System settings via touch display

Display Corlo Touch KNX

 • Status: 09.03.2017 • Technical changes and errors reserved.

Then use the 

Next

 

 key (bottom right) to skip to the next setting.

Then use the 

Next

 

 key (bottom right) to skip to the next setting.

Then use the 

Next

 

 key (bottom right) to skip to the next setting.

Set the alarm duration. 

Scroll to the desired setting using the +/-
buttons on the rocker.

Determine the snooze period (in minutes)
after which the alarm should be repeated.
Select "none" if the alarm is not to be
repeated. 

Scroll to the desired setting using the +/-
buttons on the rocker.

Switch the alarm tone 

ON

 or 

OFF

.

Summary of Contents for Corlo Touch KNX 70258

Page 1: ...rloTouch KNX CorloTouch KNX WL Display andTouch Switch Item numbers CorloTouch KNX WL 70252 white Chrome glossy 70253 black Chrome glossy 70254 white Chrome matt 70255 black Chrome matt 70334 white wh...

Page 2: ......

Page 3: ...ional start up 12 1 3 Addressing the device 13 1 4 Setting up the WLAN connection 13 1 4 1 WLAN settings in the ETS 13 1 4 2 Displaying WLAN status on the display 13 1 5 Maintenance and care 14 1 6 Lo...

Page 4: ...tion 58 3 5 Ambient lighting 58 3 5 1 Brightness 59 3 5 2 Colour 61 3 6 Button tone 62 3 7 Alarm 64 3 8 Timer 66 3 9 Alarm 67 3 10 Service 70 3 10 1 Reset the access code 70 3 10 2 Reset the system to...

Page 5: ...he shading 107 Sun position angle 112 5 4 Automatic window mode 112 5 4 1 Set bus communication 112 5 4 2 Changing basic parameters 113 5 4 3 Setting the window automation 114 Setting the window venti...

Page 6: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Page 7: ...5 Description Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved 1 Description...

Page 8: ...uch KNX WL model you can display predefined web pages using the WLAN connection You enter URL addresses in the ETS Icons for display can be exchanged symbol library in the device own pictures from by...

Page 9: ...ection Opening angle x 75 to 75 typ Opening angle y 55 to 75 typ Colors White glass bright chromed edge White glass matt chromed edge Black glass bright chromed edge Black glass matt chromed edge Whit...

Page 10: ...n when ambient and logo lighting off display brightness 50 approx 0 6 W in standby operation when ambient and logo lighting off display off was measured with 24 V auxiliary voltage Power consumption C...

Page 11: ...pose Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims After unpacking the device check it immediately for possible mechanical d...

Page 12: ...h a separation of 71 mm must be placed accordingly The frames must be installed vertically Overall dimensions with frame Single approx 80 mm x 81 mm W x H Dual approx 80 mm x 153 mm W x H Triple appro...

Page 13: ...s longitudinal holes the frame can alternatively be bolted via the four outside holes e g for boxes from Swiss systems or other installation systems Fig 5 The display unit can now be put in place The...

Page 14: ...ust not exceed a relative air humidity of 95 Avoid condensation After the operating voltage has been applied the device will enter an initialisation phase lasting a few seconds During this phase no in...

Page 15: ...the WLAN setting section in the manual ETS System Settings WLAN 2 13 1 WLAN You set the network name and the encryption for compatibility with the WLAN network access point The IP address allocation c...

Page 16: ...idual images 1 6 1 Images for screensaver The setting of the screen saver is described in the manual chapters 2 4 Display ETS and 3 4 4 Screen saver Display Images that are shown as the screensaver mu...

Page 17: ...so that they can be called up in the ETS and in the menu 0001 9999 1 6 3 Exchanging images and graphics For the Corlo Touch KNX display pages a large number of icons from the area of security multimed...

Page 18: ...of the Corlo Touch KNX is only active after the current time has been received from the bus 1 7 1 An overview of the automatic functions The Display Corlo Touch KNX has five automatic channels which m...

Page 19: ...rature Wind protection retraction when a pre set wind speed is exceeded Rain protection retraction during precipitation Automatic resets time periods can be set Window In order to control the windows...

Page 20: ...eriods can be set Heating and cooling For the control of heating cooling the ambient parameter measuring value Indoor temperature is needed Heating and cooling can be set in two degrees 1 Level PI con...

Page 21: ...ngs Yes Yes Interface assignment Yes Temperature threshold values Yes Scenes Yes Logic Yes Access codes Yes modification reset only No Name Function DPT Length in byte Flags 1 Software version Output...

Page 22: ...W T 24 Ambient lighting green ratio in Input Output 5 001 1 C R W T 25 Ambient lighting blue ratio in Input Output 5 001 1 C R W T 26 Ambient lighting RGB Input Output 232 600 3 C R W T 27 Reserve 28...

Page 23: ...e 1 area 1A Input Output 16 000 14 C R W T 102 Page 1 area 1B Output 1 010 1 C R T 103 Page 1 area 1C Input 5 001 1 C W 104 Page 1 area 1D Input 5 001 1 C W 105 Page 1 area 2A Input Output 16 000 14 C...

Page 24: ...1 C R W T 137 Page 1 Rocker 1 Feedback Input 1 001 1 C W 138 Page 1 Rocker 2 Long term Output 1 008 1 C R W T 139 Page 1 Rocker 2 Short term Output 1 010 1 C R T 140 Page 1 Rocker 2 Position Input 5...

Page 25: ...nside temp meas value Input 9 001 2 C W 602 Automatic inside humidity meas value Input 9 007 2 C W 603 Automatic CO2 meas value in ppm Input 9 008 2 C W 604 Automatic wind measuring value Input 9 005...

Page 26: ...ic X Wind warning Output 1 001 C R T 620 655 690 725 760 Automatic X Frost warning Output 1 001 C R T 621 656 691 726 761 Reserve 622 657 692 727 762 Reserve 623 658 693 728 763 Reserve 624 659 694 72...

Page 27: ...Temp controller Current set point Output 9 001 C R T 617 652 687 722 757 Temp controller Switching object 0 Heating 1 Cooling Input 1 002 C W 618 653 688 723 758 Temp controller Set point comfort hea...

Page 28: ...troller Control variable heating level 1 Output 5 001 C R T 631 666 701 736 771 Temp controller Control variable Heating level 2 Output 5 001 C R T 632 667 702 737 772 Temp controller Control variable...

Page 29: ...itching output Output 14 4 C R T 798 Period 8 Switching output Output 14 4 C R T 799 Period 9 Switching output Output 14 4 C R T 800 Period 10 Switching output Output 14 4 C R T 801 Period 11 Switchin...

Page 30: ...on 1 8 bit encoder Output 5 1 C R T 856 Button 1 16 bit encoder Output 9 2 C R T 857 Button 1 Scene Output 18 001 1 C R T 858 Button 2 Extended Output 1 008 1 C R T 859 Button 2 Brief Output 1 010 1 C...

Page 31: ...2 C R T 896 Temp_sensor_2 external measuring value Input 9 001 2 C W 897 Temp_sensor_2 overall measuring value Output 9 001 2 C R T 898 Temp_sensor_2_malfunction Output 1 001 1 C R T 899 Temp_sensor_3...

Page 32: ...Input 7 005 2 C W 932 Temp threshold value 2 Switching delay from 1 to 0 Input 7 005 2 C W 933 Temp threshold value 2 Switching output Output 1 001 1 C R T 934 Temp threshold value 2 Switching output...

Page 33: ...002 1 C W 977 Logic input 7 Input 1 002 1 C W 978 Logic input 8 Input 1 002 1 C W 979 Logic input 9 Input 1 002 1 C W 980 Logic input 10 Input 1 002 1 C W 981 Logic input 11 Input 1 002 1 C W 982 Log...

Page 34: ...1 8 bit output A Output 5 010 1 C R T 1009 OR Logic 1 8 bit output B Output 5 010 1 C R T 1010 OR Logic 1 Block Input 1 001 1 C W 1011 OR Logic 2 1 bit switching output Output 1 002 1 C R T 1012 OR Lo...

Page 35: ...33 System settings via ETS Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved 2 System settings via ETS...

Page 36: ...e objects Via object no 10 the date and the time are requested from the bus As soon as the data is available on the bus the query cycle is reset regardless of whether the query was generated autonomou...

Page 37: ...guage object may be activated in the ETS Adaptation on the display The language settings on the display is done via the menu Settings system system language and can be secured with an access code set...

Page 38: ...he ETS Adaptation on the display The language settings on the display is done via the menu Settings system editable text language and can be secured with an access code set up in the ETS System settin...

Page 39: ...d for the time period set here Object control For the display settings via objects i e via the bus objects 14 18 and 21 are available The display object may be activated in the ETS The following param...

Page 40: ...ddition you can set the options for what is to happen if no setting is entered on the display for 5 minutes Independently of the automatic shut down you may select an individual screen saver This scre...

Page 41: ...y be made via objects on the display or on the ETS menu ETS ambient lighting Object control For the settings via objects i e via the bus objects 22 26 are available The ambient lighting objects may be...

Page 42: ...be modified via objects no 23 25 ambient lighting shares red green blue in or no 26 ambient lighting RGB via the bus depending on the parameter setting RGB shares are set via The objects are input and...

Page 43: ...isplay The settings on the display are modified via the menu Settings system button tone and can be secured with an access code set up in the ETS System settings via touch display Button tone Page 62...

Page 44: ...ed Alarm messages may be acknowledged with the button shown on the display or via the bus For this purpose decide whether to use a 1 or a 0 for the acknowledgement The alarm functions use objects no 5...

Page 45: ...ure of blinds The respective period objects no 791 to 806 can be configured as inputs or outputs i d send to the bus timer via Corlo Touch KNX also for other bus members or be switched from there time...

Page 46: ...y timer periods 1 16 Select Transmit the following parameters Yes to render the modifications valid Previous settings are then overwritten including modifications done on the display The timer menu on...

Page 47: ...and thus may both receive a status change or transmit the status to the bus autonomously This means that the alarm clock may also be activated switched or set to snooze from for example a different l...

Page 48: ...in the menu Settings system service by selecting the button reset to last ETS download System settings via touch display Service Page 70 Object value for alarm acknowledgement Object no 83 alarm cloc...

Page 49: ...es and errors reserved The reset to ETS download may be protected with a code Select Transmit the following parameters Yes in the ETS to modify the code Transfer the following parameters Yes No Access...

Page 50: ...48 System settings via ETS Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved...

Page 51: ...49 System settings via touch display Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved 3 System settings via touch display...

Page 52: ...You can call up the system settings via the tool symbol on the display screens The symbol can be set to visible or hidden when the display screens are adapted If you want to allow system modifications...

Page 53: ...object no 5 access code reset 3 2 System language The language used for the settings menu may be selected in the menu Settings system system language The menu can be secured with an access code Access...

Page 54: ...ess codes for display menus Page 50 Confirm with OK to save and return to the previous menu selection Or cancel using the skip back arrow or the house button 3 4 Display 3 4 1 Cleaning mode For cleani...

Page 55: ...atus 09 03 2017 Technical changes and errors reserved 3 4 2 Screen options Screen options can be adapted in the menu Settings system screen The menu can be secured with an access code Access codes for...

Page 56: ...e set to a fixed value setting OFF Setting using the internal brightness sensor setting according to room brightness Setting via the KNX bus this setting can only be selected if pre set in the ETS If...

Page 57: ...Screen saver The screen saver is displayed if the display has not been touched for a pre set period of time Settings system screen Then use the Next key bottom right to skip to the next setting If the...

Page 58: ...isplay as screen savers have to be saved on an SD card that remains in the device Please refer to the chapter Images for screensaver Page 14 The screen saver may be linked to the proximity sensor Sele...

Page 59: ...ch screen is shown on the display when you press the house button and after a reset Settings system screen Confirm with OK to save and return to the previous menu selection Or cancel using the skip ba...

Page 60: ...n 3 5 Ambient lighting The Display Corlo Touch KNX has LEDs installed which are directed to the side from behind the frame This ambient lighting can be adjusted in terms of colour and brightness The l...

Page 61: ...ing the arrow keys on the rocker Then use the Next key bottom right to skip to the next setting The brightness may be set to a fixed value setting OFF Adapted to the screen brightness as screen bright...

Page 62: ...r the house button without saving If the brightness value is fixed and the control is done via the KNX bus brightness or start brightness can be set in percent Scroll to the desired setting using the...

Page 63: ...e Next key bottom right to skip to the next setting The colour may be set to a fixed value which is set via RGB fixed value which is set via the colour wheel Adapted to the logo colour as logo illumin...

Page 64: ...he house button without saving 3 6 Button tone The Display Corlo Touch KNX may emit a sound if a button on the display is touched This button tone can be switched on or off in the menu Settings system...

Page 65: ...via touch display Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved Confirm with OK to save and return to the previous menu selection Or cancel using the skip back arrow...

Page 66: ...an alarm tone emitted The alarm can be acknowledged directly on the display or via the bus The reaction upon an alarm may be adapted in the menu Settings system alarm The menu can be secured with an a...

Page 67: ...the first setting Then use the Next key bottom right to skip to the next setting Then use the Next key bottom right to skip to the next setting Select the alarm function you with to modify 1 6 Scroll...

Page 68: ...the ETC menu weekly timer period Periods configured as outputs may also be modified on the display Periods configured as inputs only receive the time settings from another time in the bus system Only...

Page 69: ...itched off manually it stops by itself after the set alarm time is reached Alternatively the wake up call can be switched off via the bus After the Select the period you wish to modify Only the period...

Page 70: ...the settings menu Settings system alarm clock The menu can be secured with an access code Access codes for display menus Page 50 Then use the Next key bottom right to skip to the next setting If the a...

Page 71: ...om right to skip to the next setting Then use the Next key bottom right to skip to the next setting Set the alarm duration Scroll to the desired setting using the buttons on the rocker Determine the s...

Page 72: ...bout the device software versions read the license text access the internal area manufacturer service only 3 10 1 Reset the access code All codes may be reset to the level of the last ETS download via...

Page 73: ...5 Info This is where you can find the KNX software version information the display software version and the operating system software version Settings system service info 3 10 6 License Here you can f...

Page 74: ...72 System settings via touch display Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved...

Page 75: ...73 Set up display screens Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved 4 Set up display screens...

Page 76: ...set up menus and after a reset In addition you may set the starting screen to be displayed if no entry is made on the display for 5 minutes 4 2 Setting up screens in the ETS ETS menu Screens 1 10 The...

Page 77: ...dapted Area Select a name for this function A name can be selected for each of the six available languages max 15 characters Editable text language Page 36 Transfer with download Access code Yes No Ac...

Page 78: ...ating point Display 32 bit counter without math symbol Display 32 bit counter with math symbol Display 32 bit floating point Display text Display energy DPT 29 01X Input 1 Input 0 Press enter 1 releas...

Page 79: ...me for this function A name can be selected for each of the six available languages max 15 characters Editable text language Page 36 Select the rocker function Set time requirements for each function...

Page 80: ...2 in 10ms Only for long term short term 0 200 Display movement position Only for long term short term Yes No Display slat position Only for long term short term Yes No Button symbol for 1 0 no symbol...

Page 81: ...ction Temperature function RGB control function 8 bit value function 0 255 0 100 0 360 Name Languages 1 6 free text Function see above Rotary control functions Rotary control symbol no symbol symbol 1...

Page 82: ...32767 Resolution observe settings range 1 60000 10 1 30000 10 Start value 0 65535 32768 32767 0 Text for unit free text Minimum value in 0 1 2147483648 Maximum value in 0 1 2147483647 Resolution in 0...

Page 83: ...s shown are examples areas rockers and rotary control labels may be customized 0 Do not use Maximum value in 0 1 2147483647 Resolution in 0 1 observe settings range 1 2000000000 10 Conversion factor a...

Page 84: ...lo Touch KNX Status 09 03 2017 Technical changes and errors reserved 5 three surfaces vertical 6 four surfaces 7 six surfaces 8 single rocker vertical 9 single rocker vertical left one surface 10 sing...

Page 85: ...errors reserved 11 single rocker vertical left two surfaces 12 single rocker vertical centre two surfaces 13 single rocker vertical right two surfaces 14 single rocker vertical left four surfaces 15...

Page 86: ...changes and errors reserved 17 double rocker vertical 18 double rocker vertical one surface left 19 double rocker vertical one surface centre 20 double rocker vertical one surface right 21 double roc...

Page 87: ...es and errors reserved 23 double rocker vertical two surfaces right 24 single rocker horizontal 25 single rocker horizontal top one surface 26 single rocker horizontal bottom one surface 27 single roc...

Page 88: ...o Touch KNX Status 09 03 2017 Technical changes and errors reserved 29 double rocker horizontal 30 triple rocker vertical 31 rotary control 32 rotary control one surface vertical 33 rotary control roc...

Page 89: ...rary of the Corlo Touch KNX the following symbols are predefined Lighting 35 rotary control one surface bottom 36 rotary control two surfaces right 37 rotary control with display at top 38 rotary cont...

Page 90: ...loor light on 0012 Floor light off 0013 Floor luminaire on 0014 Floor luminaire off 0015 Table lamp o 0016 Table lamp off 0017 Bulb on 0018 Bulb off 0019 Indirect lamp on 0020 Indirect lamp off 0031 S...

Page 91: ...ight closed 0049 Light dome open 0050 Light dome closed 0071 Rotary control heating 0072 Rotary control Light 0073 Rotary control ventilation 0074 Rotary control Colour 0081 Display black 0082 Display...

Page 92: ...ow up 0098 Operating arrow down 0099 Skip back 0100 Skip forward 0101 Plus 0102 Minus 0103 Tool 0104 Switch on 0105 Switch off 0106 On Off 0107 Standby 0108 Clock 0109 Manual 0110 Automatic 0111 OK 01...

Page 93: ...y 0123 Scene 0126 Radiator on 0127 Radiator off 0128 Floor heating 0129 Wall heating 0130 Ceiling heating 0131 Floor cooling 0132 Wall cooling 0133 Ceiling cooling 0134 Night time reduction 0135 Absen...

Page 94: ...d Sensors 0146 Heating minus 0147 Cooling 0156 Sun 0157 Precipitation 0158 Tank 0159 Pyranometer 0160 Air humidity 0161 Earth moisture 0162 Outside temperature 0163 Inside temperature 0164 Fountain 01...

Page 95: ...88 Projector screen 0189 Socket 0190 Music 0191 Play 0192 Pause 0193 Rewind 0194 Fast Forward 0195 Stop 0196 Forward 0197 Back 0198 Loudspeaker 0199 Volume up 0200 Volume down 0216 Motion detector 021...

Page 96: ...9 03 2017 Technical changes and errors reserved House 0236 House 0237 Dining room 0238 Living room 0239 Kitchen 0240 Children s room 0241 Bathroom 0242 Bedroom 0243 Cloakroom 0244 Garage 0245 Carport...

Page 97: ...95 Automatic functions Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved 5 Automatic functions...

Page 98: ...ed windows or sliding roofs Humidity sensitive items should therefore not be placed in an area where they might be damaged by incoming precipitation Please also bear in mind that in the event of a pow...

Page 99: ...levation or be calculated within the system The type of the sun position objects 2 or 4 byte depends on the device sending the values For the calculation of the sun position information about the loca...

Page 100: ...A Sun elevation will be Calculated Received via communication objects Location input using City Coordinates E longitude degrees 180 180 180 180 9 E longitude Minutes 59 59 59 59 10 N latitude Degrees...

Page 101: ...matic channels shall move to a safe position Wind alarm If the wind threshold value for an automatic channel is exceeded a 5 minute wind warning is triggered if the wind value is exceeded once more du...

Page 102: ...out interruption the set reaction for short is activated e g the slats are opened Only if the light intensity is uninterruptedly under the threshold value for the duration of the retraction delay long...

Page 103: ...st alarm for blinds and windows will be active when during or after precipitation the outdoor temperature falls below a defined level The frost alarm is triggered in the following situations The outdo...

Page 104: ...he respective automatic channel always remains in manual mode automatic mode is deactivated At the time of the daily automatic reset the channels may be returned to automatic mode In addition you may...

Page 105: ...t the following parameters Yes to render the modifications valid Previous settings are then overwritten including modifications done on the display You may want to enter an access code for the automat...

Page 106: ...tic mode for blinds and awnings offers the same setting options For shutters there is the additional slat setting option ETS Automatic X shutters awnings blinds 5 3 1 Set bus communication First confi...

Page 107: ...ation and use of the shade status The safety object links frost wind and precipitation alarm with OR Use with alarm object Yes activates separate objects for frost wind and precipitation warnings Bloc...

Page 108: ...n automatic shading mode 1 Alarm functions Alarm functions are used for shades in manual and in automatic mode In case of frost wind or precipitation alarm shades are retracted and may not be extended...

Page 109: ...he slats of shutters may always follow the sun position Shading may be opened and closed based on a timer closed during the night and operated manually You may set a separate heat protection position...

Page 110: ...or temperature is for example under the set value in the morning the shades remain retracted despite the sun As soon as the set indoor temperature is exceeded the block is lifted and the shade release...

Page 111: ...n order to reliably prevent damage due to ice use the frost alarm function Note Time coordinated night closure function and outdoor temperature block If the outdoor temperature is below the blocking t...

Page 112: ...osition in 0 100 75 Slat position Does not track the sun Tracks the sun From a brightness of in kLux 1 99 40 Sun direction Sun position angle Page 112 All sides West South West South South East East A...

Page 113: ...iod for shades after a wind alarm are determined in the Automation menu Frost alarm Page 101 and Wind alarm Page 99 Finally activate or deactivate the automatic resets for this shading channel Heat pr...

Page 114: ...eters to no if many actuators are controlled via this channel In this case the information about manual automatic should be processed by each actuator individually Several different objects allow an e...

Page 115: ...ected for each of the six available languages max 15 characters Editable text language Page 36 Use status objects for outdoor temperature block Objects no 626 661 696 731 766 AutoX window status outdo...

Page 116: ...ty is granted to timed closure followed by outdoor temperature blocks keep closed timed ventilation open supply air temperature block keep closed and night time re cooling open This means that e g tim...

Page 117: ...r temperature block alarm has priority over blocking temperature Manual operation continues to remain possible even when the window is blocked because of low outdoor temperatures Select the periods du...

Page 118: ...ipitation alarm are maintained for 5 minutes Conditions for frost alarm and the delay period for the ventilation block are determined in the Automation menu Ventilation lock Page 101 and Frost alarm P...

Page 119: ...is case the information about manual automatic should be processed by each actuator individually The Status outdoor temperature block object allows an external evaluation and use of the fan status 5 5...

Page 120: ...ntilation or night time re cooling will only occur when the outdoor temperature exceeds the pre set value for the outdoor temperature block Ventilation automation according to temperature air humidity...

Page 121: ...y timer Page 43 The ventilation block is activated when cooling is switched on object no 608 Automatic cooling status 1 and prevents ventilation However the fan may be restarted manually immediately U...

Page 122: ...omfort when present Standby during short absences Eco as a night time mode and Frost heat protection building protection during longer absences The settings for the temperature control include the set...

Page 123: ...a message does not reach a recipient You may also set up periodical monitoring by the actuator with this setting The status object shows the current status of the output variable 0 OFF 0 ON and may f...

Page 124: ...ogramming This also applies to a comfort extension The control may be manually reset to comfort mode from eco or night mode This allows the user to maintain the daily nominal value for a longer time e...

Page 125: ...t point value is defined as well as a temperature range in which the nominal value may be modified If the comfort set point value is used as a basis If the comfort set point value is used as a basis t...

Page 126: ...building before the controls switch to frost heat protection mode General variables This setting appears for the control types Heating and Cooling only This is where you can decide whether to use a c...

Page 127: ...which reaches maximum variable value i e the point at which maximum heating power is activated The reset time shows how quickly the controls react to deviations from the set point value In case of a s...

Page 128: ...In case of a common variable for heating and cooling 0 is always transmitted as a fixed value 2 point rule only level 2 The 2 point rule is used for systems which are only set to ON or OFF When blocke...

Page 129: ...level 2 the set point deviation between the two levels must furthermore be determined i e the highest set point value from which the 2nd level is then added when values exceed this set point PI contro...

Page 130: ...g Now determine what should be transmitted when the control is blocked Upon release the control variable follows the rule again 2 point rule only level 2 The 2 point rule is used for systems which are...

Page 131: ...ntage off should be used Now determine what should be transmitted when the control is blocked Upon release the control variable follows the rule again In case of a common variable for heating and cool...

Page 132: ...130 Automatic functions Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved...

Page 133: ...131 Additional settings ETS Display Corlo Touch KNX Status 09 03 2017 Technical changes and errors reserved 6 Additional settings ETS...

Page 134: ...nput select the bus function Switch and specify which value is sent when pressing releasing the button and when it will be sent Use interface 1 2 3 4 No Yes Bus function Switch Changeover switch Shutt...

Page 135: ...bus function Dimmer and specify the button function time interval switching dimming and if requested the repeat interval for a long button press Bus function Selector switch Command when pressing the...

Page 136: ...t set the behaviour malfunction object transmission behaviour and mixed value calculation here If the measuring values of the sensor should deviate from the actual temperature values e g in case the i...

Page 137: ...comfort mode pushing the button briefly a bit longer and long will trigger different responses of the drive The time intervals are set individually By pushing the button shorter than adjustable time 1...

Page 138: ...NTC at an input using the temperature threshold values and then activate output objects accordingly ETS Temperature thresholds Point in time 0 Push of button start of time 1 Release before time 1 exp...

Page 139: ...smission behaviour for the output Use threshold values 1 4 No Yes Threshold value setting via Parameter Communication object Threshold value in 0 1 C 300 800 200 Hysteresis of the threshold value in 0...

Page 140: ...f objects are delayed via yes objects valid till 1st communication No 5 s 2 h Delay from 1 to 0 if objects are delayed via yes objects valid till 1st communication No 5 s 2 h Switching output transmit...

Page 141: ...to 60 for the guests scene 6 4 Logic ETS The Corlo Touch KNX provides 16 logistics inputs four logic gates with AND and four with OR ETS Logic Activate the logic inputs and assign object values up to...

Page 142: ...A Shade position Height 0 safe position 255 fully extended Object B Shade position slat angle 255 100 closed 200 approx 80 closed AND logic output 1 4 Not active Active OR logic output 1 4 Not active...

Page 143: ...ng output On block do not transmit message transmit value for logic 0 transmit value for logic 1 On release with 2 seconds release delay Dependent on the Switching output transmits setting Switching o...

Page 144: ...60184 white 60185 60189 black WS1 Style PF 60191 60194 white 60196 60199 black WS1000 Style 60201 60204 white 60206 60209 black WS1000 Style PF 60211 60214 white 60216 60219 black Elsner Elektronik Gm...

Reviews: