B-34
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
438E
...Repeated for Route 6
Installation (Read/Write Setting)
43E0
Relay Programmed State
0 to 1
---
1
F133
0 (Not
Programmed)
43E1
Relay Name
---
---
---
F202
“Relay-1”
User Programmable Self Tests (Read/Write Setting)
4441
User Programmable Detect Ring Break Function
0 to 1
---
1
F102
1 (Enabled)
4442
User Programmable Direct Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4443
User Programmable Remote Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4444
User Programmable First Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4445
User Programmable Secondary Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4446
User Programmable Battery Fail Function
0 to 1
---
1
F102
1 (Enabled)
4447
User Programmable SNTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
4448
User Programmable IRIG-B Fail Function
0 to 1
---
1
F102
1 (Enabled)
4449
User Programmable Ethernet Switch Fail Function
0 to 1
---
1
F102
1 (Enabled)
444A
Process Bus Failure Operand
0 to 4294967295
---
1
F300
0
444C
PTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
444D
User Programmable Third Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
444E
User Programmable SFP Fail Function
0 to 1
---
1
F102
0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480
Phase CT 1 Primary
1 to 65000
A
1
F001
1
4481
Phase CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4482
Ground CT 1 Primary
1 to 65000
A
1
F001
1
4483
Ground CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4484
...Repeated for CT Bank 2
4488
...Repeated for CT Bank 3
448C
...Repeated for CT Bank 4
4490
...Repeated for CT Bank 5
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (6 modules)
4500
Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
4501
Phase VT 1 Secondary
25 to 240
V
0.1
F001
664
4502
Phase VT 1 Ratio
1 to 24000
:1
1
F060
1
4504
Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
4505
Auxiliary VT 1 Secondary
25 to 240
V
0.1
F001
664
4506
Auxiliary VT 1 Ratio
1 to 24000
:1
1
F060
1
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
4518
...Repeated for VT Bank 4
4520
...Repeated for VT Bank 5
4528
...Repeated for VT Bank 6
Source Settings (Read/Write Setting) (4 modules)
4580
Source 1 Name
0 to 1
---
1
F206
“SRC 1"
4583
Source 1 Phase CT
0 to 63
---
1
F400
0
4584
Source 1 Ground CT
0 to 63
---
1
F400
0
4585
Source 1 Phase VT
0 to 63
---
1
F400
0
4586
Source 1 Auxiliary VT
0 to 63
---
1
F400
0
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
Power System (Read/Write Setting)
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
4602
Frequency and Phase Reference
0 to 5
---
1
F167
0 (SRC 1)
Table B–10: MODBUS MEMORY MAP (Sheet 26 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...