112
Automatic functions
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
Sun position angle
5.4.
Automatic window mode
ETS: Automatic X (window)
Windows may be configured with or without gradual opening (opening step by step).
5.4.1. Set bus communication
First, configure a lock via a blocking object.
Due to the "change to manual mode if the feedback value does not correspond to the set
point value", changes caused by external switches are still registered in the system. Set
the parameter to "yes", if all actuators of this channel are to be set to "manual", if the
object "AutoX ... feedback" does not correspond to the set point value. This means that
the automatic mode is inactive until the next automatic reset.
It is therefore advisable to set the parameters to "no" if many actuators are controlled
via this channel. In this case, the information about "manual/automatic" should be
processed by each actuator individually.
Several different objects allow an external evaluation and use of the window status.
All sides
greater than 0°
smaller than 360°
West
greater than 180°
smaller than 360°
South-West
greater than 135°
smaller than 315°
South
greater than 90°
smaller than 270°
South-East
greater than 45°
smaller than 225°
East
greater than 0°
smaller than 180°
Window type
• without gradual opening
• with gradual opening
Number of steps
only for gradual opening
2...10; 5
Evaluation of the blocking object
Blocking objects no. 615/650/685/720/755
"AutoX ... block"
• 1 = block | 0 = release
• 0 = block | 1 = release
Blocking object value before 1st
communication
0 • 1
Action after locking
• Execution of last automatic command
• Waiting for next automatic command
Switch to manual if feedback value
deviates from automatic set point value.
Objects no. 636/667/702/737/772
"AutoX ... feedback"
No • Yes