Automatic functions
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
Note:
There are no automation menus available in version 0.1 of the display software!
Select a name for this fan. A name can be selected for each of the six available
languages (max. 15 characters).
5.5.3. Setting the automatic ventilation
Priority for the fan automation functions:
The fan settings are only activated if there is a fan in automatic mode and the
ventilation block (because of active cooling, object no. 608) is not active.
The highest priority is awarded to the
outdoor temperature block (switched off),
followed by
timed ventilation (activated),
supply air temperature block (switched off) and
night-time re-cooling (switched on).
This means that e.g. timed ventilation or night-time re-cooling will only occur, when
the outdoor temperature exceeds the pre-set value for the outdoor temperature block.
Ventilation automation according to temperature, air humidity or CO
2
content is only
executed if no block applies.
Ventilation settings
Select "Transmit the following parameters: Yes" to render the modifications valid.
Previous settings are then overwritten - including modifications done on the display!
For the
ventilation
you may evaluate the indoor temperature, relative air humidity
and the r CO
2
content of the air in the room.
Access code
(8 digits from 0 to 9)
[free text]
An empty field means that no code query is
done
Automatic name
Languages 1...6
[free text]
Transfer the following parameters
No • Yes
Use indoor temperature
No • Yes
Start ventilation from (in 0.1°C)
only if ventilation based on indoor
temperature
(Hysteresis = 2°C)
50...400; 220
Use air humidity
No
• Yes
Start ventilation from (in % rH)
only if ventilation based on air humidity
(Hysteresis = 3%)
10...95; 60