B
Diagnostic messages
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
267
Error group 58
Error during communication / parameterisation (only CMMP-AS-...-M3)
No.
Reaction
Message
Code
58-6
80EBh
Cross comparison error processor 1 - 2
configurable
Cause
Timeout during cross-comparison (no data) or cross-comparison
faulty (data for μC1 and μC2 are different).
–
Error in cross-comparison for digital IO.
–
Error in cross-comparison for analogue input.
–
Error in cross-comparison for internal operating voltage meas
urement (5 V, 3.3 V, 24 V) and reference voltage (2.5 V).
–
Error in cross-comparison for SIN/COS angle encoder analogue
values.
–
Error in cross-comparison for programme sequence monitoring.
–
Error in cross-comparison for interrupt counter.
–
Error in cross-comparison for input map.
–
Error in cross-comparison for violation of safety conditions.
–
Error in cross-comparison for temperature measurement.
Measure
This is an internal error in the module that should not occur during
operation.
Check the operating conditions (temperature, air humidity,
condensation).
Check the EMC wiring as specified, screening concept, are
there any external interference sources?
Safety module may be faulty is error resolved after replacing
the module?
Check whether a new firmware for the motor controller or a new
version of the safety module is available from the manufac
turer.
Error group 59
Internal safety module error (only CMMP-AS-...-M3)
No.
Code
Message
Reaction
59-1
80F1h
Failsafe supply/safe pulse inhibitor
configurable
Cause
–
Internal error in module in failsafe supply circuit section or in
the driver supply for the upper and lower switches.
Measure
Module faulty, replace.
59-2
80F2h
External voltage supply error
configurable
Cause
–
Reference voltage 2.5V outside tolerance.
–
Logic supply overv24 V detected.
Measure
Module faulty, replace.
59-3
80F3h
Internal voltage supply error
configurable
Cause
–
Voltage (internal 3.3 V, 5 V, ADU reference) outside the per
missible range.
Measure
Module faulty, replace.