Error group 49
DCO file
No.
Code
Message
Reaction
49-1
-
DCO file: wrong password
QStop
Cause
–
Parameter file with wrong password shall be loaded.
–
Old parameter file (no password defined) should be loaded in
protected motor controller.
Measure
Loading only possible with valid password.
Error group 50
CAN communication
No.
Code
Message
Reaction
50-0
-
Too many synchronous PDOs
configurable
Cause
More PDOs have been activated than can be processed in the un
derlying SYNC interval.
This message also appears if only one PDO is to be transmitted
synchronously, but a high number of other PDOs with a different
transmission type have been activated.
Measure
Check the activation of PDOs.
If the configuration is appropriate, the warning can be suppressed
using error management.
Extend the synchronisation interval.
50-1
-
SDO error has occurred
configurable
Cause
An SDO transfer has caused an SDO abort.
–
Data exceed the range of values.
–
Access to non-existent object.
Measure
Check the command sent.