Chapter 8 System Operation
PAGE 8- 44
D-No.109
2
ND
Torque
[Nm]
Setting Range
:
0
~
D-No.100 [Full Scale Torque] ×1.0
The torque value that the speed is shifted from D-No.402 [2
ND
Speed] to D-No.403 [3
RD
Speed].
It is a synchronization point of the 2
nd
STEP prior to commencing a 3 STEP fastening operation.
*Input the same value as D-No.010 [Full Scale Torque] if the 2
ND
Torque is not used as a fastening
control.
D-No.110
Reverse Torque High Limit
[Nm]
Setting Range
:
0
~
D-No.100 [Full Scale Torque] ×1.1
Set the torque high limit during a reverse operation.
If the reverse torque exceeds the D-No.110 [Reverse Torque High Limit] during reverse operation, the
fastening stops and the abnormal signal A.9-8 [Reverse Torque Abnormal] will be generated.
D-No.111
Torque Inhibit Limit
[Nm]
Setting Range
:
0
~
D-No.100 [Full Scale Torque] ×1.1
Limit for ignoring the Torque sensed at the start of fastening (due to large mass inertia or high prevailing
torque applications (self threading / tapping applications)
Torque Inhibit is conducted from fastening start to the D-No.205 [Torque Inhibit Angle] value.
If the torque exceeds D-No.111 [Torque Inhibit Limit] before reaching the D-No.205 [Torque Inhibit Angle]
the fastening result will be REJECT.
D-No.112
1
ST
Rate Start Torque
[Nm]
D-No.113
1
ST
Rate End Torque
[Nm]
Setting Range
:
0
~
D-No.100 [Full Scale Torque] ×1.0
Set the start and end points for measuring 1
ST
Torque Rate.
Judgment of the torque slope (torque vs angle) is performed between D-No.112 [1
ST
Rate Start Torque]
and D-No.113 [1
ST
Rate End Torque].
D-No.114
2
ND
Rate Start Torque
[Nm]
D-No.115
2
ND
Rate End Torque
[Nm]
Setting Range
:
0
~
D-No.100 [Full Scale Torque] ×1.0
Set the start and end points for measuring 2
ND
Torque Rate.
Judgment of the torque slope (torque vs angle) is performed between D-No.114 [2
ND
Rate Start Torque]
and D-No.115 [2
ND
Rate End Torque].
D-No.116
3
RD
Rate Start Torque
[Nm]
D-No.117
3
RD
Rate End Torque
[Nm]
Setting Range
:
0
~
D-No.100 [Full Scale Torque] ×1.0
Set the start and end points for measuring 3
RD
Torque Rate.
Judgement of the torque slope (torque vs angle) is performed between D-No.116 [3
RD
Rate Start Torque]
and D-No.117 [3
RD
Rate End Torque].
Summary of Contents for AFC3000
Page 1: ...AFC3000E HW 1 ...
Page 17: ......
Page 18: ...Chapter 1 Outline PAGE 1 1 Chapter 1 Outline 1 ...
Page 25: ......
Page 26: ...Chapter 2 Specifications PAGE 2 1 Chapter 2 Specifications 2 ...
Page 34: ...Chapter 3 System Description PAGE 3 1 Chapter 3 System Description 3 ...
Page 64: ...Chapter 4 Installation and Wiring PAGE 4 1 Chapter 4 Installation and Wiring 4 ...
Page 131: ...Chapter 4 Installation and Wiring PAGE 4 68 Blank Page ...
Page 132: ...Chapter 5 I O Expansion Unit Page 5 1 Chapter 5 I O Expansion Unit 5 ...
Page 164: ...Chapter 6 Power up and Initial Checks PAGE 6 1 Chapter 6 Power Up and Initial Checks 6 ...
Page 168: ...Chapter 7 Fastening Instructions PAGE 7 1 Chapter 7 Fastening Instructions 7 ...
Page 207: ... Blank Page ...
Page 208: ...Chapter 8 System Operation PAGE 8 1 Chapter 8 System Operation 8 ...
Page 259: ...Chapter 8 System Operation PAGE 8 52 ...
Page 260: ...Chapter 9 Maintenance Inspection PAGE 9 1 Chapter 9 Maintenance Inspection 9 ...
Page 268: ...Chapter 10 Troubleshooting PAGE 10 1 Chapter 10 Troubleshooting 10 ...
Page 294: ......