Automatic functions
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
Eco set point
Eco mode is usually used for night mode.
If set point values are entered separately:
A starting set point value is defined as well as a temperature range in which the
nominal value may be modified.
If the comfort set point value is used as a basis:
If the comfort set point value is used as a basis, the deviation from this value is set.
Set point values for frost/heat protection (building protection)
The building protection mode is used during longer absences. Set points for frost
protection (heating) and heat protection (cooling) are determined which may not be
modified from outside (no access via operating devices etc.). The building protection
mode may be activated with delay, which allows you to leave the building before the
controls switch to frost/heat protection mode.
General variables
This setting appears for the control types "Heating
and
Cooling" only. This is where
you can decide whether to use a common variable for heating and cooling. If the 2nd
level has a common variable, this is also where you determine the control mode of the
2nd level.
Initial heating/cooling set point (in 0.1 °C)
valid till 1st communication
-300…800; 210
Min. object value heating/cooling (in 0.1
°C)
-300…800; 160
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280
Reduce nominal heating value (in 0.1°C)
for heating
0…200; 50
Increase nominal cooling value\r\n (in
0.1°C)
for cooling
0…200; 60
Nominal value frost protection\r\n (in 0,1°C)
-300…800; 70
Nominal value heat protection (in 0,1°C)
-300…800; 350
Activation delay
no • 5 s • ... • 5 min • … • 2 h
For heating and cooling
• separate variables are used
• common variables are used for
Level 1
• common variables are used for
Level 2
• common variables are used for
Level 1+2
Use actuating variable for 4/6-way valve
Yes • No