Diagnostic messages
270
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
Error group 63
EtherCAT (only CMMP-AS-...-M3)
No.
Code
Message
Reaction
63-0
-
EtherCAT: Defective module
configurable
Cause
Error in the hardware.
Measure
Replace the interface and send it to the manufacturer for in
spection.
63-1
-
EtherCAT: Invalid data
configurable
Cause
Faulty telegram type.
Measure
Check the wiring.
63-2
-
EtherCAT: TPDO data has not been read
configurable
Cause
The buffer for sending the data is full.
Measure
The data was sent faster than the motor controller could process it.
Reduce the cycle time on the EtherCAT bus.
63-3
-
EtherCAT: No distributed clocks active
configurable
Cause
Warning: Firmware is synchronising with the telegram, not with the
distributed clocks system. When the EtherCAT was started, no
hardware SYNC (distributed clocks) was found. The firmware now
synchronises with the EtherCAT frame.
Measure
If necessary, check whether the master supports the distrib
uted clocks feature.
Otherwise: Ensure that the EtherCAT frames are not interrupted
by other frames if the Interpolated Position Mode is to be used.
63-4
-
EtherCAT: Missing SYNC message in IPO cycle
configurable
Cause
Telegrams are not being sent in the time slot pattern of the IPO.
Measure
Check responsible participant for distributed clocks.
Error group 64
DeviceNet (only CMMP-AS-...-M3)
No.
Code
Message
Reaction
64-0
-
DeviceNet: Duplicate MAC ID
configurable
Cause
The duplicate MAC-ID check has found two nodes with the same
MAC-ID.
Measure
Change the MAC-ID of one node to an unused value.
64-1
-
DeviceNet: Bus power lost
configurable
Cause
The DeviceNet interface is not supplied with 24 V DC.
Measure
In addition to the motor controller, the DeviceNet interface
must also be connected to 24 V DC.
64-2
-
DeviceNet: RX queue overflow
configurable
Cause
Too many messages received within a short period.
Measure
Reduce the scan rate.