GE Multilin
C60 Breaker Protection System
5-47
5 SETTINGS
5.2 PRODUCT SETUP
5
–
Set
REMOTE DEVICE 1 ETYPE APPID
to match the ETHERTYPE application ID from the transmitting device. This is
“0” in the example above.
–
Set the
REMOTE DEVICE 1 DATASET
value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3.
Configure the Boolean data by making the following changes in the
INPUTS/OUTPUTS
REMOTE INPUTS
REMOTE
INPUT 1
settings menu:
–
Set
REMOTE IN 1 DEVICE
to “GOOSEOut_1”.
–
Set
REMOTE IN 1 ITEM
to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
4.
Configure the analog data by making the following changes in the
INPUTS/OUTPUTS
IEC 61850 GOOSE ANALOG
INPUTS
settings menu:
–
Set the
IEC61850 GOOSE ANALOG INPUT 1 DEFAULT VALUE
to “60.000”.
–
Enter “Hz” for the
IEC61850 GOOSE ANALOG INPUT 1 UNITS
setting.
The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The C60 must be
rebooted (control power removed and re-applied) before these settings take effect.
The value of GOOSE analog input 1 in the receiving device will be determined by the MMXU1.MX.Hz.mag.f value in the
sending device. This MMXU value is determined by the source 1 frequency value and the MMXU Hz deadband setting of
the sending device.
Remote input 1 can now be used in FlexLogic equations or other settings. The C60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
For intercommunication between C60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the
C60 (DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN
support).
Set the
CONFIG GSE 1 FUNCTION
function to “Disabled” when configuration changes are required. Once changes are
entered, return the
CONFIG GSE 1 FUNCTION
to “Enabled” and restart the unit for changes to take effect.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
CONFIGURABLE GOOSE
CONFIGURABLE GOOSE 1(8)
CONFIG GSE 1(64) DATA ITEMS
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: “GGIO1.ST.Ind1.stVal” and “GGIO1.ST.Ind1.q”. The C60 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.
CONFIG GSE 1
DATASET ITEMS
ITEM 1:
GGIO1.ST.Ind1.stVal
Range: all valid MMS data item references for
transmitted data
MESSAGE
ITEM 2:
GGIO1.ST.IndPos1.stV
Range: all valid MMS data item references for
transmitted data
MESSAGE
ITEM 3:
None
Range: all valid MMS data item references for
transmitted data
↓
MESSAGE
ITEM 64:
None
Range: all valid MMS data item references for
transmitted data
NOTE
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...