Diagnostic messages
278
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
Error group 84
Conditions for controller enabled
No.
Code
Message
Reaction
84-0
-
Conditions for controller enable not fulfilled
Warn
Cause
One or more conditions for controller enable are not fulfilled. This
includes:
–
DIN4 (output stage enable) is off.
–
DIN5 (controller enable) is off.
–
Intermediate circuit not yet loaded.
–
Encoder is not yet ready for operation.
–
Angle encoder identification is still active.
–
Automatic current regulator identification is still active.
–
Encoder data are invalid.
–
Status change of the safety function not yet completed.
–
Firmware or DCO download via Ethernet (TFTP) active.
–
DCO download onto memory card still active.
–
Firmware download via Ethernet active.
Measure
Check status of digital inputs.
Check encoder cables.
Wait for automatic identification.
Wait for completion of the firmware or DCO download.
Error group 90
Internal error
No.
Code
Message
Reaction
90-0
5080h
External RAM not recognized
PSoff
Cause
External SRAM not detected / not sufficient.
Hardware error (SRAM component or board is faulty).
Measure
Please contact Technical Support.
90-2
5080h
Error at FPGA boot-up
PSoff
Cause
The FPGA (hardware) cannot be booted. The FPGA is booted seri
ally when the device is started, but in this case it could not be
loaded with data or it reported a checksum error.
Measure
Switch on the device again (24 V). If the error occurs again, the
hardware is faulty.
90-3
5080h
Error at SD-ADU start
PSoff
Cause
SD-ADUs (hardware) cannot be started. One or more SD-ADUs are
not supplying any serial data.
Measure
Switch on the device again (24 V). If the error occurs again, the
hardware is faulty.