GE Multilin
C60 Breaker Protection System
5-91
5 SETTINGS
5.2 PRODUCT SETUP
5
An example user display setup and result is shown below:
If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the
bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items
are different.
5.2.17 DIRECT INPUTS AND OUTPUTS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
DIRECT I/O
USER DISPLAY 1
DISP 1 TOP LINE:
Current X ~
A
Shows user-defined text with first tilde marker.
MESSAGE
DISP 1 BOTTOM LINE:
Current Y ~
A
Shows user-defined text with second tilde marker.
MESSAGE
DISP 1 ITEM 1:
6016
Shows decimal form of user-selected Modbus register
address, corresponding to first tilde marker.
MESSAGE
DISP 1 ITEM 2:
6357
Shows decimal form of user-selected Modbus register
address, corresponding to second tilde marker.
MESSAGE
DISP 1 ITEM 3:
0
This item is not being used. There is no corresponding
tilde marker in top or bottom lines.
MESSAGE
DISP 1 ITEM 4:
0
This item is not being used. There is no corresponding
tilde marker in top or bottom lines.
MESSAGE
DISP 1 ITEM 5:
0
This item is not being used. There is no corresponding
tilde marker in top or bottom lines.
USER
DISPLAYS
→
Current X 0.850
Current Y 0.327 A
Shows the resultant display content.
DIRECT I/O
DIRECT OUTPUT
DEVICE ID: 1
Range: 1 to 16
MESSAGE
DIRECT I/O CH1 RING
CONFIGURATION: Yes
Range: Yes, No
MESSAGE
DIRECT I/O CH2 RING
CONFIGURATION: Yes
Range: Yes, No
MESSAGE
DIRECT I/O DATA
RATE: 64 kbps
Range: 64 kbps, 128 kbps
MESSAGE
DIRECT I/O CHANNEL
CROSSOVER: Disabled
Range: Disabled, Enabled
MESSAGE
CRC ALARM CH1
MESSAGE
CRC ALARM CH2
MESSAGE
UNRETURNED
MESSAGES ALARM CH1
MESSAGE
UNRETURNED
MESSAGES ALARM CH2
NOTE
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...