Diagnostic messages
236
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
Error group 11
Homing
No.
Code
Message
Reaction
11-0
8A80h
Error when homing is started
configurable
Cause
Controller enable missing.
Measure
Homing can only be started when closed-loop controller enable is
active.
Check the condition or sequence.
11-1
8A81h
Error during homing
configurable
Cause
Homing was interrupted, e.g. by:
–
Withdrawal of controller release.
–
Reference switch is beyond the limit switch.
–
External stop signal (a phase was aborted during homing).
Measure
Check homing sequence.
Check arrangement of the switches.
If applicable, lock the stop input during homing if it is not de
sired.
11-2
8A82h
Homing: No valid zero pulse
configurable
Cause
Required zero pulse during homing missing.
Measure
Check the zero pulse signal.
Check the angle encoder settings.
11-3
8A83h
Homing: Timeout
configurable
Cause
The parameterised maximum time for the homing run was ex
ceeded before homing was completed.
Measure
Check the time setting in the parameters.
11-4
8A84h
Homing: Incorrect limit switch
configurable
Cause
–
Associated limit switch not connected.
–
Limit switches swapped?
–
No reference switch found between the two limit switches.
–
Reference switch is on the limit switch.
–
Current position with zero pulse method: Limit switch active in
the area of the zero pulse (not permissible).
–
Both limit switches active at the same time.
Measure
Check whether the limit switches are connected in the correct
direction of travel or whether the limit switches have an effect
on the intended inputs.
Reference switch connected?
Check configuration of the reference switches.
Move limit switch so that it is not in the zero pulse area.
Check limit switch parameterisation (N/C contact/N/O contact.