4. Commissioning
4-96
Festo P.BE-SBO-Q-EN en 1602e
Fig. 4/29: Selecting the Ethernet module
3. Enter the following values in the dialogue for the new
module and select “OK”.
Input field
Explanation
Value
Name
Name of fieldbus node
freely selectable
Description
Description
freely selectable
Comm Format
Communication format
Data - INT
IP Address
IP address of the Compact Vision
System
e.g. 192.168.2.10
Connection parameters
– Assembly Instance Input
– Size
– Instance for inputs
– Size
769
2 (2 x 16 bit)
– Assembly Instance Output
– Size
– Instance for outputs
– Size
770
1 (1 x 16 bit)
– Assembly Instance Configuration
– Size
– Instance for configuration data
– Size
771
0 (0 x 16 bit)