17 Advanced functions
17.4 Upper limit of the flow velocity
FLUXUS F60*
2017-10-16, UMFLUXUSF60xV5-0EN
154
• Enter the time after which the transmitter has to toggle from the TransitTime mode back
to the NoiseTrek mode if there are no valid measured values.
• Press ENTER.
In order to manually toggle between the TransitTime and the NoiseTrek mode during the
measurement, press key
when the measuring mode is displayed.
17.4
Upper limit of the flow velocity
Single outliers caused by heavily disturbed surroundings can appear among the mea-
sured values of the flow velocity. If these outliers are not ignored, they will affect all de-
rived physical quantities, which will be unsuitable for the integration (e.g., pulse outputs).
It is possible to ignore all measured flow velocities exceeding the preset upper limit.
These measured values will be marked as outliers.
The upper limit of the flow velocity is set in
Special Funct.\SYSTEM settings\
Measuring\Velocity limit
.
• Enter zero to switch off the outliers check.
• Enter a limit > 0 to switch on the outliers check. The measured flow velocity will then be
compared to the entered upper limit.
• Press ENTER.
Special Funct.\...\Auto NoiseTrek\Keep TT |For checking
Example
TT-Failed
NoiseTrek: After 40s
NT-Failed
TransTime: After 60s
NT-Ok,but check TT: Each 300s
Keep TT checking: For 5s
If no measurement is possible in the TransitTime mode within 40 s, the transmitter tog-
gles to the NoiseTrek mode. If no measurement is possible in the NoiseTrek mode
within 60 s, the transmitter toggles back to the TransitTime mode.
If valid measured values are obtained during the measurement in the NoiseTrek mode,
the transmitter toggles to the TransitTime mode every 300 s. If no measurement is
possible in the TransitTime mode for the duration of 5 s, the transmitter toggles back to
the NoiseTrek mode. If a valid measured value is obtained in the TransitTime mode
within 5 s, the transmitter continues the measurement in the TransitTime mode.