GE Multilin
C60 Breaker Protection System
B-51
APPENDIX B
B.4 MEMORY MAPPING
B
993D
Breaker Restrike 1 Target
0 to 2
---
1
F109
0 (Self-reset)
993E
Breaker Restrike 1 Events
0 to 1
---
1
F102
0 (Disabled)
993F
Reserved (2 items)
---
---
---
F002
0
9941
...Repeated for Breaker Restrike 2
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9980
Teleprotection Clear Lost Packets
0 to 1
---
1
F126
0 (No)
Teleprotection Inputs/Outputs (Read/Write Settings)
9990
Teleprotection Function
0 to 1
---
1
F102
0 (Disabled)
9991
Teleprotection Number of Terminals
2 to 3
---
1
F001
2
9992
Teleprotection Number of Channels
1 to 2
---
1
F001
1
9993
Teleprotection Local Relay ID
0 to 255
---
1
F001
0
9994
Teleprotection Terminal 1 ID
0 to 255
---
1
F001
0
9995
Teleprotection Terminal 2 ID
0 to 255
---
1
F001
0
9996
Reserved (10 items)
0 to 1
---
1
F001
0
9A00
Teleprotection Input 1-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9A10
Teleprotection Input 2-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9A20
Teleprotection Output 1-n Operand (16 items)
0 to 4294967295
---
1
F300
0
9A40
Teleprotection Output 2-n Operand (16 items)
0 to 4294967295
---
1
F300
0
Teleprotection Channel Tests (Read Only)
9AA0
Teleprotection Channel 1 Status
0 to 2
---
1
F134
1 (OK)
9AA1
Teleprotection Channel 1 Number of Lost Packets
0 to 65535
---
1
F001
0
9AA2
Teleprotection Channel 2 Status
0 to 2
---
1
F134
2 (n/a)
9AA3
Teleprotection Channel 2 Number of Lost Packets
0 to 65535
---
1
F001
0
9AA4
Teleprotection Network Status
0 to 2
---
1
F134
2 (n/a)
9AAF
Teleprotection Channel 1 Input States
0 to 1
---
1
F500
0
9AB0
Teleprotection Channel 2 Input States
0 to 1
---
1
F500
0
9AC0
Teleprotection Input 1 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
9AD0
Teleprotection Input 2 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
VT Fuse Failure (Read/Write Setting) (4 modules)
A09A
VT Fuse Failure1 Function
0 to 1
---
1
F102
0 (Disabled)
A09B
VT Fuse Failure Neutral Wire Open1 Function
0 to 1
---
1
F102
0 (Disabled)
A09C
VT Fuse Failure Neutral Wire Open 1 3rd Harmonic Pickup
0 to 3
pu
0.001
F001
100
A09D
...Repeated for module number 2
A0A0
...Repeated for module number 3
A0A3
...Repeated for module number 4
VT Fuse Failure Actuals (Read Only) (4 modules)
A0AC
VT Fuse Failure 1 V0 3rd Harmonic
0 to 999999.999
V
0.001
F060
0
A0AE
...Repeated for module number 2
A0B0
...Repeated for module number 3
A0B2
...Repeated for module number 4
Selector Switch Actual Values (Read Only)
A210
Selector Switch 1 Position
1 to 7
---
1
F001
0
A211
Selector Switch 2 Position
1 to 7
---
1
F001
1
Selector Switch Settings (Read/Write) (2 modules)
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
A281
Selector 1 Range
1 to 7
---
1
F001
7
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
A283
Selector 1 Step Up
0 to 4294967295
---
1
F300
0
A285
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
A286
Selector 1 Acknowledge
0 to 4294967295
---
1
F300
0
A288
Selector 1 Bit0
0 to 4294967295
---
1
F300
0
A28A
Selector 1 Bit1
0 to 4294967295
---
1
F300
0
A28C
Selector 1 Bit2
0 to 4294967295
---
1
F300
0
A28E
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
Table B–10: MODBUS MEMORY MAP (Sheet 43 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...