B-80
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F143
UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number)
A bit value of 0 = no error, 1 = error
F144
ENUMERATION: FORCED CONTACT INPUT STATE
0 = Disabled, 1 = Open, 2 = Closed
F146
ENUMERATION: MISCELLANEOUS EVENT CAUSES
11
Equipment Mismatch
12
Process Bus Failure
13
Unit Not Programmed
14
System Exception
15
Latching Output Discrepancy
17
Maintenance Alert 01
18
SNTP Failure
19
Maintenance Alert
20
Maintenance Alert
21
Maintenance Alert
22
Temperature Monitor
23
Process Bus Trouble
24
Brick Trouble
25
Field RTD Trouble
26
Field TDR Trouble
27
Remote Device Offline
28
Direct Device Offline
29
Maintenance Alert
30
Any Minor Error
31
Any Major Error
33
Maintenance Alert
64
Maintenance Alert
65
IEC 61850 Data Set
66
Aggregator Error
67
Unit Not Calibrated
68
Settings Save Error
69
SRAM Data Error
70
Program Memory
71
Watchdog Error
72
Low On Memory
73
Prototype Firmware
74
Module Failure 01
75
Module Failure 02
76
Module Failure 03
77
Module Failure 04
78
Module Failure 05
79
Module Failure 06
80
Module Failure 07
81
Module Failure 08
82
Module Failure 09
83
Incompatible H/W
84
Module Failure 10
85
Module Failure 11
86
Module Failure 12
87
High ENET Traffic
89
Relay Restart
90
FGM Failure
91
FGM Failure
92
FGM Failure
93
FGM Failure
94
FGM Failure
95
FGM Error
96
Maintenance Alert
Bitmask
Error
97
PHY Monitor
98
Storage Media Alarm
99
Wrong Transceiver
100
Power Supply Warning
Bitmask
Definition
0
Events Cleared
1
Oscillography Triggered
2
Date/time Changed
3
Default Settings Loaded
4
Test Mode Forcing On
5
Test Mode Forcing Off
6
Power On
7
Power Off
8
Relay In Service
9
Relay Out Of Service
10
Watchdog Reset
11
Oscillography Clear
12
Reboot Command
13
Led Test Initiated
14
Flash Programming
15
Fault Report Trigger
16
User Programmable Fault Report Trigger
17
---
18
Reload CT/VT module Settings
19
---
20
Ethernet Port 1 Offline
21
Ethernet Port 2 Offline
22
Ethernet Port 3 Offline
23
Ethernet Port 4 Offline
24
Ethernet Port 5 Offline
25
Ethernet Port 6 Offline
26
Test Mode Isolated
27
Test Mode Forcible
28
Test Mode Disabled
29
Temperature Warning On
30
Temperature Warning Off
31
Unauthorized Access
32
System Integrity Recovery
33
System Integrity Recovery 06
Bitmask
Error
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...