5-214
C60 Breaker Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
SELECTOR 1 FUNCTION:
“Enabled”
SELECTOR 1 3BIT A0:
“CONT IP 1 ON”
SELECTOR 1 FULL-RANGE:
“4”
SELECTOR 1 3BIT A1:
“CONT IP 2 ON”
SELECTOR 1 STEP-UP MODE:
“Time-out”
SELECTOR 1 3BIT A2:
“CONT IP 3 ON”
SELECTOR 1 TIME-OUT:
“5.0 s”
SELECTOR 1 3BIT MODE:
“Time-out”
SELECTOR 1 STEP-UP:
“PUSHBUTTON 1 ON”
SELECTOR 1 3BIT ACK:
“Off”
SELECTOR 1 ACK:
“Off”
SELECTOR 1 POWER-UP MODE:
“Synchronize”
Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the
SETTINGS
INPUTS/OUTPUTS
CONTACT OUTPUTS
menu:
OUTPUT H1 OPERATE:
“SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE:
“SELECTOR 1 BIT 1"
OUTPUT H3 OPERATE:
“SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the
SETTINGS
PRODUCT
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1
menu:
PUSHBUTTON 1 FUNCTION:
“Self-reset”
PUSHBUTTON 1 DROP-OUT TIME:
“0.10 s”
The logic for the selector switch is shown below:
Figure 5–94: SELECTOR SWITCH LOGIC
842012A2.CDR
step up
acknowledge
3-bit position out
ON
FLEXLOGIC™ OPERANDS
SELECTOR 1 POS 1
SELECTOR 1 POS 2
SELECTOR 1 POS 3
SELECTOR 1 POS 4
SELECTOR 1 POS 5
SELECTOR 1 POS 6
SELECTOR 1 POS 7
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
FLEXLOGIC™ OPERANDS
RUN
SELECTOR 1 POWER-UP MODE:
SETTINGS
SELECTOR 1 TIME-OUT:
SELECTOR 1 STEP-UP MODE:
SELECTOR 1 FULL RANGE:
SELECTOR 1 STEP-UP:
Off = 0
SELECTOR 1 FUNCTION:
SETTINGS
Enabled = 1
SELECTOR 1 ACK:
Off = 0
SELECTOR 1 3BIT A0:
Off = 0
SELECTOR 1 3BIT A1:
Off = 0
SELECTOR 1 3BIT A2:
Off = 0
SELECTOR 1 3BIT ACK:
Off = 0
3-bit acknowledge
SELECTOR 1 POSITION
ACTUAL VALUE
2
1
3
4
5
6
7
SELECTOR 1 3BIT MODE:
SELECTOR 1 PWR ALARM
thr
ee-bit
contr
ol
input
OR
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...