Automatic functions
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
The
supply temperature block
prevents ventilation if it is warmer outside than
inside.
Set the
rotational speed range
you wish to use for ventilation.
Select the periods for
night-time re-cooling
. Activate and define periods you would
like to use here in the "weekly timer" menu first!
The
outdoor temperature lock
prevents ventilation when it is cold outside (e. g.
protection of plants against cold). The block only applies to automatic mode, manual
operation is still possible.
Select the
periods
when you want to activate the ventilation. Activate and define
periods you would like to use here in the "weekly timer" menu first!
The
ventilation block
is activated when cooling is switched on (object no. 608
"Automatic cooling status" = 1) and prevents ventilation. However, the fan may be
restarted manually immediately.
Use CO
2
No
• Yes
Start ventilation from above (in 10 ppm)
only if ventilation based on CO
2
value
50...200; 80
Stop ventilation from below (in 10 ppm)
only if ventilation based on CO
2
value
50...200; 55
Terminate ventilation if the supply air
temp. is higher than the room temperature
No
• Yes
Start exhaust ventilation at (in %)
1...100; 10
and increase exhaust ventilation to (in %)
1...100; 80
Use night-time re-cooling for
Period 1 - 16
No
• Yes
Ventilate until room temperature
falls below (in 0.1°C)
50...500; 160
Ventilate at level (in %)
0...100; 30
Use outdoor temperature block
No
• Yes
Close when below (in 0.1°C)
if temperature block is used
-100...200; 50
Use timed ventilation for
Period 1 - 16
No
• Yes
Ventilate at level (in %)
only for timed ventilation
1...100; 50
Use ventilation lock
No
• Yes
Summary of Contents for Corlo Touch KNX 70258