervision
0 to 1
---
1
F126
1 (Yes)
8604
Breaker Failure 1 Use Seal-In
0 to 1
---
1
F126
1 (Yes)
8605
Breaker Failure 1 Three Pole Initiate
0 to 4294967295
---
1
F300
0
8607
Breaker Failure 1 Block
0 to 4294967295
---
1
F300
0
8609
Breaker Failure 1 Phase Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860A
Breaker Failure 1 Neutral Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860B
Breaker Failure 1 Use Timer 1
0 to 1
---
1
F126
1 (Yes)
860C
Breaker Failure 1 Timer 1 Pickup
0 to 65.535
s
0.001
F001
0
860D
Breaker Failure 1 Use Timer 2
0 to 1
---
1
F126
1 (Yes)
860E
Breaker Failure 1 Timer 2 Pickup
0 to 65.535
s
0.001
F001
0
860F
Breaker Failure 1 Use Timer 3
0 to 1
---
1
F126
1 (Yes)
8610
Breaker Failure 1 Timer 3 Pickup
0 to 65.535
s
0.001
F001
0
8611
Breaker Failure 1 Breaker Status 1 Phase A/3P
0 to 4294967295
---
1
F300
0
8613
Breaker Failure 1 Breaker Status 2 Phase A/3P
0 to 4294967295
---
1
F300
0
8615
Breaker Failure 1 Breaker Test On
0 to 4294967295
---
1
F300
0
8617
Breaker Failure 1 Phase Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8618
Breaker Failure 1 Neutral Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8619
Breaker Failure 1 Phase Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861A
Breaker Failure 1 Neutral Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861B
Breaker Failure 1 Loset Time
0 to 65.535
s
0.001
F001
0
861C
Breaker Failure 1 Trip Dropout Delay
0 to 65.535
s
0.001
F001
0
861D
Breaker Failure 1 Target
0 to 2
---
1
F109
0 (Self-reset)
861E
Breaker Failure 1 Events
0 to 1
---
1
F102
0 (Disabled)
861F
Breaker Failure 1 Phase A Initiate
0 to 4294967295
---
1
F300
0
8621
Breaker Failure 1 Phase B Initiate
0 to 4294967295
---
1
F300
0
8623
Breaker Failure 1 Phase C Initiate
0 to 4294967295
---
1
F300
0
8625
Breaker Failure 1 Breaker Status 1 Phase B
0 to 4294967295
---
1
F300
0
8627
Breaker Failure 1 Breaker Status 1 Phase C
0 to 4294967295
---
1
F300
0
8629
Breaker Failure 1 Breaker Status 2 Phase B
0 to 4294967295
---
1
F300
0
862B
Breaker Failure 1 Breaker Status 2 Phase C
0 to 4294967295
---
1
F300
0
862D
...Repeated for Breaker Failure 2
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
0 to 4294967295
---
1
F300
0
Table B–10: MODBUS MEMORY MAP (Sheet 38 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...