5
Setting parameters
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
103
5.6
Speed Control
Overview
The parameter set of the motor controller must be adapted for the application. In particular, the ampli
fication is strongly dependent on dimensions that may be connected to the motor. The data must be
optimally determined during commissioning of the system with the help of the parametrisation soft
ware.
Caution
Incorrect setting of the speed regulator parameters can result in strong vibrations and
possibly destroy parts of the system!
Description of the objects
Index
Object
Name
Type
Attr.
60F9
h
RECORD
velocity_control_parameters
rw
2073
h
VAR
velocity_display_filter_time
UINT32
rw
Object 60F9
h
: velocity_control_parameters
The data of the speed controller must be taken from the parametrisation software. The following calcu
lations must be observed:
Amplification of the speed regulator must be multiplied by 256.
With an amplification of 1.5 in the “Speed Regulator” menu of the parametrisation software, the
value384 = 180
h
must be written in the object velocity_control_gain.
The speed regulator time constant is specified in the parametrisation software in milliseconds. To trans
fer this time constant into the velocity_control_time object, it must previously be converted into micro
seconds. With a specified time of 2.0 milliseconds, the corresponding value 2000 is entered in the ob
ject velocity_control_time.
Index
60F9
h
Name
velocity_control_parameter_set
Object Code
RECORD
No. of Elements
3
Sub-Index
01
h
Description
velocity_control_gain
Data Type
UINT16
Access
rw
PDO mapping
no
Units
256 = Gain 1
Value Range
20 … 64*256 (16384)
Default Value
256