120
Automatic functions
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
Finally, activate or deactivate the
automatic resets
for this fan channel.
5.6.
Temperature controller
Due to the temperature control, heating and cooling may be controlled in two levels.
ETS: Automatic X (temperature control)
General regulation
You may want to enter an access code for the automatic fan settings on the display.
The code is requested before the automation menus are shown. Select "Transmit the
access code: Yes" to render the modifications valid.
Note:
There are no automation menus available in version 0.1 of the display software!
For an adequate regulation of the indoor temperature, comfort, standby, eco and
building protection modes may be used.
Comfort
when present,
Standby
during short absences,
Eco
as a night-time mode and
Frost/heat protection
(building protection) during longer absences.
The settings for the temperature control include the set point temperatures for the
individual modes. Objects are used to determine which mode is to be selected. A
change of mode may be triggered manually or automatically (e.g. by a timer, window
contact).
The
mode
may be switched with two 8 bit objects of different priority. Objects
"... HVAC mode (Prio 2)" for switching in everyday operation and
"... HVAC mode (Prio 1)" for central switching with higher priority.
The objects are coded as follows:
Perform Automatic Reset
at set time
No
• Yes
After the input waiting period following
manual operation
No
• Yes
Transmit access code
No
• Yes
Access code
(8 digits from 0 to 9)
[free text]
An empty field means that no code query is
done
ID
Name
Encoding
Range
Use
20,102
DPT_HVACMode
field1 = HVACMode
0 = Auto
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
[0 … 4]
HVAC