B-20
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Synchrocheck Actual Values (Read Only) (4 modules)
2400
Synchrocheck 1 Delta Voltage
-1000000000000 to
1000000000000
V
1
F060
0
2402
Synchrocheck 1 Delta Frequency
0 to 655.35
Hz
0.01
F001
0
2403
Synchrocheck 1 Delta Phase
0 to 180 (not 0 to 359.9)
degrees
0.1
F001
0
2404
...Repeated for Synchrocheck 2
2408
...Repeated for Synchrocheck 3
240C
...Repeated for Synchrocheck 4
Autoreclose Status (Read Only)
2410
Autoreclose 1 Count
0 to 65535
---
1
F001
0
Field Unit Raw Data Settings (Read/Write Setting)
2460
Field Raw Data Port
0 to 7
---
1
F244
6 (H1a)
2461
Field Raw Data Freeze
0 to 1
---
1
F102
0 (Disabled)
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 modules)
2540
Remote Double-point Status Input 1 Device
1 to 32
---
1
F001
1
2541
Remote Double-point Status Input 1 Item
0 to 64
---
1
F606
0 (None)
2542
Remote Double-point Status Input 1 Name
1 to 64
---
1
F205
"RemDPS Ip 1"
2548
Remote Double-point Status Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
2549
... Repeated for Remote Double-point Status Input 2
2552
... Repeated for Remote Double-point Status Input 3
255B
... Repeated for Remote Double-point Status Input 4
2564
... Repeated for Remote Double-point Status Input 5
Phasor Measurement Unit Actual Values (Read Only) (2 modules)
256D
PMU 1 Phase A Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
256F
PMU Unit 1 Phase A Voltage Angle
-180 to 180
°
0.01
F002
0
2570
PMU 1 Phase B Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2572
PMU 1 Phase B Voltage Angle
-180 to 180
°
0.01
F002
0
2573
PMU 1 Phase C Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2575
PMU 1 Phase C Voltage Angle
-180 to 180
°
0.01
F002
0
2576
PMU 1 Auxiliary Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2578
PMU 1 Auxiliary Voltage Angle
-180 to 180
°
0.01
F002
0
2579
PMU 1 Positive Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
257B
PMU 1 Positive Sequence Voltage Angle
-180 to 180
°
0.01
F002
0
257C
PMU 1 Negative Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
257E
PMU 1 Negative Sequence Voltage Angle
-180 to 180
°
0.01
F002
0
257F
PMU 1 Zero Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2581
PMU 1 Zero Sequence Voltage Angle
-180 to 180
°
0.01
F002
0
2582
PMU 1 Phase A Current Magnitude
0 to 999999.999
A
0.001
F060
0
2584
PMU 1 Phase A Current Angle
-180 to 180
°
0.01
F002
0
2585
PMU 1 Phase B Current Magnitude
0 to 999999.999
A
0.001
F060
0
2587
PMU 1 Phase B Current Angle
-180 to 180
°
0.01
F002
0
2588
PMU 1 Phase C Current Magnitude
0 to 999999.999
A
0.001
F060
0
258A
PMU 1 Phase C Current Angle
-180 to 180
°
0.01
F002
0
258B
PMU 1 Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
258D
PMU 1 Ground Current Angle
-180 to 180
°
0.01
F002
0
258E
PMU 1 Positive Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
2590
PMU 1 Positive Sequence Current Angle
-180 to 180
°
0.01
F002
0
2591
PMU 1 Negative Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
2593
PMU 1 Negative Sequence Current Angle
-180 to 180
°
0.01
F002
0
2594
PMU 1 Zero Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
2596
PMU 1 Zero Sequence Current Angle
-180 to 180
°
0.01
F002
0
2597
PMU 1 Frequency
2 to 90
Hz
0.001
F003
0
2599
PMU 1 df/dt
-327.67 to 327.67
Hz/s
0.01
F002
0
259A
PMU 1 Configuration Change Counter
0 to 65535
---
1
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 12 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...