5 SETTINGS
5.4 SYSTEM SETUP
5
The trigger responds to the frequency signal of the phasor measurement unit (PMU) source. The frequency is calculated
from among phase voltages, auxiliary voltage, phase currents and ground current, in this hierarchy, depending on the
source configuration as per C60 standards. This element requires that the frequency be above the minimum measurable
value. If the frequency is below this value, such as when the circuit is de-energized, the trigger drops out.
•
PMU 1 FREQ TRIGGER LOW-FREQ
: This setting specifies the low threshold for the abnormal frequency trigger. The
comparator applies a 0.02 Hz hysteresis.
•
PMU 1 FREQ TRIGGER HIGH-FREQ
: This setting specifies the high threshold for the abnormal frequency trigger. The
comparator applies a 0.02 Hz hysteresis.
•
PMU 1 FREQ TRIGGER PKP TIME
: This setting can be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
•
PMU 1 FREQ TRIGGER DPO TIME
: This setting can be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
Figure 5–48: FREQUENCY TRIGGER SCHEME LOGIC
g) VOLTAGE TRIGGERING
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT...
PMU 1(2) TRIGGERING
PMU 1(2) VOLTAGE TRIGGER
PMU 1 VOLTAGE
TRIGGER
PMU 1 VOLT TRIGGER
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
PMU 1 VOLT TRIGGER
LOW-VOLT: 0.800 pu
Range: 0.250 to 1.250 pu in steps of 0.001
MESSAGE
PMU 1 VOLT TRIGGER
HIGH-VOLT: 1.200 pu
Range: 0.750 to 1.750 pu in steps of 0.001
MESSAGE
PMU 1 VOLT TRIGGER
PKP TIME: 0.10 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PMU 1 VOLT TRIGGER
DPO TIME: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PMU 1 VOLT TRIG BLK:
Off
Range: FlexLogic operand
MESSAGE
PMU 1 VOLT TRIGGER
TARGET: Self-Reset
Range: Self-Reset, Latched, Disabled
MESSAGE
PMU 1 VOLT TRIGGER
EVENTS: Disabled
Range: Enabled, Disabled
SETTINGS
PMU 1 FREQ TRIGGER
FUNCTION:
Enabled = 1
PMU 1 FREQ TRIG BLK:
Off = 0
SETTING
PMU 1 SIGNAL
SOURCE:
FREQUENCY, f
AND
SETTINGS
PMU 1 FREQ TRIGGER LOW-FREQ:
PMU 1 FREQ TRIGGER HIGH-FREQ:
0< f < LOW-FREQ
OR
f > HIGH-FREQ
RUN
SETTINGS
PMU 1 FREQ TRIGGER PKP TIME:
PMU 1 FREQ TRIGGER DPO TIME:
t
DPO
FLEXLOGIC OPERAND
PMU 1 FREQ TRIGGER
FLEXLOGIC OPERANDS
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER
PMU 1 ROCOF TRIGGER
SETTING
PMU 1 USER TRIGGER:
Off = 0
OR
FLEXLOGIC OPERAND
PMU 1 TRIGGERED
to STAT bits of
the data frame
847008A1.CDR
SETTINGS
PKP
t
0
0
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...