5-220
C60 Breaker Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
5.7.6 AUTORECLOSE (ANSI 79)
PATH: SETTINGS
CONTROL ELEMENTS
AUTORECLOSE
AUTORECLOSE
AUTORECLOSE
AR FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
AR MODE:
Mode 1 (1 & 3 Pole)
Range: Mode 1(1 & 3 Pole), Mode 2 (1 Pole), Mode 3 (3
Pole-A), Mode 4 (3 Pole-B)
MESSAGE
Mode 1 Activation:
Off
Range: FlexLogic operand
MESSAGE
Mode 2 Activation:
Off
Range: FlexLogic operand
MESSAGE
Mode 3 Activation:
Off
Range: FlexLogic operand
MESSAGE
Mode 4 Activation:
Off
Range: FlexLogic operand
MESSAGE
AR MAX NUMBER OF
SHOTS: 2
Range: 1, 2, 3, 4
MESSAGE
AR INITIATE MODE:
Protection AND CB
Range: Protection AND CB, Protection Only
MESSAGE
AR BLOCK BKR1:
Off
Range: FlexLogic operand
MESSAGE
AR CLOSE TIME BKR 1:
0.10 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR BKR MAN CLOSE:
Off
Range: FlexLogic operand
MESSAGE
AR BLK TIME UPON MAN
CLS:
10.00 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 1P INIT:
Off
Range: FlexLogic operand
MESSAGE
AR 3P INIT:
Off
Range: FlexLogic operand
MESSAGE
AR 3P TD INIT:
Off
Range: FlexLogic operand
MESSAGE
AR MULTI-P FAULT:
Off
Range: FlexLogic operand
MESSAGE
BKR ONE POLE OPEN:
Off
Range: FlexLogic operand
MESSAGE
BKR 3 POLE OPEN:
Off
Range: FlexLogic operand
MESSAGE
AR 3-P DEAD TIME 1:
0.50 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 2:
1.20 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 3:
2.00 s
Range: 0.00 to 655.35 s in steps of 0.01
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...