GE Multilin
C60 Breaker Protection System
5-207
5 SETTINGS
5.7 CONTROL ELEMENTS
5
Figure 5–90: TRIP BUS LOGIC
5.7.3 SETTING GROUPS
PATH: SETTINGS
CONTROL ELEMENTS
SETTINGS GROUPS
SETTING GROUPS
SETTING GROUPS
FUNCTION: Enabled
Range: Disabled, Enabled
MESSAGE
SETTING GROUPS BLK:
Off
Range: FlexLogic operand
MESSAGE
GROUP 2 ACTIVATE ON:
Off
Range: FlexLogic operand
MESSAGE
GROUP 3 ACTIVATE ON:
Off
Range: FlexLogic operand
↓
MESSAGE
GROUP 6 ACTIVATE ON:
Off
Range: FlexLogic operand
MESSAGE
GROUP 1 NAME:
Range: up to 16 alphanumeric characters
MESSAGE
GROUP 2 NAME:
Range: up to 16 alphanumeric characters
↓
MESSAGE
GROUP 6 NAME:
Range: up to 16 alphanumeric characters
MESSAGE
SETTING GROUP
EVENTS: Disabled
Range: Disabled, Enabled
***
SETTINGS
= Off
TRIP BUS 1 INPUT 2
= Off
TRIP BUS 1 INPUT 1
= Off
TRIP BUS 1 INPUT 16
OR
SETTINGS
= Enabled
TRIP BUS 1
FUNCTION
= Off
TRIP BUS 1 BLOCK
AND
AND
Latch
S
R
Non-volatile,
set-dominant
SETTINGS
= Enabled
TRIP BUS 1
LATCHING
= Off
TRIP BUS 1 RESET
FLEXLOGIC OPERAND
TRIP BUS 1 PKP
OR
SETTINGS
TRIP BUS 1 PICKUP
DELAY
TRIP BUS 1 RESET
DELAY
T
PKP
T
RST
FLEXLOGIC OPERAND
RESET OP
FLEXLOGIC OPERAND
TRIP BUS 1 OP
842023A1.CDR
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...