17 Advanced functions
FLUXUS F60*
17.1 Totalizers
149
UMFLUXUS_F60xV5-0EN, 2017-10-16
17
Advanced functions
17.1
Totalizers
The heat quantity, total volume or total mass of the fluid at the measuring point can be
determined.
There are 2 totalizers, one for the positive and other for the negative flow direction. The
unit of measurement used for totalizing corresponds to the heat, volume or mass unit se-
lected for the physical quantity.
The totalizer values can be displayed with up to 11 places, e.g.,
74890046.03
. For the
adjustment of the decimal places (max. 4), see section 18.7.
Tab. 17.1: Functions to display the totalizers
activation
press key
during the measurement
deactivation
press key
3 times during the measurement
display of the flow totalizer for the positive
flow direction
press key
during the measurement
display of the flow totalizer for the negative
flow direction
press key
during the measurement
toggling of totalizer display between
positive and negative flow direction
Select
Special Funct.\SYSTEM settings\
Measuring\Toggle totalizer
.
Enter a time interval between 0 (off) and 5 s.
reset of the totalizers to zero
press key
3 times during the measurement
Notice!
The totalizers can only be activated for the measuring channel whose measured values
are currently displayed.
Notice!
A keystroke will only influence the flow totalizers if the flow totalizer is displayed in
the upper line.