2-26
C60 Breaker Protection System
GE Multilin
2.4 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.8 COMMUNICATION PROTOCOLS
RS232
Front port:
19.2 kbps, Modbus RTU
RS485
1 rear port:
Up to 115 kbps, Modbus RTU, DNP 3,
IEC 60870-5-103
Typical distance:
1200 m
Isolation:
2 kV, isolated together at 36 Vpk
FIBER ETHERNET PORT
ETHERNET (10/100 MB TWISTED PAIR)
Modes:
10 MB, 10/100 MB (auto-detect)
Connector:
RJ45
SIMPLE NETWORK TIME PROTOCOL (SNTP)
clock synchronization error: <10 ms (typical)
PRECISION TIME PROTOCOL (PTP)
PTP IEEE Std 1588
2008 (version 2)
Power Profile (PP) per IEEE Standard PC37.238TM2011
Slave-only ordinary clock
Peer delay measurement mechanism
PARALLEL REDUNDANCY PROTOCOL (PRP)
(IEC 62439-3 CLAUSE 4, 2012)
Ethernet ports used:
2 and 3
Networks supported:
10/100 MB Ethernet
OTHER
TFTP, HTTP, IEC 60870-5-104, Ethernet Global Data (EGD)
2.4.9 INTER-RELAY COMMUNICATIONS
SHIELDED TWISTED-PAIR INTERFACE OPTIONS
RS422 distance is based on transmitter power and
does not take into consideration the clock source
provided by the user.
LINK POWER BUDGET AND MAXIMUM OPTICAL INPUT POWER
PARAMETER
FIBER TYPE
100 MB MULTI-
MODE
Wavelength
1310 nm
Connector
LC
Transmit power
–20 dBm
Receiver sensitivity
–30 dBm
Power budget
10 dB
Maximum input
power
–14 dBm
Typical distance
2 km
Full duplex
yes
Redundancy
yes
INTERFACE TYPE
TYPICAL DISTANCE
RS422
1200 m
G.703
100 m
NOTE
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...