16 Data transmission
FLUXUS F60*
16.5 Online transmission of data to a terminal program
145
UMFLUXUS_F60xV5-0EN, 2017-10-16
• Set the transmission parameters in the 3 scroll lists. Press ENTER.
–
baud
: baud rate
–
parity
: parity
–
st
: number of stop bits
The default transmission parameters will be set if
default
is selected and the transmis-
sion parameters have not been changed.
16.5
Online transmission of data to a terminal program
• Start the terminal program.
• Enter the transmission parameters into the terminal program, see section 16.4. The
transmission parameters of the terminal program and the transmitter have to be identical.
Transmitter settings
• Select the program branch
Output Options
.
• Press ENTER.
• Select the channel for which the online transmission is to be activated.
• Press ENTER until the menu item
Serial Output
is displayed.
• Select
yes
to activate the online transmission.
• Press ENTER.
• Enter the storage rate.
• Start the measurement.
Output Options\for Channel A:
Output Options\...\Serial Output
Output Options\...\Serial Output\SEND ONLINE-HEAD
BAUD< parity st
9600 EVEN
1