GE Multilin
C60 Breaker Protection System
6-7
6 ACTUAL VALUES
6.2 STATUS
6
b) STATISTICS
PATH: ACTUAL VALUES
STATUS
REMOTE DEVICES STATISTICS
REMOTE DEVICE 1(16)
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The
STNUM
number is obtained from the indicated remote device and increments whenever a change of state of at least
one item occurs in the GSSE/GOOSE message. The
SQNUM
number is obtained from the indicated remote device and
increments whenever a GSSE/GOOSE message, without a state change, is sent. When the GSSE/GOOSE message
trasmits a state change, the
SQNUM
resets to 0. This number rolls over to zero when a count of 4,294,967,295 is incre-
mented.
6.2.10 DIGITAL COUNTERS
PATH: ACTUAL VALUES
STATUS
DIGITAL COUNTERS
DIGITAL COUNTERS Counter 1(8)
The present status of the eight digital counters is shown here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date and
time stamp for the frozen count. The
COUNTER 1 MICROS
value refers to the microsecond portion of the time stamp.
6.2.11 SELECTOR SWITCHES
PATH: ACTUAL VALUES
STATUS
SELECTOR SWITCHES
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
REMOTE DEVICE 1
REMOTE DEVICE 1
StNum: 0
MESSAGE
REMOTE DEVICE 1
SqNum: 0
DIGITAL COUNTERS
Counter 1
Counter 1
ACCUM:
0
MESSAGE
Counter 1
FROZEN:
0
MESSAGE
Counter 1
FROZEN:
YYYY/MM/DD HH:MM:SS
MESSAGE
Counter 1
MICROS:
0
SELECTOR SWITCHES
SELECTOR SWITCH 1
POSITION: 0/7
Range: Current Position / 7
MESSAGE
SELECTOR SWITCH 2
POSITION: 0/7
Range: Current Position / 7
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...