Automatic functions
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
5.5.
Automatic fan mode
Automatic control and manual operation of fans is only possible if the
Display Corlo
Touch KNX
receives feedback about the current exhaust air level from the fan
actuator.
ETS: Automatic X (fan)
5.5.1. Set bus communication
First, configure a lock via a blocking object.
Due to the "change to manual mode if the feedback value does not correspond to the
set point value", changes caused by external switches are still registered in the system.
Set the parameter to "yes", if all actuators of this channel are to be set to "manual", if
the object "AutoX ... feedback" does not correspond to the set point value. This means
that the automatic mode is inactive until the next automatic reset.
It is therefore advisable to set the parameters to "no" if many actuators are controlled
via this channel. In this case, the information about "manual/automatic" should be
processed by each actuator individually.
The "Status outdoor temperature block" object allows an external evaluation and use
of the fan status.
5.5.2. Changing basic parameters
Select "Transmit the following parameters: Yes" to render the modifications valid.
Previous settings are then overwritten - including modifications done on the display!
You may want to enter an access code for the automatic fan settings on the display.
The code is requested before the automation menus are shown.
Evaluation of the blocking object
Blocking objects no. 615/650/685/720/755
"AutoX ... block"
• 1 = block | 0 = release
• 0 = block | 1 = release
Blocking object value before 1st
communication
0 • 1
Action after locking
• Execution of last automatic command
• Waiting for next automatic command
Switch to manual if feedback value
deviates from automatic set point value.
Objects no. 636/667/702/737/772
"AutoX ... feedback"
No • Yes
Use status objects for
outdoor temperature block
Objects no. 626/661/696/731/766 "AutoX
window status outdoor temperature block"
No • Yes
Transfer the following parameters
No • Yes